Claim denied under faulty workmanship exclusion for cyclone damage to roller doors and wall

FirmFinancial Firm (Unknown - Insurer)
Decided2015-03-13
ProductGeneral Insurance · Business / commercial
OutcomeFor the firm
Amount awarded—
Non-financial loss—
Amount claimed$120,890
SourceAFCA PDF

Summary

The applicant company claimed $120,890 for cyclone damage to roller doors and a wall at its industrial property. AFCA found the bulk of the damage was caused by roller doors not installed to manufacturer specifications, which the policy excludes, and that the remaining damage fell below the cyclone excess, so nothing is payable.

The faulty workmanship exclusion applies because faulty installation was the proximate cause of the bulk of the damage, and the Wayne Tank principle allows denial of the whole claim.

Issues

Subjects and remedies

home or building damagenatural disastersmall businessno remedy

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Determination General Insurance - Small Business/Farm Insurance - Commercial Property - FSP Decision - Denial of claim-Exclusion/ condition Determination Case No: 383958 Determination Page 1 of 8 Case number : 383958 1 2 March 2015 1 Overview 1.1 Dispute The Applicant held a business insurance policy with the Financial Services Provider (FSP) which provided cover for an industrial property owned by the Applicant. The Applicant lodged a claim under the policy for damage to roller doors and a wall at the property, following a cyclone in December 2013. The Applicant incurred costs of $120,890 to replace the damaged roller doors and repair the wall. The FSP denied the claim on the basis that the majority of the damage to the roller doors was due to the incorrect manner in which they had been installed, rather than the cyclone itself. The FSP says that the remaining damage was pre- existing and caused by factors unrelated to the cyclone. 1.2 Issues and key findings Is the FSP liable for the damage to the Applicant’s property ? The Applicant has established a prima facie claim for cyclone damage under the policy. However, the available information (including the engineers’ reports) establishes that the bulk of the damage to the roller doors was caused by the doors not having been installed in accordance with the manufacturer’s specifications. Damage caused in this manner is not covered under the policy. The FSP has not established that it is entitled to rely on a policy exclusion for the damage to the wall of Shed 1 and the middle roller door in Shed 4. However, on balance, the cost of repairing this damage does not exceed the cyclone excess of $20,000. Is the Applicant entitled to reimbursement of professional costs? The Applicant is not entitled to reimbursement of its professional costs as the work performed did not assist the Applicant in establishing its claim. 1.3 Determination This Determination is in favour of the FSP. The FSP is not liable for the Applicant’s claim . Case No: 383958 Determination Page 2 of 8 2 Reasons for Determination 2.1 Is the FSP liable for the damage to the Applicant’s property ? Applicant has established prima facie claim The Applicant is required to show that, on the balance of probabilities, it has suffered a loss caused by a risk insured against under the policy. This is known as a prima facie claim. If the Applicant is able to establish a prima facie claim, then the onus shifts to the FSP to show that, on the balance of probabilities, it is entitled to rely on an exclusion under the policy to deny the claim. The Applicant ’ s policy provides cover for damage to the insured property caused by the events listed in the policy (including storm and wind), subject to the conditions and exclusions set out in the policy. The FSP accepts that there was a tropical cyclone in the vicinity of the Applicant’s property. The reports provided by the FSP’s cont ractors (and the photographs included therein) confirm that the roller doors and wall at the property sustained extensive damage due to the effects of the strong winds experienced during the cyclone. On this basis, the Panel is satisfied that the Applicant has established a prima facie claim under the policy. In these circumstances, the FSP bears the onus of establishing that, on the balance of probabilities, it is entitled to rely on a policy exclusion to deny the Applicant’s claim. Policy contains exclusion for damage caused by faulty work The FSP says that it is not liable for the damage to the roller doors, as the strong winds experienced during the cyclone would not have damaged the doors, had they been properly installed in accordance with the manufact urer’s guidelines. Accordingly, the FSP says that it is entitled to rely on the general exclusion under the policy for damage caused by faulty workmanship to deny the Applicant’s claim. In order to establish that the exclusion applies, the FSP must show that, on the balance of probabilities, the proximate cause of the damage to the Applicant’s property (that is, the real, effective or dominant cause) was the faulty installation of the roller doors. Proximate cause of bulk of damage was faulty installation of roller doors Having carefully reviewed the available information, the Panel is satisfied that, on the balance of probabilities, the proximate cause of the bulk of the damage to the roller doors was the fact that the doors were not installed in accordance with the manufacturer’s guidelines. Case No: 383958 Determination Page 3 of 8 The reports prepared by the various contractors (and the photographs contained therein) establish that six of the nine roller doors installed in sheds at the property sustained extensive damage by way of track fixing failure and/or curtain deformation (that is, bowing of the metal door curtain or crimping and buckling of the curtain ribs). After the FSP denied his claim, the Applicant engaged an engineer (BH) to report on whether the roller doors were suitable for their intended purpose at the time they were installed, in light of the damage suffered during the cyclone. In his report, BH concluded that most of the damage to the roller doors had occurred as a result of the doors not having been correctly installed, due to inadequate track fixings. BH noted that the fixings (tek screws) used to attach the door tracks to the door frame had been installed every 500 millimetres (at best), whereas the manufacturers’ specifications req uire the screws to be installed every 150 millimetres (based on a door curtain width of five metres). The copy of the manufacturer’s specifications attached to BH’s report confirms this requirement. The Applicant says that BH’s report should not be relied on to determine the proximate cause of the damage to the roller doors, due to limitations in the methodology employed by BH. In particular, the Applicant says that:  by the time BH attended the property in March 2014, the damaged roller doors had been removed and replaced;  BH was unable to measure the fixings on the damaged roller doors and confirm the nature and extent of damage to each door and therefore his conclusions as to the cause of the damage are necessarily non-specific and speculative;  BH has referred to a number of potential causes of damage (such as track fixings, curtain deformation and buckled curtain ribs) and it is impossible to establish with sufficient certainty which of these is the proximate cause; and  the fact that other roller doors at the property were not damaged is inconsistent with BH’s conclusions that the damage was due to the manner in which the doors were installed. The Panel does not agree that BH’s conclusions as to the cause of the damage to the roller doors are unreliable. The Panel considers that, as a structural engineer with over 20 years’ experience in cyclone areas, BH is appropriately qualified to determine the cause of the damage. While BH did not inspect the damaged roller doors, he was provided with numerous photographs of the doors taken immediately after the cyclone, many of which are included in his report. BH was also able to inspect the three undamaged roller doors of the same make and model which remained at the property. The FSP’s building consultant (S), who attended the property before the damaged roller doors were replaced, had previously confirmed that the fixing Case No: 383958 Determination Page 4 of 8 method (including the spacing of the tek screws) was the same for all of the doors. While BH’s report refers to the different types of damage obse rved to the various doors (tracking failure, bowing, crimping etc), his report clearly identifies the inadequate installation of the doors as the cause of the bulk of the damage sustained during the cyclone. BH’s report attaches an academic publication wh ich confirms that tracking failure and/or failure of the attachment to the door frame can result in damage to the door curtain of the nature described in BH’s report. Further, the detailed description of the damage to each of the doors prepared by the FSP ’s building consultant (S) in March 2014 confirms tha t, in the case of all but the middle door in Shed 4, the fixings connecting the roller door channel to the door frame were loose or missing and/or the door channel had partially detached from the door frame. The Panel does not consider that the fact that three (out of nine) doors at the property survived the cyclone undamaged undermines BH’s conclusions. The Applicant has acknowledged that the nature and effect of cyclonic winds can vary significantly within a localised area , and this is also reflected in BH’s report . The Panel notes that BH’s conclusions were broadly consistent with the findings of the FSP’s engineer (DW), who concluded that the size, type and spacing of the tek screws used to attach the roller door channels to the door frames were inadequate to enable the doors to withstand cyclonic activity. The Panel acknowledges that, in concluding that the installation of the roller doors was inadequate, DW referred to the Building Code of Australia, which does not impose any specific requirements for roller doors (other than the general requirement that all aspects of a building be designed to withstand the loads to which it may reasonably be subjected). However, the Panel does not consider t hat this invalidates DW’s views as to the inadequacy of the door fastenings, in circumstances where BH has confirmed that the method adopted did not comply with the manufacturer’s specifications. For the reasons outlined above, the Panel is satisfied that the underlying cause of the bulk of the claimed damage was the failure to install the doors in accordance with the manufacturer’s specifications, rather than the cyclone itself. The Panel notes that BH considered that certain denting and puncture damage observed to the southern door of Shed 2 may have been caused by the impact of flying objects during the cyclone (rather than by the prior impact of a forklift or similar machinery as suggested by the FSP’s contractors, S and DW). There is limited information available to determine the cause of the denting and puncture damage to the southern door of Shed 2 or when the damage occurred. However, the Panel is satisfied that the significant damage to this door which occurred due to faulty installation (including its partial detachment from the door frame on both sides) would have necessitated its replacement in any event. Case No: 383958 Determination Page 5 of 8 FSP is entitled to deny Applicant’s claim for bulk of damage For the reasons outlined above, the Panel is satisfied that the proximate cause of the damage to the roller doors was their inability to withstand the loading imposed during the cyclone, due to the manner in which they had been affixed. The failure to install the doors in accordance with the manufa cturer’s specifications constitutes faulty workmanship, which is excluded under the policy. Even if the Panel were to accept that the cyclone and the faulty installation of the roller doors operated interdependently and concurrently to cause the claimed damage, the FSP would still be entitled to deny the claim. Where a loss is caused by two proximate causes operating in tandem and one is excluded while the other is not, the exclusion clause operates to allow the insurer to deny the claim in its entirety. This is an established principle of insurance law known as the Wayne Tank principle. FSP’s liability for remaining damage does not exceed cyclone excess For the reasons outlined above, the Panel is satisfied that the bulk of the damage to the roller doors a t the Applicant’s policy was due to faulty installation. However the Panel is not satisfied that the FSP has shown that, on the balance of probabilities, it is entitled to rely on a policy exclusion to deny the Applicant’s claim for the remaining damage. This damage consists of:  the damage to the external corrugated iron wall cladding of Shed 1, which photographs show had separated from the main structure; and  the damage to the second roller door in Shed 4, which the FSP’s building consultant (S) described as being crumpled up across the entire face of the door. The available information does not suggest that the damage to the external wall of Shed 1 was related to, or caused by, the damage to the roller doors. The builder (BB) originally appointed by the FSP to inspect the property considered that this damage was due to the wall having been incorrectly affixed to the main structure. However, the available information is not sufficient to establish that the policy exclusion for faulty workmanship applies. The FSP’s building consultant (S) , who examined the damage to each of the roller doors in detail, did not note any damage to the door channels, frames or fixings of the second roller door in Shed 4. S considered that the damage to this door had occurred prior to the cyclone, as a result of the door having forcibly slammed to the ground with the gear of the door unengaged during maintenance works. However, S has not provided any explanation as to the basis on which he reached this view and the FSP has not provided any additional information to support’s S’s conclusion as to the cause of the damage. Neither of the engineers appointed by the parties expressed a view on this issue. Case No: 383958 Determination Page 6 of 8 In these circumstances, the Panel does not consider that the available information is sufficient to establish that, on the balance of probabilities, the FSP is entitled to rely on a policy exclusion to deny the Applicant’s claim (in circumstances where a prima facie claim has been established). However, the Panel notes that under the policy an excess of $20,000 applies to claims for damage caused by a named tropical cyclone. Having carefully reviewed the quotation provided by the Applicant’s repairer (G) for the replacement of the six damaged roller doors, the Panel considers that, on balance, the proportionate cost of replacing the middle door of Shed 4 and repairing the external wall of Shed 1 is unlikely to exceed the applicable policy excess of $20,000. On this basis, the Panel considers that the FSP should not be required to pay any amount in settlement of the Applicant’s claim. 2.2 Is the Applicant entitled to reimbursement of professional costs? FSP is not required to contribute to Applicant’s costs The Applicant seeks reimbursement for engineer’s fees of $4,3 06.50 and legal fees of $10,111.14 incurred for the purpose of pursuing this dispute. Under paragraph 9.4 of the FOS Terms of Reference, a financial services provider may be required to contribute to professional costs incurred by an applicant in the course of their dispute. The Panel considers that it was not unreasonable for the Applicant to seek its own engineer’s report to confirm the proximate cause of damage to the roller doors. However, for the reasons outlined above, the Panel considers that BH’s report confirmed the application of the exclusion relied upon by the FSP. In these circumstances, the Panel does not consider that the FSP should be required to reimburse the Applicant for costs incurred in obtaining BH’s report. Further, the Panel is not satisfied that the nature of the legal issues raised in this dispute required the Applicant to obtain legal advice. FOS provides a service that is free for applicants and it is generally unnecessary for either party to be legally represented. If an applicant chooses to be represented, they will usually have to cover their legal fees themselves. In the present case, the dispute revolved primarily around the cause of the damage to the Applicant ’s property. In these circumstances, legal advice is unlikely to add significant substantive value. Case No: 383958 Determination Page 7 of 8 3 Supporting information 3.1 FOS approach to this dispute This dispute has not been the subject of a FOS Recommendation. Due to the nature of the dispute, it has been referred directly to a Panel for Determination, in line with the Operational Guidelines to the FOS Terms of Reference. The Panel consists of an Ombudsman and two representatives with consumer and insurance experience. The Panel has decided this case on its merits, having regard to the relevant law, good industry practice, codes of practice and previous Financial Ombudsman Service (FOS) decisions. There has been a full exchange of all material information relied on for the purposes of this Determination and each party has had the opportunity to address any issues raised by the other. The Panel has reviewed and considered all of the material provided by the parties. While the parties have raised numerous issues in their submissions, for the purposes of this Determination, the Panel has restricted its commentary to those issues that it considers directly relevant to the outcome only. The Panel notes that the policyholder is a company. For reasons of brevity and simplicity, in this Determination the company and its representatives have been referred to collectively as the Applicant. The Applicant has been assisted by its solicitor for the purposes of this dispute. Any submissions made by the Applicant’s solicitor have been treated as having been made by the Applicant itself, for the purposes of this Determination. 3.2 Terms of policy Exclusion for faulty work “We will not pay for loss or damage under the business property section caused by:  faulty work - error in, omission of or wrong design; - faulty materials or workmanship; provided that this exclusion … shall not apply to subsequent loss or damage to your business property occasioned by a peril (not otherwise excluded) resulting from any event referred to in this exclusion .” Panel comment The Panel notes that the above exclusion does not apply to subsequent damage to the insured property which results from faulty workmanship and is caused by an insured event. This aspect of the exclusion would apply where, for example, faulty workmanship in the construction of a roof results in internal damage to the insured property Case No: 383958 Determination Page 8 of 8 during a storm. However, it has no application in the context of the current dispute, as the claimed damage is limited to that resulting directly from the faulty workmanship itself.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.