Home / Financial Firm (Unknown - Insurer) / Determination 366212
Determination 366212
Denial of claim
Summary
The owners corporation claimed the cost of replacing four strata balconies after one partially collapsed. The FSP declined because the damage was gradual deterioration and construction defects, and AFCA agreed the policy exclusions applied.
The policy excludes gradual deterioration, wet rot, faulty design and workmanship, and the damage arose from those excluded causes.
Issues
- Claim denial primary · not upheld“The FSP is entitled to deny the Applicant's claim because the balconies gradually deteriorated due to water entering through gaps”
Subjects and remedies
home or building damageno remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
claim
Determination
Case No: 366212 Determination Page 1 of 5
Case number : 366212 11 March 2015
1 Overview
1.1 Dispute
The Applicant is the Owner’s Corporation, which has a residential strata insurance
policy with the Financial Services Provider (FSP). After the partial collapse of unit
on e’s balcony, the Applicant lodged a claim on the policy for the cost of replacing
the balcony of all four units.
The FSP declined the Applicant’s claim because no single event caused the
failure of the balconies. The FSP considered the balconies deteriorated over time
due to the way they were constructed.
1.2 Issues and key findings
Is the FSP entitled to deny the Applicant’s claim ?
The FSP is entitled to deny the Applicant’s claim because:
the balconies gradually deteriorated due to water entering through gaps
the balcony of unit one had wet rot
the damage arose from the failure of a waterproofing membrane
the policy excludes gradual deterioration, wet rot and the failure of any item
the FSP is not liable for the damage under the terms of the polic y.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is not required to pay the Applicant’s claim for the cost of replacing all
four balconies in the strata plan.
Case No: 366212 Determination Page 2 of 5
2 Reasons for Determination
2.1 Is the FSP entitled to deny the Applicant’s clai m?
Applicant must show a claimed loss occurred
The policy covers the Applicant for any accidental damage to the properties in the
strata plan, subject to exclusions.
An accepted principle of insurance law is the Applicant is required to show they
suffered a loss covered under the policy. This is called a prima facie claim.
Once established, the onus then shifts to the FSP to show the policy excludes the
claimed loss or the FSP is entitled to deny the claim. The Applicant and the FSP
have to show this based on what was probable.
The parties do not dispute the balcony to unit one partially collapsed and there is
evidence of damage to the other balconies.
The FSP provided a building consultant’s report, which indicated a building
construction defect caused th e damage. The Applicant disputes the consultant’s
finding and obtained an engineer’s report. Both parties’ engineers considered the
structure complied with the relevant building codes.
Damage arose from the failure of a waterproofing membrane
The information provided shows the cause of damage to the balconies is due to
water entering over time because of:
the design of the curved fascia edge of the balconies
the lack of appropriate drainage
the flawed waterproofing membrane
gradual deterioration
wear and tear
the cracks and small gaps, which weakened the structure.
The damage included wet rot and possible corrosion. The FSP’s engineer
considered the damage did not occur from a single event.
The policy excludes gradual deterioration, wet rot and the failure of any item
The policy excludes cover for any damage, which arose from or was caused by:
gradual deterioration
wear or tear
wet or dry rot
the failure of or the defect in any item
structural defect
faulty design
faulty workmanship.
The information shows the damage occurred over time due to the failure of the
waterproofing membrane and the design of the balconies. This means the policy
Case No: 366212 Determination Page 3 of 5
does not cover the damage claimed because it arose from the above excluded
factors.
3 Supporting information
3.1 Key information
Product disclosure statement.
Certificate of insurance.
Applicant’s claim form.
Applicant’s engineer’s report, 27 March 2014.
FSP’s engineer’s report, 11 July 2014.
Applicant’s statements, various.
Photographs and descriptions of damage.
3.2 Reports of damage
Record Key points
FSP’s building
consultant (M)
Report
11 February 2014
Notes from inspection of balcony of unit one:
Grout has bubbled which indicates the water has been
trapped in the joints and the grout has failed.
Large crack in one of the joints in the tiling towards the
front edge of the balcony.
This allowed water ingress into the sub - floor framing.
Exposed framing had completely rotted away.
Possible failure of the waterproofing (or none applied).
Eaves lining have fallen off.
Method of construction was totally unacceptable and non -
compliant.
Recommended residents should not use all balconies.
Evidence of water penetration to unit 2 - 4 balconies.
FSP’s building
consultant (M)
Report
4 March 2014
Provided responses to Applicant’s statements.
Indicated without invasive testing, it was unable to
determine the level of defects present.
Applicant’s engineer (A )
Report
27 March 2014
Overall:
Observations indicated t he balconies to units 2 - 4 might
also be deteriorated.
Balconies were structurally acceptable with standards.
Cause of deterioration is likely to be water ingress at the
curved fascia edge causing wet rot.
Recommended all four balconies not be loaded or
tra versed until further notice.
Balcony of unit one:
Timber elements destroyed by significant rotting.
Case No: 366212 Determination Page 4 of 5
Record Key points
Water entry from curved fascia edge.
Silicon sealing was present between tiled balcony and
external brick façade, indicating previous water ingress
and maintenance.
Ring stains from pot plants show balcony may have been
heavily loaded or over - loaded, which caused deflection of
timber joists.
Separation between tiles may have exacerbated water
ingress.
Hairline cracks in tiles at stress concentration point s.
Vertical separation between sheets observed.
There was a waterproof membrane and mesh.
Balcony of unit four:
Inspected the surface.
Water entry point present at curved fascia edge.
Hairline cracks present in tiles at stress concentration
points.
Stainin g observed on the vertical surfaces below
indicating possible corrosion.
The Applicant should demolish and rebuild the rotted
balconies.
Applicant’s builder ( DJ )
Quote
28 April 2014
$10,800 (incl GST) to repair each balcony.
FSP’s engineer (DB)
Report
11 July 2014
Overall:
There is flawed waterproofing membrane and drainage
provisions given the extent of damage and wet rot.
The deteriorated condition of the waterproofing membrane
occurred over years and is unrelated to a single or defined
event.
The con dition of the grouted floor tile joints and escape of
efflorescence from the balcony fascia supports this.
The construction of the structure did not influence the
cause for the waterproofing membrane to deteriorate.
A combination of factors lead to the wat erproofing
membrane failure, including:
the membrane initially applied was poor or defective
inadequate drainage
gradual deterioration, wear and tear of the membrane
temperature changes of the balcony surface
movement within the support joists
Balcony of u nit one:
Long - term water/moisture exposure (wet and dry) rotted
the timber joists supporting the balcony structure, which
compromised completely the integrity of the timber
support joists.
The structure is unsafe.
The balcony should be propped and not used.
Case No: 366212 Determination Page 5 of 5
Record Key points
The FSP’s building consultant incorrectly determined the
details of the balcony construction.
The Applicant’s engineer correctly reported the balconies
are compliant with building standards.