Denial of storm water damage claim under faulty workmanship and gradual deterioration exclusions
Summary
Building owners claimed for water damage from wind-driven rain. The insurer denied the claim under exclusions for faulty workmanship, faulty design and gradual deterioration, and AFCA agreed and found no breach of utmost good faith.
The insurer established on the balance of probabilities that the damage was caused by faulty installation of the doors and flashing, and that the policy's faulty workmanship, faulty design and gradual deterioration exclusions applied.
Issues
- Claim denial primary · not upheld
“The FSP is entitled to deny the Applicants' claim because it has established, on the balance of probabilities, one or more exclusions apply.”
- Poor claim handling secondary · not upheld
“There is no evidence to suggest the FSP has acted inappropriately; there is no information to suggest the FSP failed in its duty of utmost good faith.”
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
Claim
Determination
Case No: 357577 Determination Page 1 of 7
Case number : 357577 2 8 November 2014
1 Overview
1.1 Dispute
The Applicants lodged a claim for water damage sustained to their insured
building, against a defined events insurance policy. Water had penetrated the
building causing extensive damage to internal walls, skirting and floors.
The Financial Services Provider (FSP) denied the Applicants’ claim on the
grounds the damage had occurred over a period of time and was, on the balance
of probabilities, as a result of a structural defect or faulty design which allowed
water to seep into the property.
The Applicants reject the FSP’s denial of their claim and seek a review by the
Financial Ombudsman Service (FOS).
1.2 Issues and key findings
Is th e FSP entitled to deny the Applicants’ claim ?
The FSP is entitled to deny the Applicants’ claim because it has established, on
the balance of probabilities, one or more exclusions apply in order to defeat the
claim.
Has the FSP failed in its duty of utmost good faith towards the Applicants?
There is no evidence to establish the FSP has failed in its duty of utmost good
faith towards the Applicants.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is entitled to deny the Applicants’ claim.
Case No: 357577 Determination Page 2 of 7
2 Reasons for Determination
I have decided this dispute on its merits, doing what is fair in the all the
circumstances, having regard to the relevant law, good industry practice, codes of
practice and previous FOS decisions. I have taken into account all the material
submitted by the parties. I am satisfied that the documentation I have relied on
has been provided to both parties.
This dispute has been expedited to a Determination. No Recommendation was
issued.
2.1 Is the FSP entitled to deny the Applicants’ c laim?
The Applicant has established a prima facie claim
The onus of proof rests on the Applicants to establish, on the balance of
probabilities, they have suffered a loss caused by an insured event. This is known
as a prima facie claim. Once the Applicants have established a prima facie claim,
the onus shifts to the FSP to show, on the balance of probabilities, that an
exclusion applies to defeat the claim.
The Applicants ’ material supports water has entered the property during storms.
The FSP does not dispute wind driven rain has been the source of water entering
the property. Therefore, the Applicants have established a prima facie claim. The
onus is now on the FSP to prove an exclusion applies to defeat the claim.
The cause of the damage was faulty installation of the doors
The FSP relies on the information provided by the Applicants’ appointed builder
(BJ), the FSP’s appointed assessor (CL) and the FSP’s engineer (RB) in the
denial of the claim. These parties have confirmed in their reports that:
The relevant area of damage is to the western side of the property which is
subject to wind driven rain during storms.
It appeared water had been infiltrating the wall between two sliding doors at
the property and was most likely coming in around the flashing.
It appeared the flashing around the large sliding doors was either faulty or
wrongly installed. The sealant had deteriorated over a period of time.
Regular impact by the doors on the frame may have caused some opening or
damage to the flashings around the doors, allowing water to enter the wall
cavity.
Doors, frames and their associated flashings and sealants should be able to
cope with this sort of impact without failure. That they did not, suggests the
doors may not have been installed properly.
As the original doors had been replaced, RB was unable to be certain of this.
However, the pattern of damage suggests rainwater had been infiltrating
through or around the doors for a prolonged period.
There were no other identifiable causes of the water entry.
The Applicants submit that the FSP must construe ambiguous circumstances and
facts in a manner beneficial to the insured. They state the FSP’s experts are not
Case No: 357577 Determination Page 3 of 7
sufficiently conclusive in their opinion and that the FSP has not established the
cause of the dama ge “verified beyond doubt”.
The Applicants further state that the test of balance of probabilities requires a
state of actual persuasion of the occurrence or existence of the fact in issue
before it can be found. They state that in the present case, greater evidence
should be required by the FSP to prove its case because they:
have expended a significant amount of money in good faith
have not been responsible for any damage caused, and
are the victim of unjust circumstances.
According to the Applicants, the FSP should not be allowed to rely on
assumptions and suggestive comments, as opposed to conclusive facts, given the
gravity of the consequences for the Applicants which flow from such finding.
On the Applicants’ authority BJ replaced the sliding doors and flashing and
reconfigured the relevant area. RB inspected the property after repairs were
completed. There has been no complaint of any further damage since the repairs
were undertaken.
While the experts are unable to say with complete certainty what the cause of
damage is, they have proffered their opinions. In the absence of evidence to the
contrary, I am persuaded on the balance of probabilities, that the cause of the
damage was the incorrect installation of the flashing to the sliding doors which
has ultimately resulted in water damaging the property. This is a finding of fact I
make, acknowledging that this is not the fault of the Applicants nor were they in
any way aware of the damage given they had maintained their property well.
A relevant exclusion applies
Having determined that the cause of the damage was due to the faulty installation
of the doors, the FSP must establish that the cause falls within an exclusion within
the policy. The FSP refers to three possible e xclusions:
damage as a result of structural defects, faulty workmanship or faulty design
of the building
wear or tear and gradual deterioration, and
water seeping or otherwise percolating through a wall, floor or roof.
The cause of the damage falls withi n the first two of these exclusions being faulty
workmanship or faulty design. As such, there is no need to debate whether it falls
within the third exclusion relating to water seepage.
CL did not represent the claim should be accepted
There was much debate by the parties in respect of a statement by CL that the
Applicants say demonstrates CL was of the view the FSP was liable to pay their
claim. CL’s comment was:
“ The cause of the water entry was not previously evident to your insured and the home is
maintained in good condition, however, there appears to be grounds for denial of liability.
Case No: 357577 Determination Page 4 of 7
If, however , acceptance is given to the insured’s claim, we recommend that the insured
should incur the cost of rectifying the source of water entry as quoted at $3, 20 0. 00.”
This statement does not indicate CL was of the view that the damage was
covered by the policy. CL notes there are grounds for denial of the claim, but
offers that if the FSP disagrees and decides to accept the claim, then the
Applicants should still be liable for the cost of rectifying the source of water entry.
2.2 Has the FSP failed in its duty of utmost good faith towards the
Applicants?
The Applicants suggest the FSP’s continual denial of their claim and the FSP’s
reliance on its experts’ inconclusi ve reports, is a breach of the FSP’s duty of
utmost good faith towards them. The Applicants also assert that the introduction
of a new ground for rejection in the latest denial letter is a denial of natural justice.
The Applicants reported the claim to the FSP in July 2012 and after appointing CL
to make enquiries, the FSP denied the Applicants’ claim on 23 August 2012 via
their broker. The denial of the claim was again confirmed by letter to the
Applicants on 25 September 2012. There is no explanation for the delay between
these advices.
The Applicants first disputed the FSP’s denial of their claim by letter of 20
November 2012. The FSP maintained its decision by email to the Applicants on 5
December 2012.
The Applicants provided further information to the FSP on 18 February 2013 and
the FSP responded on 1 March 2013. The decision was again maintained and the
FSP responded to the Applicants’ particular concerns raised by them in their
letter.
The Applicants’ broker requested the matter be considered via the FSP’s Internal
Disputes Resolution (IDR) process on 20 March 2013. As a result of this request
and in an attempt to address the Applicants’ concerns, the FSP appointed RB to
provide a report on the cause and extent of damage to the Applicants’ property.
The relevant inspection occurred on 8 May 2013. After considering the contents of
RB’s findings and addressing the Applicants’ concerns the FSP confirmed the
denial of the claim in writing on 16 May 2013.
On reviewing the Applicants’ concerns, when and how they were raised and the
FSP’s actions in attempting to address the Applicants’ concerns, there is no
evidence to suggest the FSP has acted inappropriately. The FSP has reviewed
the material, appointed an engineer and addressed the concerns raised by the
Applicants in a timely manner, and certainly within accepted industry standards.
Therefore, there is no information to suggest the FSP failed in its duty of utmost
good faith towards the Applicants.
Case No: 357577 Determination Page 5 of 7
3 Supporting information
3.1 Relevant policy extracts
Policy wording
“ DEFINITIONS
…
“Storm” means a violent disturbance of the atmosphere, including strong winds which may
be accompanied by lightning, rain, snow, sleep and hail.
DEFINED EVENTS
…
7. Storm (see Definitions)
Excluding loss or damage caused:
…
(e) as a result of structural defects, faulty workmanship in the construction of the Building
or building at the Situation, faulty design of the Building or your failure to adequately
maintain the Building or building at the Situation.
…
SECTION 5 GENERAL EXCLUSIONS
These General Exclusions apply to the whole of your Policy unless otherwise stated. Your
Policy does not cover:
5.1 loss or damage to your property which is caused by, arising from or in any way
connected with:
(a) wear or tear, rust, corrosion, gradual deterioration and depreciation;
…
(j) faulty workmanship, inherent defect, errors or omissions in design, structural
defects and faulty design;
(k) water seeping or otherwise percolating through a wall, floor or roof;”
3.2 Reports
Report Key points
Applicants’ Builder ( BJ )
Undated report
Confirms extent of damage was not known until the skirt
was removed and the floating floor lifted.
Confirms the existing windows seemed to be installed
correctly however the water had entered on the stiles of
the wi ndows.
One of the Applicants’
appointed repairers (JJ)
Email report
10 January 2012
“There mus t be a small leak above the sliding doors for the
skirting in the living room to be damaged. From outside all
looks good. I suspect that it is a problem with flashing over
Case No: 357577 Determination Page 6 of 7
Report Key points
roof sheets and the water is finding its way down the internal
wall, but it is very hard to find that problem and solve it
without major investigation and expense.”
Real estate agent
24 February 2012
The plumber has inspected the roof and flashing, the
leaking is apparently coming through the cracks in render
on the wall which faces the west, extreme weather
conditions.”
Applicants’ builder (BJ)
Email report
14 August 2012
Con firms timber wall frames have rotted out, indicating
long term exposure to water.
FSP’s assessor (CL)
Report
15 August 2012
Water appears to be seeping into the wall cavity around
the sealant at the base of wall cladding on the first floor
causing the timber wall frames to rot.
Damage has been sustained over a period of time.
There are no water pipes in the vicinity and no evidence of
water entering the property v ia the roof.
No evidence the Applicants were or could have been
aware of the extent or cause of damage.
There is no evidence of deterioration or water entry along
the rear 1 st floor balcony, to the naked eye, however the
sealant has obviously deteriorated over a period of time
and there may have been inadequate water proofing /
flashing installed during original construction of the home.
The water damage has been from storm conditions,
however there is no indication it is from one singular event,
rather it has been occurring over a considerable period of
time with water entering the wall cavity.
The cause of the water entry was not previously evident
and the home is maintained in good condition.
FSP’s engineer (RB)
Report
8 May 2013
In general, the house w as in excellent condition and very
well maintained.
Discussions held between RB and BJ revealed the
flashings around the large sliding doors had been either
faulty or wrongly installed.
It was clearly apparent the damage to the building had not
been cause d by any single storm event, rather it had been
caused by slow and persistent infiltration of rain water
around or through the flashings attached to the original
sliding doors.
The infiltration has been unable to escape from wall and
floor cavities and has remained in place for long periods.
This has led to rotting of the timber members of both the
walls and floors.
No other windows at the property displayed concerns with
Case No: 357577 Determination Page 7 of 7
Report Key points
their flashings.
The subject sliding doors have been exposed to fairly
regular impact by the doors on the frame which may have
caused some opening or damage to the flashings around
the doors.
Normally doors, flashings and sealants should be able to
cope with this type of impact without failure indicating the
original doors may not have been installed properly.
The nature of the damage is consistent with gradual
deterioration.
The nature of the damage suggests the original sliding
doors had a fault or were not installed correctly or the
flashing surrounding the doors was not installed correct ly.
However, because the original doors had been replaced,
he was unable to be certain that this was the cause, but
the pattern of damage suggests that rainwater had been
infiltrating through or around these doors for a prolonged
period.
There does not ap pear to have been a structural fault with
the building when it was first built but the damage to the
wall studs and floor joists may have induced a structural
threat. This has been resolved with the repairs undertaken.
The internal damage to the timber me mbers in the walls
and floors appears to have be e n caused by gradual
deterioration and depreciation, probably du e to regular and
persis tent infiltration of water through or a round the
flashing to the sliding doors at the rear façade on the first
floor .