Claim denied under faulty workmanship exclusion for cyclone damage to roller doors and wall
Text of the determination
Determination
General Insurance - Small Business/Farm Insurance - Commercial Property - FSP
Decision - Denial of claim-Exclusion/ condition
Determination
Case No: 383958 Determination Page 1 of 8
Case number : 383958 1 2 March 2015
1 Overview
1.1 Dispute
The Applicant held a business insurance policy with the Financial Services
Provider (FSP) which provided cover for an industrial property owned by the
Applicant.
The Applicant lodged a claim under the policy for damage to roller doors and a
wall at the property, following a cyclone in December 2013. The Applicant
incurred costs of $120,890 to replace the damaged roller doors and repair the
wall.
The FSP denied the claim on the basis that the majority of the damage to the
roller doors was due to the incorrect manner in which they had been installed,
rather than the cyclone itself. The FSP says that the remaining damage was pre-
existing and caused by factors unrelated to the cyclone.
1.2 Issues and key findings
Is the FSP liable for the damage to the Applicant’s property ?
The Applicant has established a prima facie claim for cyclone damage under the
policy. However, the available information (including the engineers’ reports)
establishes that the bulk of the damage to the roller doors was caused by the
doors not having been installed in accordance with the manufacturer’s
specifications. Damage caused in this manner is not covered under the policy.
The FSP has not established that it is entitled to rely on a policy exclusion for the
damage to the wall of Shed 1 and the middle roller door in Shed 4. However, on
balance, the cost of repairing this damage does not exceed the cyclone excess of
$20,000.
Is the Applicant entitled to reimbursement of professional costs?
The Applicant is not entitled to reimbursement of its professional costs as the
work performed did not assist the Applicant in establishing its claim.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is not liable for the Applicant’s claim .
Case No: 383958 Determination Page 2 of 8
2 Reasons for Determination
2.1 Is the FSP liable for the damage to the Applicant’s property ?
Applicant has established prima facie claim
The Applicant is required to show that, on the balance of probabilities, it has
suffered a loss caused by a risk insured against under the policy. This is known
as a prima facie claim.
If the Applicant is able to establish a prima facie claim, then the onus shifts to the
FSP to show that, on the balance of probabilities, it is entitled to rely on an
exclusion under the policy to deny the claim.
The Applicant ’ s policy provides cover for damage to the insured property caused
by the events listed in the policy (including storm and wind), subject to the
conditions and exclusions set out in the policy.
The FSP accepts that there was a tropical cyclone in the vicinity of the Applicant’s
property. The reports provided by the FSP’s cont ractors (and the photographs
included therein) confirm that the roller doors and wall at the property sustained
extensive damage due to the effects of the strong winds experienced during the
cyclone.
On this basis, the Panel is satisfied that the Applicant has established a prima
facie claim under the policy.
In these circumstances, the FSP bears the onus of establishing that, on the
balance of probabilities, it is entitled to rely on a policy exclusion to deny the
Applicant’s claim.
Policy contains exclusion for damage caused by faulty work
The FSP says that it is not liable for the damage to the roller doors, as the strong
winds experienced during the cyclone would not have damaged the doors, had
they been properly installed in accordance with the manufact urer’s guidelines.
Accordingly, the FSP says that it is entitled to rely on the general exclusion under
the policy for damage caused by faulty workmanship to deny the Applicant’s
claim.
In order to establish that the exclusion applies, the FSP must show that, on the
balance of probabilities, the proximate cause of the damage to the Applicant’s
property (that is, the real, effective or dominant cause) was the faulty installation
of the roller doors.
Proximate cause of bulk of damage was faulty installation of roller doors
Having carefully reviewed the available information, the Panel is satisfied that, on
the balance of probabilities, the proximate cause of the bulk of the damage to the
roller doors was the fact that the doors were not installed in accordance with the
manufacturer’s guidelines.
Case No: 383958 Determination Page 3 of 8
The reports prepared by the various contractors (and the photographs contained
therein) establish that six of the nine roller doors installed in sheds at the property
sustained extensive damage by way of track fixing failure and/or curtain
deformation (that is, bowing of the metal door curtain or crimping and buckling of
the curtain ribs).
After the FSP denied his claim, the Applicant engaged an engineer (BH) to report
on whether the roller doors were suitable for their intended purpose at the time
they were installed, in light of the damage suffered during the cyclone.
In his report, BH concluded that most of the damage to the roller doors had
occurred as a result of the doors not having been correctly installed, due to
inadequate track fixings.
BH noted that the fixings (tek screws) used to attach the door tracks to the door
frame had been installed every 500 millimetres (at best), whereas the
manufacturers’ specifications req uire the screws to be installed every 150
millimetres (based on a door curtain width of five metres). The copy of the
manufacturer’s specifications attached to BH’s report confirms this requirement.
The Applicant says that BH’s report should not be relied on to determine the
proximate cause of the damage to the roller doors, due to limitations in the
methodology employed by BH.
In particular, the Applicant says that:
by the time BH attended the property in March 2014, the damaged roller doors
had been removed and replaced;
BH was unable to measure the fixings on the damaged roller doors and
confirm the nature and extent of damage to each door and therefore his
conclusions as to the cause of the damage are necessarily non-specific and
speculative;
BH has referred to a number of potential causes of damage (such as track
fixings, curtain deformation and buckled curtain ribs) and it is impossible to
establish with sufficient certainty which of these is the proximate cause; and
the fact that other roller doors at the property were not damaged is
inconsistent with BH’s conclusions that the damage was due to the manner in
which the doors were installed.
The Panel does not agree that BH’s conclusions as to the cause of the damage to
the roller doors are unreliable.
The Panel considers that, as a structural engineer with over 20 years’ experience
in cyclone areas, BH is appropriately qualified to determine the cause of the
damage.
While BH did not inspect the damaged roller doors, he was provided with
numerous photographs of the doors taken immediately after the cyclone, many of
which are included in his report. BH was also able to inspect the three
undamaged roller doors of the same make and model which remained at the
property. The FSP’s building consultant (S), who attended the property before the
damaged roller doors were replaced, had previously confirmed that the fixing
Case No: 383958 Determination Page 4 of 8
method (including the spacing of the tek screws) was the same for all of the
doors.
While BH’s report refers to the different types of damage obse rved to the various
doors (tracking failure, bowing, crimping etc), his report clearly identifies the
inadequate installation of the doors as the cause of the bulk of the damage
sustained during the cyclone.
BH’s report attaches an academic publication wh ich confirms that tracking failure
and/or failure of the attachment to the door frame can result in damage to the
door curtain of the nature described in BH’s report.
Further, the detailed description of the damage to each of the doors prepared by
the FSP ’s building consultant (S) in March 2014 confirms tha t, in the case of all
but the middle door in Shed 4, the fixings connecting the roller door channel to the
door frame were loose or missing and/or the door channel had partially detached
from the door frame.
The Panel does not consider that the fact that three (out of nine) doors at the
property survived the cyclone undamaged undermines BH’s conclusions. The
Applicant has acknowledged that the nature and effect of cyclonic winds can vary
significantly within a localised area , and this is also reflected in BH’s report .
The Panel notes that BH’s conclusions were broadly consistent with the findings
of the FSP’s engineer (DW), who concluded that the size, type and spacing of the
tek screws used to attach the roller door channels to the door frames were
inadequate to enable the doors to withstand cyclonic activity.
The Panel acknowledges that, in concluding that the installation of the roller doors
was inadequate, DW referred to the Building Code of Australia, which does not
impose any specific requirements for roller doors (other than the general
requirement that all aspects of a building be designed to withstand the loads to
which it may reasonably be subjected).
However, the Panel does not consider t hat this invalidates DW’s views as to the
inadequacy of the door fastenings, in circumstances where BH has confirmed that
the method adopted did not comply with the manufacturer’s specifications.
For the reasons outlined above, the Panel is satisfied that the underlying cause of
the bulk of the claimed damage was the failure to install the doors in accordance
with the manufacturer’s specifications, rather than the cyclone itself.
The Panel notes that BH considered that certain denting and puncture damage
observed to the southern door of Shed 2 may have been caused by the impact of
flying objects during the cyclone (rather than by the prior impact of a forklift or
similar machinery as suggested by the FSP’s contractors, S and DW).
There is limited information available to determine the cause of the denting and
puncture damage to the southern door of Shed 2 or when the damage occurred.
However, the Panel is satisfied that the significant damage to this door which
occurred due to faulty installation (including its partial detachment from the door
frame on both sides) would have necessitated its replacement in any event.
Case No: 383958 Determination Page 5 of 8
FSP is entitled to deny Applicant’s claim for bulk of damage
For the reasons outlined above, the Panel is satisfied that the proximate cause of
the damage to the roller doors was their inability to withstand the loading imposed
during the cyclone, due to the manner in which they had been affixed.
The failure to install the doors in accordance with the manufa cturer’s
specifications constitutes faulty workmanship, which is excluded under the policy.
Even if the Panel were to accept that the cyclone and the faulty installation of the
roller doors operated interdependently and concurrently to cause the claimed
damage, the FSP would still be entitled to deny the claim.
Where a loss is caused by two proximate causes operating in tandem and one is
excluded while the other is not, the exclusion clause operates to allow the insurer
to deny the claim in its entirety. This is an established principle of insurance law
known as the Wayne Tank principle.
FSP’s liability for remaining damage does not exceed cyclone excess
For the reasons outlined above, the Panel is satisfied that the bulk of the damage
to the roller doors a t the Applicant’s policy was due to faulty installation.
However the Panel is not satisfied that the FSP has shown that, on the balance of
probabilities, it is entitled to rely on a policy exclusion to deny the Applicant’s
claim for the remaining damage.
This damage consists of:
the damage to the external corrugated iron wall cladding of Shed 1, which
photographs show had separated from the main structure; and
the damage to the second roller door in Shed 4, which the FSP’s building
consultant (S) described as being crumpled up across the entire face of the
door.
The available information does not suggest that the damage to the external wall of
Shed 1 was related to, or caused by, the damage to the roller doors.
The builder (BB) originally appointed by the FSP to inspect the property
considered that this damage was due to the wall having been incorrectly affixed to
the main structure. However, the available information is not sufficient to establish
that the policy exclusion for faulty workmanship applies.
The FSP’s building consultant (S) , who examined the damage to each of the roller
doors in detail, did not note any damage to the door channels, frames or fixings of
the second roller door in Shed 4. S considered that the damage to this door had
occurred prior to the cyclone, as a result of the door having forcibly slammed to
the ground with the gear of the door unengaged during maintenance works.
However, S has not provided any explanation as to the basis on which he
reached this view and the FSP has not provided any additional information to
support’s S’s conclusion as to the cause of the damage. Neither of the engineers
appointed by the parties expressed a view on this issue.
Case No: 383958 Determination Page 6 of 8
In these circumstances, the Panel does not consider that the available information
is sufficient to establish that, on the balance of probabilities, the FSP is entitled to
rely on a policy exclusion to deny the Applicant’s claim (in circumstances where a
prima facie claim has been established).
However, the Panel notes that under the policy an excess of $20,000 applies to
claims for damage caused by a named tropical cyclone.
Having carefully reviewed the quotation provided by the Applicant’s repairer (G)
for the replacement of the six damaged roller doors, the Panel considers that, on
balance, the proportionate cost of replacing the middle door of Shed 4 and
repairing the external wall of Shed 1 is unlikely to exceed the applicable policy
excess of $20,000.
On this basis, the Panel considers that the FSP should not be required to pay any
amount in settlement of the Applicant’s claim.
2.2 Is the Applicant entitled to reimbursement of professional costs?
FSP is not required to contribute to Applicant’s costs
The Applicant seeks reimbursement for engineer’s fees of $4,3 06.50 and legal
fees of $10,111.14 incurred for the purpose of pursuing this dispute.
Under paragraph 9.4 of the FOS Terms of Reference, a financial services
provider may be required to contribute to professional costs incurred by an
applicant in the course of their dispute.
The Panel considers that it was not unreasonable for the Applicant to seek its own
engineer’s report to confirm the proximate cause of damage to the roller doors.
However, for the reasons outlined above, the Panel considers that BH’s report
confirmed the application of the exclusion relied upon by the FSP.
In these circumstances, the Panel does not consider that the FSP should be
required to reimburse the Applicant for costs incurred in obtaining BH’s report.
Further, the Panel is not satisfied that the nature of the legal issues raised in this
dispute required the Applicant to obtain legal advice. FOS provides a service that
is free for applicants and it is generally unnecessary for either party to be legally
represented. If an applicant chooses to be represented, they will usually have to
cover their legal fees themselves.
In the present case, the dispute revolved primarily around the cause of the
damage to the Applicant ’s property. In these circumstances, legal advice is
unlikely to add significant substantive value.
Case No: 383958 Determination Page 7 of 8
3 Supporting information
3.1 FOS approach to this dispute
This dispute has not been the subject of a FOS Recommendation. Due to the
nature of the dispute, it has been referred directly to a Panel for Determination, in
line with the Operational Guidelines to the FOS Terms of Reference. The Panel
consists of an Ombudsman and two representatives with consumer and insurance
experience.
The Panel has decided this case on its merits, having regard to the relevant law,
good industry practice, codes of practice and previous Financial Ombudsman
Service (FOS) decisions.
There has been a full exchange of all material information relied on for the
purposes of this Determination and each party has had the opportunity to address
any issues raised by the other.
The Panel has reviewed and considered all of the material provided by the
parties. While the parties have raised numerous issues in their submissions, for
the purposes of this Determination, the Panel has restricted its commentary to
those issues that it considers directly relevant to the outcome only.
The Panel notes that the policyholder is a company. For reasons of brevity and
simplicity, in this Determination the company and its representatives have been
referred to collectively as the Applicant.
The Applicant has been assisted by its solicitor for the purposes of this dispute.
Any submissions made by the Applicant’s solicitor have been treated as having
been made by the Applicant itself, for the purposes of this Determination.
3.2 Terms of policy
Exclusion for faulty work
“We will not pay for loss or damage under the business property section caused by:
faulty work
- error in, omission of or wrong design;
- faulty materials or workmanship;
provided that this exclusion … shall not apply to subsequent loss or damage to your
business property occasioned by a peril (not otherwise excluded) resulting from any
event referred to in this exclusion .”
Panel comment
The Panel notes that the above exclusion does not apply to subsequent damage
to the insured property which results from faulty workmanship and is caused by
an insured event.
This aspect of the exclusion would apply where, for example, faulty workmanship
in the construction of a roof results in internal damage to the insured property
Case No: 383958 Determination Page 8 of 8
during a storm. However, it has no application in the context of the current
dispute, as the claimed damage is limited to that resulting directly from the faulty
workmanship itself.