Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
claim
Determination
Case No: 356331 Determination Page 1 of 10
Case number : 356331 9 December 2014
1 Overview
1.1 Dispute
The Applicant holds a home building policy with the Financial Services Provider
(FSP) covering his residential property for a sum insured of $600,000.
On 9 August 2013 the swimming pool at the property was damaged and a claim
was subsequently lodged. After considering the claim, the FSP declined it on the
basis that the loss had not arisen as a result of any event which would be covered
by the policy. The Applicant disputes that decision.
This dispute has not been the subject of a Financial Ombudsman Service (FOS)
Recommendation. Due to its nature, it was appropriate to proceed directly to a
Determination in line with the Operational Guidelines to the FOS Terms of
Reference.
1.2 Issues and key findings
Was the FSP entitled to decline the claim?
The FSP was entitled to decline the claim because the loss did not arise as a
result of an insured event. Further, the loss arose as a result of causes
specifically excluded from cover by the policy.
1.3 Determination
This Determination is in favour of the FSP.
The FSP was entitled to decline the claim as the loss did not arise as a result of
any event which would be covered by the policy.
Insofar as the pool has sustained deterioration since the FSP’s decline of the
claim, this cannot be attributed to the FSP. The responsibility remained with the
Applicant to mitigate his exposure to further damage occurring once the claim had
been declined.
Case No: 356331 Determination Page 2 of 10
2 Reasons for Determination
I have decided this case on its merits, having regard to the relevant law, good
industry practice, codes of practice and previous FOS decisions. I have taken into
account all the material submitted by the parties.
There has been a full exchange of all documents relied on to make this
Determination and each party has had the opportunity to address any issues
raised by the other. Expert opinion has been provided by the parties.
The Applicant has provided a report from a plumber, DE, and an engineer’s report
from NC, whilst the FSP has provided reports from two engineers, FC and NJ.
Such opinions must be considered by me but they are not binding as I must weigh
them in the context of all the evidence in reaching a decision.
2.1 Was the FSP entitled to decline the claim?
The damage was not caused by an insured event
The FSP’s policy is a defined events policy. Therefore, the policy only responds
where the damage has been caused by one or more of the listed events, subject
to any exclusions. Three of these listed events are earthquake, explosion and
water damage from cracked or leaking pipes. The Applicant has, at various times,
attributed the loss to one or all of these events.
The Applicant has the initial onus of proving that an event covered under the
terms of the policy had occurred in order to establish a prima facie claim. Once
the Applicant has discharged this onus, it then shifts to the FSP to demonstrate
that one or more of the listed exclusions operates to defeat the claim.
For the sake of completeness, although the suggestion that the loss has been
caused by either earthquake or explosion appears to have been abandoned by
the Applicant, I am satisfied that there is no evidence to suggest either of those
events occurred to cause damage to the property.
Accordingly, this Determination will only address the issue as to whether a
cracked or broken pipe caused or contributed to the damage occurring.
The Applicant asserts that there is a leaking pipe in the pool surrounds, which has
caused hydrostatic pressure to build up to the point where the concrete casing
and inner liner of the pool have ruptured. In order to trigger the policy coverage, a
clear causal link between the leaking pipe and the damage to the pool must be
established.
The Applicant has provided numerous photographs and a videos showing the
pool, piping, water entering the pool and water gushing from a pipe, in support of
his case. He also has a report from plumber DE stating the leaking pipe has
caused the damage to the pool.
DE’s report has been considered , however, whilst a plumber is able to comment
on plumbing matters, there are limits on his qualification to comment on the
structural matters in issue. Accordingly, limited weight can be placed on DE’ s
Case No: 356331 Determination Page 3 of 10
report on the damage to the pool structure. DE’s report will be weighed in this light
with the other evidence and, in particular, the reports of FC and NJ on file. It is
accepted that FC and NJ are appropriately qualified and experienced to comment
on this matter and the FSP is entitled to rely on their findings. It is of note that
neither FC nor NJ attributed the failure to anything other than general wear and
tear, which is specifically excluded from cover.
The loss arose from causes specifically excluded from cover
After considering the available evidence, the Applicant has not provided sufficient
evidence to link the cracked pipe and/or its leak to the current issues which have
arisen. On this basis, the Applicant has not discharged the onus on him to
establish a valid claim under the terms of the policy.
Engineering firm FC inspected the pool on the FSP’s instruction. FC concluded
the damage had arisen as a result of the pool liner rupturing during the act of
cleaning/vacuuming the pool. The liner was old and brittle and the pressure of the
cleaning has caused it to rupture. FC considered there was no structural damage
to the pool and it could be restored to its pre -loss condition by the fitting of a new
liner.
Engineering firm NJ also inspected the pool on the instruction of the FSP. NJ also
concluded that the pool liner had most likely ruptured during cleaning as it had
reached the end of its serviceable life. NJ was in agreement that there was no
structural damage and the pool could be reinstated by the installation of a new
liner.
The Applicant disagrees with these findings and has provided his own engi neer’s
report from NC. NC’s report has been considered as part of this review .
In his report, NC does not mention the fact that the Applicant was cleaning the
pool at the time the damage occurred or that the liner was said to have ruptured in
the very spot that was being cleaned. This is a curious omission and it must be
asked whether NC was made aware of this fact by the Applicant. On balance, it
seems likely he was not.
Accordingly, NC’s report can only be considered to carry less weight than FC ’s or
NJ’ s as it appears likely he was not made aware of all relevant information, which
may have affected his conclusions in the matter.
In any event, NC has concluded that the cause of the structural failure evident at
the time of his inspection, some eight months after the loss occurred, was as a
result of the steel tensioning cable(s) breaking, causing the pre-cast panels to
separate due to no longer being able to contain the hydrostatic pressures. NC
states the steel cable(s) have broken because they were rusted out.
NC does not attribute the loss in any way to a leaking pipe.
On this basis, NC’s report does not assist the Applicant in establishing a valid
claim under the policy terms as the FSP’s policy specifically excludes loss or
damage caused by rust, gradual deterioration or wear and tear.
Case No: 356331 Determination Page 4 of 10
In a later emailed addendum report, NC agrees with the Applicant that if there
were a leaking pipe, this would hasten the rusting. However, it is notable that NC
does not say there is a leaking pipe. Rather, he just agrees that if there were one
(my emphasis), it would contribute to the rusting of the cables.
Such a statement is not equivocal evidence to suggest there is in fact a leaking
pipe, or that if there was one, the leak was a contributing factor to the loss.
Photographs of the alleged leaking pipe taken at the time of NJ’s second
inspection show the surrounding soil to be relatively dry, which is unsupportive of
the Applicant’s assertion that this area is responsible for a leak.
Further, NJ noted the crack was in the coupling rather than the pipe itself, making
it unlikely that any moisture was escaping. No water was observed to escape from
the area when water was introduced to the coupling. NJ did not consider the
cracked coupling had either caused or contributed to the event and stood by their
original conclusion that the liner had simply ruptured during the cleaning process,
due to its age and condition.
The Applicant has also not explained how a leaking pipe could fracture the
waterproof inner liner without damaging the concrete pool shell. Both FC and NJ
confirm that the pool remained structurally sound at the time of the respective
inspections. It is difficult to see how an external event, such as a leaking pipe,
could affect the liner without first damaging the concrete outer shell.
Whilst it seems apparent at the time of NC’ s inspection of the pool some eight
months after the loss had occurred, that there was structural damage which was
evident and NC considered the pool was no longer salvageable, this is likely due
to the pool being emptied of water for that period of time and the resultant
changes in hydrostatic pressure and the broken cabling rather than anything
related to the initial claimed event.
I am satisfied that the evidence presented supports the conclusion that the
damage to the pool has arisen as a result of the fracture of the liner during the
cleaning process, most likely due to its age and deteriorated condition. As the
policy specifically excludes loss or damage arising from any form of wear and tear
or gradual deterioration, the FSP has correctly declined the claim.
The pool has deteriorated after the refusal of the claim
Insofar as the pool has suffered structural damage and further deterioration since
the initial event occurring, such damage is not the responsibility of the FSP. The
FSP informed the Applicant his claim was declined on 14 August 2013, some five
days after lodgement.
Accordingly, it was the Applicant’s responsibility to ensure he mitigated his
exposure to further loss occurring by taking prompt remedial action to fix the pool.
He did not do so and any further damage cannot be attributed to the FSP.
Case No: 356331 Determination Page 5 of 10
3 Supporting information
3.1 Expert Evidence
Record Key points
FSP’s expert ( FC )
Engineer’s Report
23 Aug 2013
the owner reported that the liner of the pool was damaged
on 9 August 2013
the insured was cleaning the pool with a handheld vacuum
cleaner when he heard two loud noises consistent with an
explosion
the pool shook in response to these noises and within a
few seconds air injected into the pool via the north western
pool filter return line
the pool water became aerated like a spa
the internal pool liner floated up and a tsunami like wave of
water splashed over the northern pool wall
damage to the pool liner occurred as a result of the liner
floating
the pool was reportedly constructed in 1985
it is a segmentally constructed concrete pool consisting of
pre - cast concrete wall segments placed side by side and
fixed with a perimeter tensioning cable
the pool has an internal PVC liner which was the original
according to the owner
this places the liner as being 28 years old at the time of
inspection
previous patch repairs to the liner were evident and there
was a break in the liner evident at the western pool wall
the pool was partially de - watered at the time of inspection
the pool liner was found to be aged, weathered and
extremely brittle, it snapped and tore apart in hand
the floor of the pool was traversed and the walls inspected
visually. No significant deformations in the pool floor were
identified which would lead to a conclusion the floor and
wall elements had not sustained any structural damage
the pool water pump equ ipment was visually inspected and
appeared to be in sound condition although it was not
operational at the time of inspection. The loss adjuster had
inspected it previously and found it operated satisfactorily
there was no significant damage to the pool st ructural walls
or floor sufficient to cause explosion like noises
nor was there any damage to the pool that would have
been caused by an explosion or shaking of the pool
structure
the most likely explanation for the damage to the pool liner
is aged related deterioration, which has ruptured during the
cleaning process
it is possible rupture of the pool liner could have caused
some release of air and modest aeration of the pool
Case No: 356331 Determination Page 6 of 10
Record Key points
given the aged and brittle condition of the liner at
inspection, any rupture of th e pool liner would have
resulted in further rupture
the general lifespan for a pool liner is 10 - 15 years and
most manufacturers warrant their pool liners for 8 years
the liner has been damaged by long term weather and pool
chemical exposure which has cause d it to become weak
and brittle over time
it most likely ruptured during the cleaning operation
no structural damage was sustained in the incident
the pool liner can simply be removed and a new liner fitted
the new liner should be fitted promptly so as to prevent
leakage of pool water through the segmented pool
structure into the surrounding soils
failure to complete the recommended repairs in a timely
manner could result in structural damage
FSP’s expert ( NJ )
E ngineer’s Report
09 Sep 2013
a visual inspection was conducted of the site
the pool was constructed in 1985, the base is of in situ
reinforced concrete, the walls are of pre - cast concrete and
bound externally with a steel tension cable, with a vinyl
liner fitted internally
the liner h as been patched in the preceding five years
approximately three weeks ago the insured was
undertaking routing maintenance with a hand held vacuum
hose
the pool was filled to level at the time
during cleaning he heard two bangs like an explosion
which caus ed a shockwave and miniature tsunami of water
the insured believes the explosion caused a shockwave
bubbling of air and rupture of the liner
the insured believes the explosion may have been caused
by mining activity in the area or heavy rains in the past 1 2
months
a PVC pipe was installed at the time of construction
through the pool walls to allow any seepage which
migrates through the pool shell to drain out
subsequent to the damage occurring, the insured observed
water pouring out of the outfall
the pool filtration systems are all in working order including
the chlorinator
the insured pointed out cracking to the base of the pool
where water was seeping in from the ground and he
believes the concrete shell has been compromised due to
the pressure and this h as caused cracking which will
prevent the pool from being relined
the liner had been removed at the time of inspection
there were various silicon - type patch repairs evident to the
tiled section at the step outs
Case No: 356331 Determination Page 7 of 10
Record Key points
minor concrete shrinkage cracks were noted to the base of
the pool, with some minor seepage at the crack locations
a 50mm PVC pipe is installed through the western wall
near the base which has an outfall near the house. The
level of the outfall appears to be significantly higher than
the inlet
no evi dence of structural distress, damage or movement
was noted to the concrete pool shell
no obvious sources of combustible material or high
pressure vessels or gases were noted in the vicinity of the
pool
the insured advised the liner is 28 years old. Vinyl l iners
typically have a useful serviceable lifespan of around 10 - 15
years and are considered a renewable component of the
pool
liners become brittle over time as a result of exposure to
ultra violet radiation and pool chemicals
photographs shown by the insu red show the liner was at
least approaching, and possibly past, the end of its useful
life
the insured advised he was cleaning the pool in the
location where the liner ruptured and it is most likely that
the action of cleaning and the friction from the rub bing has
caused the brittle material to tear
there was no evidence of any explosion or shockwave in
the vicinity of the pool
the circumstances as described by the insured would seem
likely to have caused widespread damage to the pool shell
and surrounds and possibly injury to the insured
an explosion would require a combustible source to be
ignited or a sudden release of very high pressure. Nothing
capable of causing this was noted in the vicinity
the walls of the pool are relatively rigid and robust and
would not be expected to transmit any rapid externally
applied forces which might create a shockwave in the pool
any bubbling up of air likely originated from one or both
PVC pipes in the base of the pool, which would have filled
up with water when the lin er tore
the turbulence from air bubbles and the water moving to
the outside of the liner may have been sufficient to cause
progressive tearing around the pool
there is some relatively minor cracking to the pool base
which is normal concrete shrinkage, whic h affects most
concrete structures
no evidence of significant cracking, damage or movement
of the pool shell was evident or any indication it has been
overstressed
the property is at least 1km away from any area influenced
by mining and it is highly unlike ly the property has been
Case No: 356331 Determination Page 8 of 10
Record Key points
affected by mining works
the pool may be restored to its pre - loss condition by
installing a new liner
any replacement liner would have a service life of
approximately 10 - 15 years, after which it too would require
replacement
FSP’s expert (NJ)
Engineer’s report
22 Dec 2013
the pipework associated with the filtration system has been
exposed adjacent to the skimmer box, at a depth of
approximately 300mm below ground level
the pipework is of relatively small diameter, typical of pool
plumbing installations
a small crack was noted in one of the coupling pieces of
the pipework
the crack appears fresh with no dirt in or around the crack
a garden hose was used to introduce water to the pipework
and water was noted to flow out of one o f the water return
outlets as would be expected during normal pool function
no water was noted to escape from the cracked section of
pipe during the demonstration
the soil around the cracked section of pipe did not appear
to be damp
it is not possible to d etermine the age of the crack ,
however , it is possible the crack developed sometime after
the damage occurred to the pool liner
as the crack was noted in the coupling piece, it is possible
the pipe remained intact and therefore may not be resulting
in any moisture loss
typically, pool filtrations run between 3 - 6 hours a day which
would limit the amount of water able to escape from the
crack, if any
as the pool is effectively a closed system, should a
significant water loss occur as a result of a leak, the w ater
level would drop below the skimmer box and cease to be
able to flow into the return pipework, effectively limiting the
amount of water which is able to escape, unless the pool
were topped up on a regular basis
the requirement to top up would be unusua l and be a
signal to the owner that there was a problem. The insured
advised the pool was operating normally prior to the liner
being damaged
it is noted the cracked coupler is located well away from
where the damage to the liner originated
even if the amo unt of escaped liquid was sufficient to
trigger damage to the liner, it would not be expected to do
so on the opposite side of the pool
there were no indications of any movement or damage to
the pool shell having occurred which would be consistent
with a b uild - up of external pressure due to water escaping
Case No: 356331 Determination Page 9 of 10
Record Key points
in to the backfill
the crack in the PVC coupling does not represent a viable
mechanism by which the damage could have occurred to
the liner
NJ stands by the original conclusion that the age d and
brittle li ner failed during the process of vacuuming, which
cause d a progressive failure around the pool
the pool was still able to be reinstated to its pre - loss
condition by installation of a new vinyl liner
Applicant’s expert ( DE )
Plumber
01 Jul 2014
there is a water leak at the back of the pool on the pump
out line
the owner located the hole whi le excavating near the pool
the leak was coming from a high pressure fitting that was
cracked as a result of the leak
it has run down the back side of the pool and has u pset the
integrity of the pool
it caused the pool to shift and ultimately put pressure on
the liner and cause it to float then rip
Applicant’s expert ( NC )
Engineer’s report
16 Apr 2014
the pool is described as a module type construction built
approximately 25 years ago
the structure consists of a poured in situ base and pre - cast
wall panels held in place with a tensioned steel rope, and a
waterproof liner
in the event that water does get underneath the waterproof
liner it should drain out throu gh the relief pipe at the base
of the pool
the owner advised he has only seen this happen once or
twice over the life of the pool, each time has resulted in a
small tear or split of the liner, which was subsequently
repaired
the owner described the event w hen the damage occurred,
which was similar to a small localised earthquake creating
a loud noise similar to that of a car crash, creating large
waves and air bubbles in the pool water
this has resulted in large rips/tears in the liner and most
probably th e large extent of existing cracks in the shell
the owner conducted two experiments to show the damage
the first was pouring water down the existing pipe that
feeds water to the pool returns. After pouring water into
this pipe it was only a few minutes before it began to leak
the second aimed to show the extent of cracking in the
floor and walls of the pool. This was done by pouring water
down the back of the pool walls. After around 10 minutes
water started to weep through the cracks
although further in vestigation is required, the structural
event as described by the owner can only be explained by
Case No: 356331 Determination Page 10 of 10
Record Key points
a sudden release of stresses caused by one or more of the
tensioned steel ropes breaking
as the steel has rusted, it has eventually become too weak
to contain the pool’s hydrostatic pressure causing it to fail
this sudden release of stress has caused the waterproofing
liner to rip extensively and without adequate tension
holding the wall modules together, leaks have formed
making the pool unusable