Text of the determination
Determination
General Insurance - Domestic Insurance - Residential Strata Title - FSP Decision -
Denial of Claim
Determination
Case No: 369260 Determination Page 1 of 8
Case number : 369260 15 December 2014
1 Overview
1.1 Dispute
The Applicant is a body corporate which holds a strata insurance policy with the
Financial Services Provider (FSP) for a residential apartment building .
In March 2014, the Applicant lodged a claim under the policy when the circuit one
compressor in the building ’s air conditioning unit failed. The Applicant
subsequently replaced the entire unit due to the failure of the compressor, at a
cost of $219,197.
The FSP denied the claim on the basis that the failure was due to factors which
are excluded under the policy, such as wear and tear and overloading.
1.2 Issues and key findings
Is the FSP liable for the damage to the compressor?
The Applicant has established a prima facie claim for mechanical breakdown
under the policy, as the damage to the compressor occurred suddenly,
unexpectedly and unintentionally.
The available information does not establish that, on the balance of probabilities,
the failure of the compressor occurred due to overloading or wear and tear
resulting from age or ordinary use. Accordingly, the FSP is liable for the damage
to the compressor.
How should the claim be settled?
The FSP should cash settle the Applicant for the cost of replacing the circuit one
compressor, in order to repair the air conditioning unit to its condition prior to the
damage occurring. The Applicant is also entitled to reimbursement for costs
incurred to provide temporary cooling facilities to the apartment block following
the failure of the compressor in March 2014.
1.3 Determination
This Determination is in favour of the Applicant.
The FSP is to cash settle the Applicant for the amo unt of $102,160, plus interest
on this amount calculated in accordance with section 2.2 below.
Case No: 369260 Determination Page 2 of 8
2 Reasons for Determination
2.1 Is the FSP liable for the damage to the compressor ?
Applicant has established a prima facie claim for mechanical breakdown
The Applicant’s claim is properly considered under the section of the policy which
provides cover for machinery breakdown, rather than the section which provides
cover for accidental loss or damage to the insured property more generally. The
latter section specifically excludes damage caused by mechanical breakdown
(except where the damage results from fire, lightning or a power surge).
The mechanical breakdown section of the policy provides cover for “ Insured
Damage ” to an insur ed item (such as the air conditioning unit) which is in the
ordinary course of working at the time the damage occurs.
For this purpose, “Insured Damage” is defined to mean sudden and accidental
physical loss or damage which requires repair or replacement in order to allow for
the continued use of the item. The courts have defined “accidental” in this context
to mean “unintended and unexpected”.
It is an accepted principle of general insurance law that an insured bears the onus
of establishing that, on the balance of probabilities, they have suffered a loss
caused by a risk insured under the policy. This is known as a prima facie claim. If
the insured is able to establish a prima facie claim, the onus then shifts to the
insurer to show that, on the balance of probabilities, the loss falls within an
exclusion clause under the policy or that it is otherwise entitled to deny liability.
The FSP says that, given that the circuit one compressor was over ten years old,
the claimed damage was not “sudden and accidental” because it occurred simply
as a result of the compressor having reached its use by date. In support of its
position, the FSP refers to the fact that the other compressor for the unit (the
circuit two compressor) had failed in February 2013.
However, the Panel does not accept that the age of the circuit one compressor
(and the previous failure of the circuit two compressor) means that the claimed
damage did not occur suddenly and unexpectedly, as is required to establish a
prima facie claim for mechanical breakdown under the policy.
The available information indicates that the damage to the circuit one compressor
occurred suddenly, unexpectedly and unintentionally while the compressor was in
ordinary use. Further, repair or replacement was required in order for the air
conditioning unit to continue to function effectively.
On this basis, the Panel is satisfied that the Applicant has established a prima
facie claim for mechanical breakdown under the policy. The issues raised by the
FSP about the age of the compressor are more properly considered in the context
of determining the cause of the damage (and therefore whether the FSP is
entitled to rely on an exclusion under the policy to deny liability).
Case No: 369260 Determination Page 3 of 8
Cover for mechanical breakdown is subject to exclusions
The FSP says that it is entitled to rely on exclusions under the policy for damage
caused by:
wear and tear (which is defined in the policy to mean age, ordinary use or lack
of maintenance);
the wearing away or wasting of material caused by or naturally resulting from
atmospheric conditions, rust, erosion, corrosion, oxidation or ordinary use; or
the carrying out of tests involving abnormal stresses or the intentional
overloading of any Insured Item.
As the FSP is seeking to deny th e Applicant’s claim based on a policy exclusion, it
bears the onus of establishing that, on the balance of probabilities, the relevant
exclusion applies.
Failure of circuit one compressor was not caused by overloading
The FSP initially denied the claim based on a report from its engineer (AR), who
concluded that the failure of the circuit one compressor in March 2014 was due to
wear and tear, caused by the fact that the tandem system air conditioning unit had
been operating with only one compressor since the failure of the circuit two
compressor in February 2013.
However, the Applicant has provided an email from the regional product manager
for the relevant brand of air conditioning units (BH). In his email, BH confirms that:
the two circuits in the air conditioning unit operate independently of each
other; and
running the unit with only one compressor would not cause the failure of that
compressor, regardless of the ambient conditions or building cooling load
demand. The only potential adverse impact would be on the chilled water
temperature.
Given his role, the Panel considers that BH is likely to have a high degree of
specialised knowledge about the operation of the particular air conditioning unit
owned by the Applicant and therefore his opinion should be given considerable
weight. The Panel notes that the FSP has not provided any information (for
example, a response from its own engineer) which refutes the views expressed by
BH.
In these circumstances, the Panel does not accept that the FSP has established
that, on the balance of probabilities, the failure of the circuit one compressor in
March 2014 was due to overloading following the earlier failure of the circuit two
compressor.
Available information does not establish failure was due to wear and tear
The FSP has also relied on the policy exclusions for wear and tear due to age,
ordinary use or lack of maintenance (and/or the wasting away of materials due to
corrosion or oxidation) to deny the Applicant’s claim.
The FSP’s engineer (AR) who initially assessed the damage to the compressor
did not arrange for an internal inspection to be carried out. In his report, AR
Case No: 369260 Determination Page 4 of 8
expressly states that he is unable to comment on the actual failure or damage to
the compressor as it had not been dismantled and stripped down.
It appears that the FSP assumed that the nature and extent of the damage to the
circuit one compressor was likely to be similar to that suffered by the circuit two
compressor which had failed twelve months earlier (and which had been the
subject of a detailed inspection). In the Panel’s view, this assumption was unwise,
in the absence of an actual inspection of the circuit one compressor itself.
The FSP ultimately arranged for an inspection of the circuit one compressor to be
carried out by its air conditioning specialist (AC) in November 2014. AC prepared
a very brief report dated 2 December 2014 in which he concluded that, based on
his observations during the inspection, there was bearing wear, helicoil rotor wear
and header plate wear to the comp ressor . AC commented that:
“ This wear can cause excessive amp draw on stator windings compromising the
integrity of the winding insulations and overheating of the stator causing the
compressor to trip out on motor overload protection .”
However, the Panel d oes not consider that AC’s report is sufficient to establish
that, on the balance of probabilities, the damage to the compressor was caused
by wear and tear. In this regard, the Panel notes that:
AC does not explain how or why the various items observed during his
inspection (being the insulation meter readings, metal fragments in the oil
chamber, oil filter contamination and a missing rotor balance weight) led to his
conclusion that there was wear to the bearings, helicoil rotor and header plate
AC’s report does not include any photographs of the internal mechanism of
the compressor, which might have been helpful in explaining the basis for his
findings and
while AC notes that the type of wear identified can result in overheating and
cause the compressor to trip out, he does not state that is what has caused
the failure of the compressor in this particular instance.
The Panel also notes the comments by the regional product manager (BH) which
suggest that it may not be possible to accurately determine the underlying cause
of the damage, in cases where there is extensive internal damage to the
compressor.
The FSP says that the ordinary useful life of the Applicant’s air conditioning unit is
between ten and fifteen years. However, the mere fact tha t the compressors were
more than ten years old when they failed does not of itself establish that the
failure was due to wear and tear. The FSP has the onus of establishing this.
For the reasons outlined above, the Panel is not satisfied that the FSP has
established that, on the balance of probabilities, the failure of circuit one
compressor was caused by wear and tear and ordinary use.
Applicant is unlikely to be able to recover under warranty agreements
Under the terms of the policy, the FSP is not liable for damage caused by
mechanical breakdown, to the extent that the Applicant is able to claim for this
damage under the provisions of any maintenance or warranty agreement.
Case No: 369260 Determination Page 5 of 8
The Applicant had entered into arrangements with two maintenance contractors
(AK and AA) for the maintenance of the air conditioning unit during the twelve
month period leading up to the failure of the circuit one compressor. The FSP has
sought to obtain copies of the relevant agreements from the Applicant but to date
these have not been provided.
Given the limited and inconclusive information available about what caused the
failure of the circuit one compressor, the Panel considers that it is highly unlikely
that the Applicant would be able to recover any amount from the air conditioning
maintenance contractors in relation to this issue. Accordingly, the Panel considers
that the FSP is unable to rely on this exclusion in respect of the Applicant’s claim.
2.2 How should the claim be settled?
FSP is liable for cost of replacing circuit one compressor
The policy provides that, where a claim is made for mechanical breakdown, the
FSP may decide to repair to replace the relevant item (to the same condition as it
was in before the damage occurred) or pay the Applicant the cost of doing so.
The policy provides that no allowance for depreciation will be made where parts
are replaced.
The Applicant chose to replace the entire air conditioning unit following the failure
of the circuit one compressor in March 2014. This was based on a
recommendation from its maintenance contractor (AA) in light of factors including
the age of the unit, the relative cost of replacing the compressor and the improved
efficiencies offered by newer units.
However, it is clear from AA’s report dated 14 March 2014 (togethe r with earlier
reports prepared following the failure of the circuit two compressor) that the air
conditioning unit could have been effectively repaired by simply replacing the
circuit one compressor, at a quoted cost of $84,660 (excluding GST).
Accordingly, the Panel considers that it is fair in all the circumstances that the
FSP cash settle the Applicant for $84,660. The FSP should pay interest on this
amount at the rate determined in accordance with section 57 of the Insurance
Contracts Act 1984 (Cth) from 9 April 2014 to the payment date.
Applicant is entitled to reimbursement for cost of hiring spot coolers
The cover for machinery breakdown under the policy provides for the payment of
certain additional benefits, including the reasonable costs of hiring temporary
replacement items where necessary to maintain a vital service provided by the
insured.
After the air conditioning unit became inoperable following the failure of the circuit
one compressor in March 2014, the Applicant hired forty spot coolers for a period
of approximately two weeks, to provide air conditioning for the residents of the
apartment building.
The Panel is satisfied that the hire of temporary coolers was necessary to
maintain a vital service provided by the Applicant. While the po licy does not
Case No: 369260 Determination Page 6 of 8
provide specific guidance as to what constitutes a “vital service” the Panel
accepts that cooling is generally treated as such a service – for example, under
the residential tenancies legislation which applied to those members of the
ow ners’ corporation who rented out their properties.
The Panel has considered whether the Applicant’s entitlement to this additional
benefit should be reduced, having regard to the fact that the Applicant had not
replaced the circuit two compressor following its failure in February 2013 which
would have allowed the air conditioning unit to continue to operate.
However, the Panel considers that no such reduction is appropriate given that, at
the relevant time, the FSP had denied the Applicant’s claim for the damag e to the
circuit two compressor (a decision which was later partially overturned).
Accordingly, the Panel considers that the FSP should cash settle the Applicant for
an additional amount of $17,500, being the cost (excluding GST) of hiring the
temporary spot coolers in March 2014.
Case No: 369260 Determination Page 7 of 8
3 Supporting information
3.1 FOS approach to this dispute
This dispute has not been the subject of a FOS Recommendation. Due to the
nature of the dispute, it has been referred directly to a Panel for Determination, in
line with the Operational Guidelines to the FOS Terms of Reference. The Panel
consists of an Ombudsman and two representatives with consumer and insurance
experience.
The Panel has decided this case on its merits, having regard to the relevant law,
good industry practice, codes of practice and previous FOS decisions.
There has been a full exchange of all material information relied on for the
purposes of this Determination and each party has had the opportunity to address
any issues raised by the other.
The Panel has reviewed and considered all of the material provided by the
parties. While the parties have raised a number of issues in their submissions, for
the purposes of this Determination the Panel has restricted its commentary to
those issues which it considers directly relevant to the outcome only.
The Applicant has been represented by its insurance broker during the course of
this dispute. For the purposes of this Determination, submissions made by the
Applicant’s broker will be treated as having been made by the Applicant itself.
3.2 Terms of policy
Subject Terms
Machinery breakdown cover What we insure
We insure You against Insured Damage provided that
the insured item is within Your situation and is in the
ordinary course of working at the time damage occurs.
Machinery breakdown -
e xclusions
We will not pay for:
Damage caused by:
- Wear and T ear … ..
- the wearing away or wasting of material caused
by or naturally resulting from atmospheric
conditions, rust, erosion, corro sion, oxidation or
ordinary use …
- the carrying out of tests involving abnormal
stresses or the intentional overloading of any
Insured Item …
Damage which is claimable from any manufacturer,
supplier, engineer or other person under the
provisions of any maintenance or warrant y
agreement.
Case No: 369260 Determination Page 8 of 8
Subject Terms
Definition o f “Insured
D amage”
means sudden and accidental physical loss or damage
which occurs during the Period of Insurance and
requires repair or replacement to allow continuation of
use, other than by a cause
which is covered under [Insured Property Cover]; or
which is not claimable under [Machinery Breakdown
Cover] .
Definition of “Insured Item” m eans :
a lifts, elevators, escalators and inclinators provided
they are subject to a current comp rehensive
maintenance agreement
all other electrical, electronic and mechanical
machinery, boilers and pressure vessels and similar
plant; that forms part of Your Insured Property or its
services.
Definition of “Wear, Tear” means damage or a reduction in value through age,
ordinary use or lack of maintenance.
Machinery breakdown –
basis of settlement
We will at Our option repair or replace the Insured Item
or pay for the cost of same to a condition equal to but
not better nor more extensive than its condition
immediately before the Insured Damag e.
We will not make any deduction for Depreciation in
respect of parts replaced.
We will not pay for the cost of any alterations, additions,
improvements, modifications or overhauls .
Machinery breakdown –
additional benefits
Additional Benefits are includ ed when Your Sum
Insured under [Machinery Breakdown Cover] is not
otherwise expended in respect of any one Event.
We will pay for the reasonable cost of:
Expediting repair including overtime working ……
Replacing oil and refrigerant gas from air - conditioning
units or refrigeration units;
Hiring a temporary replacement item provided such
cost is necessary to maintain a vital service provided
by You.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.