Home / Financial Firm (Unknown - Insurer) / Determination 375128
Determination 375128
Denial of Claim - Exclusion/Condition
Summary
The Applicants claimed under their home policy after their balcony collapsed following a storm. AFCA found the damage was caused by gradual deterioration and poor design and construction, which the policy excludes, and found the FSP not liable.
The FSP proved on the balance of probabilities that the proximate cause was excluded gradual deterioration and faulty design, and section 46 of the Insurance Contracts Act 1984 does not apply to exclusions that do not depend on pre-policy defects.
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
Claim - Exclusion/Condition
Determination
Case No: 375128 Determination Page 1 of 6
Case number : 375128 30 December 2014
1 Overview
1.1 Dispute
The Applicants lodged a claim under their home insurance policy with the
Financial Services Provider (FSP) after their balcony collapsed following a storm
in November 2013.
The FSP denied the claim on the basis that the damage had been caused by
faulty design and construction and/or gradual deterioration, each of which is
excluded under the policy.
The Applicants dispute the FSP’s denial of their claim and want their balcony
repaired.
1.2 Issue and key findings
Can the FSP deny the Applicants’ claim ?
The Applicants have established a prima facie claim for accidental damage under
the policy, as the damage to the balcony was unintended and unexpected.
However, the available information establishes that the damage occurred as a
result of gradual deterioration, due to water entering the timber framework over an
extended period of time as a result of the manner in which the balcony was
designed and constructed. Damage caused in this manner is not covered under
the policy.
Section 46 of the Insurance Contracts Act 1984 (the Act) does not assist the
Applicants, as the application of the policy exclusions relied on by the FSP does
not depend on the ongoing issues with the balcony having existed before the date
the policy was taken out.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is no t liable for the Applicants’ claim .
Case No: 375128 Determination Page 2 of 6
2 Reasons for Determination
2.1 Can the FSP deny the Applicants’ claim ?
Application of policy depends on cause of damage
The Applicants’ policy provides cover for accidental damage to their property
during the period of insurance, subject to the conditions and exclusions set out in
the policy. In this context, the courts have interpreted “accidental” to mean
“unintended and unexpected.”
The policy contains exclusions for damage caused by:
gradual deterioration, depreciation, wear or tear or
inherent defects, structural defects, faulty workmanship or faulty design.
The Applicants say that their balcony “dropped” due to the effects of strong winds
and driving rain during the severe storm in November 2013.
However, the FSP says that the damage to the balcony was not caused by the
storm but has occurred over an extended period of time as a result of water
entering the balcony due to its poor design and construction.
It is an accepted principle of general insurance la w that an insured bears the onus
of establishing that, on the balance of probabilities, they have suffered a loss
caused by a risk insured under the policy. This is known as a prima facie claim. If
the insured is able to establish a prima facie claim, the onus then shifts to the
insurer to show that, on the balance of probabilities, the loss falls within an
exclusion clause under the policy or that it is otherwise entitled to deny liability.
The FSP has not disputed that the Applicants’ balcony suffered sig nificant
damage as a result of unintended and unexpected events. In these
circumstances, the Panel is satisfied that the Applicants have established a prima
facie claim, given the broad cover for accidental damage provided under the
policy.
Accordingly, the FSP bears the onus of establishing that, on the balance of
probabilities, it is entitled to rely on a policy exclusion to deny the Applicants’
claim. In order to do so, the FSP must show that the proximate cause (that is, the
real, effective or predominant cause) of the damage to the balcony was one of the
excluded factors outlined above.
Available information establishes damage was caused by excluded factors
Having carefully reviewed the available information, the Panel considers that the
damage to the Applicants’ balcony w as caused by gradual deterioration over a
prolonged period of time, due to the inappropriate design and construction of the
balcony.
The engineer (JH) appointed by the FSP to identify the cause of damage
concluded that the collapse of the balcony was due to the extensive decay of the
timber support beams caused by water entry, due to the failure of the waterproof
membrane. JH noted that the base of the aluminium handrail posts and run-off
Case No: 375128 Determination Page 3 of 6
channelled by the tiles along the outer edge of the balcony provide further
sources of water entry.
Further, JH noted that the two varieties of hardwood used to construct the timber
support beams had a very low durability rating and were not recommended for
structural use in circumstances (such as the Applicants’ balcony) where they may
be exposed to water.
Based on the extensive decay observed throughout the timber beams (which is
clearly evident in the photographs provided) and the signs of past repairs, JH
concluded that the damage had occurred over a period of several years.
The conclusions reached by the Applicant’s engineer (LO) as to the cause of
damage were generally consistent with JH’s findings. LO confirmed that the
deflection (sagging) of the balcony had been caused by the rotting of the timber
beams due to water entry over a period of time. LO did not express a view as to
the underlying cause of the water entry or refute JH’s comments about the poor
design and construction of the balcony.
Based on the engineers’ reports, the Panel is satisfied that the damage to the
balcony occurred due to water entry over an extended period of time. The Panel
also accepts JH’s findings that the underlying cause of the water entry was the
poor design and construction of the balcony - in particular, the use of
inappropriate timber for the support beams and the failure to adequately ensure
that water was not able to enter the timber framework.
Accordingly, the damage falls within the policy exclusions for damage caused by
gradual deterioration and/or faulty design and construction.
The Applicants say that their claim is limited to the collapse of the balcony which
occurred immediately following the storm in November 2013, rather than the
ongoing damage to the balcony.
However, in light of the engineers’ findings, the Panel is satisf ied that the
underlying cause of the damage in November 2013 was the ongoing water entry
which had occurred over a period of time, resulting in the extensive decay of the
timber support beams which ultimately caused the balcony to collapse.
Accordingly, the Applicants are not entitled to cover under the policy.
Section 46 of the Act does not apply
The Applicants say that section 46 of the Act operates to prevent the FSP from
denying their claim, on the basis that they were not aware (and could not possibly
have been aware) of the ongoing damage to their balcony.
Section 46 of the Act prevents an insurer from relying on a policy exclusion which
operates by reference to a defect in a thing which existed before the policy was
taken out, in circumstances where the insured was not aware (and a reasonable
person in the circumstances could not be expected to have been aware) of the
defect at the time the policy was taken out.
The report provided by the Applicants engineer (LO) states that Applicants could
not be expected to have been aware that the timber support beams of the balcony
Case No: 375128 Determination Page 4 of 6
were being damaged by water entry, until the balcony began to visibly sag
following the storm in November 2013.
The Panel accepts that the Applicants were not aware of the damage to t heir
balcony caused by the gradual rotting of the timber support beams, given the
beams were fully enclosed by fibre cement cladding.
However, the courts have confirmed that section 46 of the Act only applies in
circumstances where the insurer relies on an exclusion which operates by
reference to the time at which the relevant defect arose – that is, where the
exclusion expressly refers to the defect having been present before the policy was
taken out.
The exclusions relied upon by the FSP in the present case apply to damage
which was caused by faulty design and workmanship and/or gradual deterioration,
irrespective of when these issues arose. As the application of these exclusions
does not depend on the relevant defects having been present before the policy
was taken out, section 46 does not operate to assist the Applicants.
Case No: 375128 Determination Page 5 of 6
3 Supporting information
3.1 FOS approach to this dispute
This dispute has not been the subject of a FOS Recommendation. Due to the
nature of the dispute, it has been referred directly to a Panel for Determination, in
line with the Operational Guidelines to the FOS Terms of Reference. The Panel
consists of an Ombudsman and two representatives with consumer and insurance
experience.
The Panel has decided this case on its merits, having regard to the relevant law,
good industry practice, codes of practice and previous Financial Ombudsman
Service (FOS) decisions.
There has been a full exchange of all material information relied on for the
purposes of this Determination and each party has had the opportunity to address
any issues raised by the other.
The Panel has reviewed and considered all of the material provided by the
parties. While the parties have raised a number of issues in their submissions, for
the purposes of this Determination the Panel has restricted its commentary to
those issues which it considers directly relevant to the outcome only.
The Applicants have been represented by their broker for the purposes of this
dispute. Any submissions made by the Applicants ’ broker have been treated as
having been made by the Applicants themselves, for the purposes of this
Determination.
3.2 Reports
Record Key points
Applicant’s builder
(GM)
Quote – 24 April 2014
Balcony has suffered water damage.
FSP’s a ssessor ( CR )
R eport - 29 May 2014
The Applicants initially advised that the damage to the
balcony occurred as a result of the storm on 23 November
2013 . H owever , the Applicants subsequently clarified that
the issue became more prominent after the storm .
FSP’s e ngineer ( JH )
R eport - 10 June 20 14
The tiled floor of the rear upper level balcony displayed
excessive sagging between each of the supporting circular
columns to the point where the glass panels in two
locations had severe stress cracks in them.
The type of hardwood used for the support beams of
balcony is very strong if installed in a dry environment, but
does not perform well when exposed to weather. It has a
very low durability rating and is not recommended for any
structural application if subject to water of any kind .
The f loor tile s along th e outer edge of the balcony had
been channelling run - off water into the top edge of the
Case No: 375128 Determination Page 6 of 6
Record Key points
support beams. Water was also able to enter the floor
frame under the base of the aluminium handrail posts.
The floor tile joint and waterproof membrane around each
of the circular columns had also failed, allowing water to
track around the columns and into the ends of the timber
beams.
There was extensive decay in the ends and through the
middle of the timber s upport beams, which indicated that
the damage had occurred over a consideration period of
time (years).
The support beams had been completely encased with
fibre cement sheeting which had contributed to the decay
as water has become trapped, preventing the beams from
ever drying out properly.
The base of the handrail posts also showed long - term
sagging of the floor edge. The sagging of the floor had
transferred tremendous stress into the handrail system,
which had caused the in - fill glass panels to crack.
Th ere were signs of previous repairs (including the use of
packing material under the handrail posts and re - grouting
of the floor joints), which was further evidence that the
damage had been occurring for some time.
The damage to the support beams was a resu lt of a
construction defect due to the selection of inappropriate
timber for the beams, the use of poor techniques in
concealing the beams with fibre cement sheeting and the
poor installation of the waterproofing membrane.
Applicant’s e ngineer
(LO)
Report - 26 June 2014
The bearers supporting the balcony showed substantial
deflections. The bearers revealed rot due to water entry
over a period of time , which had caused the excessive
deflection .
He was unable to comment on the joists as they were not
exposed, but noted that they may have also suffered rot
due to water entry .
No significant staining or other signs of water ingress and
timber deterioration were noted other than in the areas
where th e fibre cement cladding had been cut away to
expose the damaged beams .
Accordingly, t he Applicants could not be expected to have
been aware that water entry was damaging the deck over
time , until the deflections became apparent .
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.