Denial of cracking and structural damage to home caused by leaking sewer pipe and storm water
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
claim-Exclusion/ condition
Determination
Case No: 363275 Determination Page 1 of 10
Case number : 363275 5 November 2014
1 Overview
1.1 Dispute
The Applicant lodged a claim under her farm insurance policy with the Financial
Services Provider (FSP) after her home suffered cracking and structural damage
on or around 2 March 2010. The Applicant initially attributed the damage to the
effects of a severe storm, but later identified the cause as being water leaking
from a broken sewer pipe discovered by her plumber in September 2010.
The FSP accepted the Applicant’s claim for water damage to her home caused by
the storm. However, it denied the Applicant’s claim for cracking and structural
damage on the basis that this damage was caused by flood and/or earth
movement.
1.2 Issues and key findings
Is the FSP liable for the damage to the Applicant’s house ?
The available information establishes that the cracking and movement damage to
the Applicant’s house was caused by earth movement resulting from the effects of
water leaking from the broken pipe, exacerbated by water ponding around the
house after the storm.
Damage caused in this manner is covered under the policy. The exclusion for
earth movement does not apply as this was not the proximate cause of the
damage. The FSP has not provided any information to establish that the damage
was caused by a “flood” as defined in the policy.
1.3 Determination
This Determination is in favour of the Applicant.
The FSP is to settle the Applicant’s claim for the cracking and movement damage
to her home in accordance with the terms of the policy.
If the Applicant’s claim is cash settled, the FSP is to pay interest on the settlement
amount at the rate determined in accordance with section 57 of the Insurance
Contracts Act 1984 (the Act) from 24 December 2010 until the payment date.
Case No: 363275 Determination Page 2 of 10
2 Reasons for Determination
2.1 Is the FSP liable for the building damage?
Application of policy depends on cause of damage
The Applicant’s policy provides cover for damage caused by certain events listed
in the policy, including storm and rainwater run-off, flash flood and water
discharging or overflowing at the property. The policy also provides cover for
accidental damage, which occurs in any circumstances not covered under one of
the listed events.
The policy contains general exclusions for damage caused by or as a result of
erosion, subsidence or any other earth movement, except where the damage is
caused by the insured events of flash flood or water discharging or overflowing.
Damage caused by flood is not covered under the policy, as the Applicant had
elected not to take out the optional flood cover available.
The Applicant says that the cracking and movement damage to her house was
caused by water escaping from a broken sewerage pipe under the concrete slab
in the bathroom, which washed the soil away from underneath the slab, creating a
large void which caused the slab to subside.
The FSP acknowledges the broken sewerage pipe, but disputes that this caused
the cracking damage to the Applicant’s home. The FSP says that the damage
occurred after the foundation soils became saturated following heavy rain, which
significantly reduced their bearing capacity and caused the slab to subside. The
FSP says that the damage to the sewerage pipe occurred as a result of the slab
subsiding.
Accordingly, it is necessary to determine the proximate cause of the cracking and
movement damage to the Applicant’s house (that is, the real, effective or
predominant cause).
Building damage was caused by effects of broken pipe and pooling water
The Panel has been provided with a number of reports from various builders and
engineers engaged by the parties to determine the cause of the damage to the
Applicant’s house. These reports are inconsistent in a number of key respects.
Having reviewed the reports provided, the Panel is satisfied that:
as a result of heavy rainfall during the storm on 2 March 2010, the Applicant’s
house was surrounded by water which pooled around the perimeter but did
not enter the house itself. The Applicant evacuated the house during the storm
and therefore is unable to confirm how long the inundation lasted. Various
estimates have been provided, ranging from a couple of hours to several
days;
major cracking damage to the house became apparent immediately after the
severe storm in early March 2010. This damage was localised to the north-
west corner of the house where the concrete slab had subsided. While there
Case No: 363275 Determination Page 3 of 10
were signs that the house had previously experienced movement damage, the
nature and extent of the prior damage was significantly less severe than the
damage which occurred in March 2010; and
in September 2010, the Applicant’s plumber discovered a cracked and leaking
sewerage pipe located under the concrete slab of the en suite bathroom in the
north west corner of the house.
Soil tests carried out at the property identified that the foundation soils were a fine
to medium grained sand and therefore would not experience significant volumetric
changes under ordinary weather conditions. The FSP’s geotechnical engineer
(AG) confirmed that rainwater would typically drain away fairly quickly from the
foundation soils. However, if they did become saturated, then their bearing
capacity would be significantly reduced.
Accordingly, it appears likely that the cracking and movement damage which is
the subject of the Applicant’s claim occurred as the result of a specific event,
rather than due to an ongoing pattern of earth movement.
Based on the available information, the Panel is satisfied that the leaking
sewerage pipe identified by the Applicant’s plumber was the proximate cause of
the subsidence of the concrete slab at the north-west corner of the house which
caused the resulting damage. In this respect, the Panel notes that:
the broken pipe is located in the corner of the house where the localised
damage occurred;
the photographs of the broken pipe taken by the Applicant’s builder in
September 2010 suggest that soil has been washed into the broken section of
the pipe and a void had developed under the slab;
the builder’s photographs show that the broken pipe remained encased in the
concrete slab. Accordingly, the crack in the pipe is more likely to have existed
before the subsidence (rather than having been caused by the slab subsiding)
and may have existed for some time; and
the FSP’s geotechnical engineer (AG) stated that water usually only ponds on
the surface of sandy soils when the soil has already become saturated. This
suggests that the soil may have already been partially saturated prior to the
storm event.
However, the Panel acknowledges that the pooling of water around the edge of
the building during and following the storm may have contributed to the damage.
Both the FSP’s geotechnical engineer (AG) and consult ing engineer (L) noted that
there was a depression in the ground along the front of the northern wall which
allowed water to collect. This may have resulted in more water pooling in this area
following the storm than in other areas around the building which (together with
the effects of the broken pipe) caused the slab to subside in the north-west corner
only.
Exclusions referred to by FSP do not apply
As outlined above, the Applicant’s policy provides cover where the proximate
cause of the damage is a leaking pipe, storm/rainwater run-off or flash flood, but
does not provide cover for damage caused by subsidence or flood.
Case No: 363275 Determination Page 4 of 10
In the present case, the exclusion for subsidence, erosion or other earth
movement does not apply as the subsidence of the slab occurred as a result of
the broken pipe, exacerbated by the pooling of water following the storm.
Accordingly, the subsidence of the slab (or the erosion of the soil underneath the
slab) was not the proximate or underlying cause of the damage.
The FSP has sugge sted that the pooling of water around the Applicant’s property
constitutes a “flood” (which is not covered under the policy), as opposed to a
“flash flood” (which is covered). However the FSP has not provided any
hydrological information to show that the pooling was caused by water escaping
or being released from the normal confines of a river or other natural watercourse,
as is required to satisfy the policy definition of “flood”.
The Panel notes that the available meteorological information shows that the
significant rainfall during the storm occurred within a 24 hour period between
2 March 2010 and 3 March 2010. Accordingly, to the extent that the pooling of
water around the Applicant’s property caused or contributed to the damage, the
Panel consider s that this is more properly categorised as “storm and rainwater
run- off” or “flash flood” as defined in the policy.
For the reasons outlined above, the Panel considers that neither of the exclusions
referred to by the FSP can be relied on in the present case. Accordingly, the FSP
is liable for the Applicant’s claim.
Case No: 363275 Determination Page 5 of 10
3 Supporting information
3.1 Approach taken by Panel
This dispute has not been the subject of a FOS Recommendation. Due to the
nature of the dispute, it has been referred directly to a Panel for Determination, in
line with the Operational Guidelines to the FOS Terms of Reference. The Panel
consists of an Ombudsman and two representatives with consumer and insurance
experience.
There has been a full exchange of all material information relied on for the
purposes of this determination and each party has had the opportunity to address
any issues raised by the other.
The Panel has reviewed all of the material provided by the parties, i ncluding the
various consultants ’ reports obtained. However, for the purposes of this
Determination, the Panel has limited its commentary to the matters which it
considers directly relevant to the outcome.
3.2 Terms of policy
Subject Terms
Insured event -
leaking of water
INSURED EVENTS
Bursting, leaking, discharging of water or liquids at the
insured address from:
pipes and taps …
drainage and sewerage systems
NOT INSURED
Repair or replacement of the tank, pipe or container that water or
liquid escaped from …
Loss or damage:
caused by flood …
Insured event –
storm and rainwater
run - off
INSURED EVENTS
Storm and rainwater run - off
NOT INSURED
Loss or damage caused by or because of: …
flood
but we will cover
- flash flood (Insured Event 6(b))
- flood damage if you are covered for flood damage under
(Option 3)
Insured event –
“flash flood”
INSURED EVENTS
Flash flood …
NOT INSURED
Loss or damage caused by or because of: …
Case No: 363275 Determination Page 6 of 10
Subject Terms
flood, if the rain that caused the flooding fell more than 24 hours
before the flood occurred
“Flash flood” - f lood or a combination of flood mixed with
rainwater run - off, caused by rain falling in the 24 hours
immediately before the Home or Contents are damaged by the
flash flood. It does not mean water from the sea.
Exclusion for
subsidence
We do NOT cover loss or damage
… caused by or as a result of erosion, vibration, subsidence,
landslip, landslide, mudslide, collapse, shrinkage or any other
earth movement
but we will cover …
Bursting, leaking, discharging or overflowing (Insured Event 7)
Flash flood (insured event 6(b))
Flood (if you have chosen and are covered by Option 3)
Definition of “flood” The covering of normally dry land by water escaping, overflowing
or being released from the normal confines of a:
river, creek or any other natural watercourse whether or not it
has been altered or modifi ed …
A “flood” is not water from: …
a burst or leaking pipe or water tank
3.3 Reports
Record Key points
FSP’s builder (D)
Report - 23 April 2010
The building was approximately 30 years old and built on
a concrete slab.
The Applicant had advised that the building had been
surrounded by approximatel y 100mm of floodwater which
had subsided after about five hours .
The building displayed severe structural failure
throughout, with major failure in one corner. The failure
was due to the construction methods used .
T he failure was not due to a single event but existed prior
to the storm. There was evidence of previous repairs .
FSP’s engineer (L)
Report - 1 July 2010
The house is in a very flat area and is not raised above
the surrounding land. This would result i n water ponding
around the house after rain.
T he recent high rainfall had softened the foundation
material resulting in subsidence of the slab and footings
that ini tiated the cracking damage to the building.
Subsidence was restricted to the damaged area with the
remainder appearing sound and unaffected. There was
evidence of previous cracking damage but not to the
extent currently observed.
As the soils were not reactive, the subsidence of the
perimeter footing was due to the loss of load bearing
capacity when the supporting soils were saturated by the
Case No: 363275 Determination Page 7 of 10
Record Key points
recent rainfall event.
The subsidence had broken or blocked the pipe draining
the vanity and shower .
Applicant’s engineer (B)
Report - 10 September
2010
The wall damage (crack ing) is due to soil movement
which was caused by leaking pipes .
The repairs carried out to address movement damage
caused by a leaking drainage pipe six years earlier were
still intact.
Applicant’s plumber (PS)
Report - 20 September
2010
He had dug down beside the house to gain acce ss under
the slab . T he damage to the slab was caused by a
broken pipe under the slab beneath the bathroom .
FSP’s engineer (L)
Report - 1 November 2010
The suggestion by the Applicant’s engineer (B) that the
damage was due to leaking pipes was not supported .
He would expect the service pipes to have sheared or
failed due to the building movement.
S oil experts (SQ) (jointly
appointed)
Report - 15 July 2011
T he foundation soils were classified as “S” (slightly
reactive) and therefore would exper ience only slight
ground movement from changes in moisture conditions.
Applicant’s engineer (B)
Report - September 2011
Design details for the co ncrete slab and footing system
we re unknown, however, the building wa s generally
stable.
There were no control joints in the masonry walling and
no steel reinforcement or core filling was apparent in the
cracked sections of the walls. This form of construction
was not unusual in the region.
The foundation soils were slightly reactive and would
lose strength if soaked.
The recent floodwater did not enter the building but only
enveloped the who le of the building perimeter (and the
inundation was not prolonged).
If the foundation soils had been soaked by floodwaters,
the damage would be more generally distribu ted rather
than localised.
The period of inundation was unlikely to have been long
enough for sufficient moisture to penetrate the soil below
the external wall footings so as to affect those footings.
The leaking sewerage pipe was approximately six metres
from the damaged area and therefore was also unlikely
to have caused the damage. [ Note: B later retracted
this opinion ]
While it was difficult to be certain, the pattern of damage
was consistent with e xcessive wind forces acting on the
building frame at the affected corner. [ Note: B later
retracted this opinion ]
FSP’s engineer (L)
Report - 12 December
2011
He agreed with the findings of the FSP’s geotechnical
engineer (AG) that the cause of the cracki ng damage
wa s a lack of soil bearing capacity in the saturated state,
which was a matter that should have been dealt with in
the design stage for the building.
The effect of soil saturation is critical for the building and
Case No: 363275 Determination Page 8 of 10
Record Key points
therefore the site should have be en classified as a
problem site.
FSP’s geotechnical
engineer (AG)
Report - 28 November
2011
Anecdotal evidence suggested that the area was flooded
for several months, and water was ponded to a depth of
about 150 millimetres in a depression along the north ern
side of the house for some time.
Water will normally only pond on the surface of sandy
soil s when the soil has become saturated .
There had been minor cracking only prior to the flood in
March 2010, which was probably associated with prior
flood events.
Tests found the soil to be a fine to medium - grained sand
with low plasticity silty grains. Soils of this type are very
susceptible to failure on saturation, which significantly
reduces the bearing capacity. In this case, it appeared
that the allowa ble bearing capacity of the soil had been
exceeded by the floods.
Given the high permeability of the soil, rainwater would
typically drain fairly quickly before the soil could become
saturated. Therefore, it is unlikely that normal rain
events, garden wate ring or leaking pipes etc. would
saturate the soils to a degree that the be aring capacity
would be reduced. This would require a large flood event
where there was so much water that it could not quickly
drain away .
FSP’s engineer (L)
Report s - 1 February 2012
and 6 February 2012
T he damage to the building is not cons istent with wind
loading damage .
In relation to why the damage had occurred primarily in
one area of the building, he notes that there was
evidence of previous settlement and repairs to damaged
walls and slabs at many different places around the
house.
There is evidence that settlement has not occurred in
one event but has been ongoing over many years.
The damage may have been localised in the north - west
corner because there was a depression in front of the
northern wall where water can collect. The Applicant
reported ankle deep ponding in this area after returning
to the house a week after the flood.
Applicant’s builder (RH)
Statement - 17 September
2012
Most of the damage was to the northern wall. The rest of
the building showed small cracks consistent with ongoing
marginal settlement only.
The subsidence in the northern corner was most
pronounced over a distance of 2.5 to 3 metres.
The pipe had broken on the lower side of the elbow and
an am ount of dir t was present in the pipe , which led
directly to the septic system.
If the footing had crushed the pipe (as claimed by the
FSP’s engineer (L)), the slab should have separated from
the footing. However, the vertical part of the PVC pipe
was firml y encased in the concrete slab, meaning the
footing, slab and pipe elbow had moved as one.
There was no pressure on the pipe from the footings and
Case No: 363275 Determination Page 9 of 10
Record Key points
no damage or indentations were visible to the pipe
except near the elbow where it had cracked.
Anecdotal ev idence suggested that a number of floods
had previously inundated the region with apparently no
major damage to the building.
After excavating the site and seeing the damage
firsthand, he was sure that the damage had been caused
by water from the cracked p ipe saturating the soils under
the slab .
Applicant’s engineer (B)
Letter – 13 March 2014
It was quite probable that leakage from the broken pipe
had caused the damage to the building.
Applicant’s engineer
(NM)
Report - 27 June 2014
He has carried out a desktop review of the various
reports regarding the cause of the cracking damage.
The assumption made by the FSP’s engineer (L) and
geotechnical expert (AG) that the house was on a strip
footing was incorrect. The photographs provided by the
Applicant’s bu ilder (RH) established that the slab was a
raft slab.
He modelled the maximum bearing pressure of the raft
slab and found that the bearing pressure of the slab in
saturated soil conditions was significantly less than that
determined by AG which showed tha t the foundations
had sufficient bearing capacity even in a saturated state.
Based on this, he concluded that the subsidence was not
caused by the flood in 2010 but by the undermining of
the slab by the broken sewer pipe .
FSP’s engineer (L)
Report s – 25 A ugust 2014
NM’s conclusion that the damage was not caused by
settlement is inconsistent with his conclusion that it was
caused by a broken pipe.
The building information does not establish that the slab
fits the requirements for a stiffened raft slab that would
provide load distribution.
The settlement has occurred due to bearing failure
(saturation of soils) and densification of the sand as the
water dissipates .
A broken pipe does not divert all the flow into the soils –
rather , very little water is lost a nd in silty sandy soils , this
water would flow vertically from the break, not laterally .
Further the Applicant had advised that the en suite
bathroom was rarely used.
The extent of settlement damage was not consistent with
a leaking pipe. It is simply not possible given the soil
profile for a leaking sewer pipe to sufficiently saturate the
soil in the damaged corner of the building. Displacement
associated with pipe leaks first shows as light cracking
but bearing is still maintained. It is progressive, and there
are enough warning signs to act before it reaches the
stage observed in the Applicant’s house.
He believes that the water ponded for a long time
adjacent to the building around the damaged area and
the highly permeable founding soils resulted in the
saturation of the corner of the building.
Case No: 363275 Determination Page 10 of 10
Record Key points
The pipe was sitting in loose backfill and it is likely that it
cracked because it had no support and hung from the
slab below the shower recess, as the soils dried out .
Applicant’s engineer
(NM)
Report - 15 Sept ember
2014
The damage was not due to the flood because the
bearing pressure was low and therefore the saturation of
the soil would not have resulted in settlement.
Settlement occurred due to the large void under the slab
created by the water from the broken sewer pipe washing
away the soil under the slab
T he foundations and slab met the standards applicable at
the time of construction. His analysis of bearing pressure
was based on the actual (not assumed) construction
methods.
The evidence establishes that ponding of water did not
occur for a long period of time, but for a few hours only.
The Applicant has confirmed that the en suite bathroom
was in use prior to the loss.
In September 2010 the plumber (PS) excavated down
the s ide of the building and found a large void area
underneath the slab and further excavation found the
broken pipe under the slab. It was these excavation
works which were the cause for the loose soil under the
bathroom identified by L (who assumed they were
associated with previous settlement issues) .
T he pipe was broken well before the 2010 damage
occurred and caused a large amount of silt and sand to
be washed out from under the slab leaving a large void
under the slab.