Denial of storm roof and internal water damage claim under faulty design, workmanship and deterioration exclusions
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building – Home Contents – Service -
FSP Decision – Delay in Complaint Handling - Denial of Claim - Exclusion/Condition
Determination
Case No: 352257 Determination Page 1 of 10
Case number : 352257 2 7 November 2014
1 Overview
1.1 Dispute
The Applicants are the owners of two units which make up a duplex and are
insured under a strata title insurance policy held by the body corporate with the
Financial Services Provider (FSP). The Applicants lodged a claim under the policy
for damage to the roof of the units (and resulting internal water damage), due to
the effects of ex-tropical cyclone Oswald in January 2013.
The FSP denied the Applicants’ claim on the basis that the damage was not
caused by the severe weather events but by matters which were excluded under
the policy, such as faulty design and faulty workmanship, gradual deterioration
and wear and tear.
1.2 Issues and key findings
Is the FSP liable for the damage to the property?
The available information (including the engineers’ reports ) establishes that, on
the balance of probabilities, the proximate cause of the internal water damage to
the property was the faulty design and installation of the metal tile roof. Damage
caused in this manner is not covered under the policy. The lifting of the roof tiles
was not caused by the cyclone, as this damage was already present in 2010.
Section 46 of the Insurance Contracts Act 1984 (the Act) does not assist the
Applicants, as the application of the policy exclusions relied on by the FSP does
not depend on the defects in the roof having existed before the date the policy
was taken out.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is not liable for the Applicants’ claim.
Case No: 352257 Determination Page 2 of 10
2 Reasons for Determination
2.1 Is the FSP liable for the damage to the property?
Application of policy depends on cause of damage
The strata title policy provides cover for accidental damage to the Applicants’
property, subject to the conditions and exclusions set out in the policy. In this
context , the courts have interpreted “accidental” to mean “unintended and
unexpected.”
The policy contains exclusions for accidental damage caused by:
a defect in an item, faulty workmanship, structural defects or faulty design or
rust, corrosion, gradual deterioration, wear or tear, wet or dry rot.
The Applicants say that the damage to the roof at their property (and the resulting
internal water damage) occurred when a number of the metal roof tiles were
dislodged during the severe storm events in January 2013.
However, the FSP says that the damage to the roof was not caused by the storms
but was due to faulty design and workmanship during the construction of the roof
and/or gradual deterioration over time. The FSP says that it was the existing
condition of the roof at the time of the storm which allowed water to enter the
property.
Accordingly, it is necessary to determine the proximate cause of the damage to
the roof of the Applicants’ units (that is, the real, effective or predominant cause).
As the FSP is seeking to rely on a policy exclusion to deny the Applicants’ claim, it
bears the onus of establishing that, on the balance of probabilities, the relevant
exclusion applies.
Water entry was caused by factors excluded under the policy
The Panel has been provided with a number of reports from various builders and
engineers engaged by the parties to determine the cause of the internal water
damage to the Applicants’ property.
Having reviewed the reports provided, the Panel is satisfied that, on the balance
of probabilities, the proximate cause of the water entry to the Applicants’ property
was the incorrect installation of the metal roofing tiles and, in particular, the
inadequate measures undertaken by the installer to ensure that the roof was
watertight.
Both of the engineers appointed by the FSP and the Applicants (SW and JH)
concluded that water entry had been occurring through the roof over an extended
period of time. Both engineers identified several aspects of the design and
installation which were deficient and/or non-compliant with the manufacturer’ s
specifications at the time of construction. In particular, the manner in which the
lead flashing was installed at the juncture of the gable walls was considered to be
ineffective to prevent water entry in this area and had also resulted in the flashing
deteriorating over time.
Case No: 352257 Determination Page 3 of 10
SW and JH are appropriately qualified to determine the cause of the water entry
and the Panel considers that their reports set out a logical and reasonable basis
for their conclusions, which is consistent with the available information. In
particular, the Panel notes that:
the areas in which water entry was observed correspond with the areas where
the engineers have identified deficiencies in the design and installation of the
roof
the photographs included in the engineers’ reports show clear evidence of
prior water damage in these areas, as well as signs of previous repairs
intended to prevent further water entry (including the extensive use of
expandable filler foam and silicone sealant). The Applicants have confirmed
that they did not undertake these repairs. Accordingly, it appears that the
water entry issues pre- existed the Applicants’ purchase of the property
approximately four years ago.
The Applicants dispute the findings of SW and JH and have provided reports from
their roofing specialist (VT) and their builder (CB) in support of their position.
However, while VT and CB conclude that the storm resulted in eight of the metal
roof tiles being dislodged, they do not explain how the damage to these tiles
correlates to the areas of water damage observed at the property. Further, CB
refers to the possibility that at least some of the damage has been caused by
leaking flashings and sealants, but does not explain how these leaks have been
caused by the storm (rather than having occurred as a result of the design and
construction issues identified by SW and JH).
For the reasons outlined above, the Panel is satisfied that the internal water
damage to the Applicants’ property has been caused by factors excluded under
the policy, namely faulty design and workmanship and gradual deterioration.
Loose roof tiles were pre-existing damage
The various consultants engaged by the parties have provided differing views as
to the cause of the eight or so roof tiles lifting.
SW concluded that this damage was caused by pre-existing corrosion of the tiles,
which made them vulnerable to the excessive winds experienced during the
storm. However, JH disputed that the relevant roof tiles were corroded and
considered that they had lifted due to the extraction of the nails affixing them to
the battens (presumably due to the force of the winds).
However, the Google street view of the property taken in January 2010 shows
that the roof tiles were already dislodged at this time. JH has confirmed that the
dislodged tiles observed during his inspection were in the same area as the tiles
shown in the photograph from January 2010.
On this basis, the Panel is satisfied that the damage to the roof tiles was not
caused by the effects of ex-tropical cyclone Oswald in January 2013. Accordingly,
the FSP is not liable for this aspect of the claimed damage.
Case No: 352257 Determination Page 4 of 10
Section 46 of the Act does not apply
The Applicants say that section 46 of the Act operates to prevent the FSP from
denying their claim.
Section 46 of the Act prevents an insurer from relying on a policy exclusion which
operates by reference to a defect in a thing which existed before the policy was
taken out, in circumstances where the insured was not aware (and a reasonable
person in the circumstances could not be expected to have been aware) of the
defect at the time the policy was taken out.
However, the courts have confirmed that section 46 of the Act only applies where
the exclusion relied on by the insurer operates by reference to the time at which
the relevant defect arose.
The exclusions relied upon by the FSP in the present case apply to damage
which was caused by faulty design and workmanship and/or gradual deterioration,
irrespective of when these issues arose. As these exclusions do not expressly
refer to the relevant defect having been present before the policy was taken out,
section 46 of the Act does not operate to assist the Applicants.
Case No: 352257 Determination Page 5 of 10
3 Supporting information
3.1 FOS approach to this dispute
This dispute has not been the subject of a FOS Recommendation. Due to the
nature of the dispute, it has been referred directly to a Panel for Determination, in
line with the Operational Guidelines to the FOS Terms of Reference. The Panel
consists of an Ombudsman and two representatives with consumer and insurance
experience.
The Panel has decided this case on its merits, having regard to the relevant law,
good industry practice, codes of practice and previous Financial Ombudsman
Service (FOS) decisions.
There has been a full exchange of all material information relied on for the
purposes of this Determination and each party has had the opportunity to address
any issues raised by the other.
The Panel has reviewed and considered all of the material provided by the
parties. While the parties have raised a number of issues in their submissions, for
the purposes of this Determination the Panel has restricted its commentary to
those issues which it considers directly relevant to the outcome only.
3.2 Terms of policy
Subject Terms
Accidental damage
cover
We will cover your buildings, y our common contents and your
common property for any accidental damage or accidental loss …
Exclusions We will not cover your buildings and your common contents and
your common property for accidental damage or accidental loss
caused by:
Rust, corrosion, gradual deterioration, wear or tear, wet or dry
rot …
A defect in an item, faulty workmanship, structural defects or
faulty design
3.3 Reports
Report Key points
FSP’s building
consultant (EP)
Report - 14 Aug ust
2013
The water entry to the units was due to a number of
maintenance related issues and was not the resul t of a single or
a recent storm .
The pre - existing raised roof tiles (as evident in the Google
street view from January 2010) had resulted in other roof tiles
becoming raised over time.
Wa ter had be en entering over time through cracks in the roof
flashings and fibre cement cladding and dented roof tiles .
Case No: 352257 Determination Page 6 of 10
Report Key points
FSP’s engineer
(SW)
Initial report - 17
October 2013
The Applicants had advised that the property was built in the
1980s and they had owned both units for around four years.
There was evidence of water entry in various locations in both
units .
T he timber battens were in good condition for the age of the
roof .
A number of the roof tiles had previously been replaced ,
apparently prior to the Applicant s purchasing the property .
F iller foam s were present in several areas where water had
entered through the roof, indicating that this had occurred
previously.
There were a few areas of minor separations of up to 2mm
between the timber battens and the roof trusses . However,
these were localised and were due to the geometry of the high
pitched roof during installation and timber shrinkage. Other
minor instances of separation were not considered to constitute
batten uplift.
There was significant rust and dete rioration at the lap of the top
tile and the lower tile. In some areas, this deterioration was
significant enough to result in the nail fixing becomi ng
inadequate so that the tile could move freely.
The front areas of the roof were in good condition with m inimal
denting and deterioration of the roof tiles .
However, the rear was in poor condition with the majority of the
roof tiles dented and the protective coating worn away in a
number of the lower sections (where access was available).
There were a number of fixing nails missing leaving holes in the
tiles, allowing direct water entry . The tiles showed evidence of
previous silicon use, indicating prior water entry.
The f ront dividing wall had a flashing installed between the wall
and the roof tiles. The edge tiles had not been turned up into
the flashing to prevent water entry. There was n o parapet
flashing on the top of the dividing wall .
In the area above the living wall of unit 2 where water entry had
occurred, the metal tiles were not turned up into the flashing
correctly and the flashing exceeded the maximum allowed
length and had cracked, allowing water entry.
The lead flashing at the rear of unit 1 had previously been cut
and glued down onto the metal tiles with evidence of previous
repairs using s ilicon filling .
A number of metal tiles had separated from the timber battens
over the entire roof due to prolonged corrosion at the
connection point which had weakened the fixing, making it
vulnerable to lifting during excessive winds .
No flashing had be en used on the storeroom window in unit 2
which ha d allowed water to seep through the frame.
None of the damage was due to the storm and was the result of
issues which had been d eveloping since completion of
construction.
Case No: 352257 Determination Page 7 of 10
Report Key points
Where metal roof tiles are used, the roof top needs to be
correctly installed and waterproofed to reduce the risk of water
entry. The installation at the Applicants’ property was deficient
in a number of respects.
FSP’s engineer
(SW)
First supplementary
report – 28 October
2013
The proximate cause of water entry during the January 2013
storms was defective workmanship of the roof. Had there been
no issues with the roof at the time of the storms, no further
damage would have occurred.
The evidence of previous repairs to the roof indi cated that water
entry had been occurring for a n extended period of time.
The storm had not caused any externa l structural damage . The
l ifting of the roof tiles was die to gradual deterioration and/or
lack of maintenance.
FSP’s engineer
(SW)
Second
suppl ementary
report
19 December 2013
The w ater entry during the storms did not caused ad ditional
damage as water entry had been occurring over a prolonged
period of time. There is no damage that could be attributed to
the storm event alone.
The presence of ro tting timber indicated that there had been
persistent water entry over a prolonged period of time.
The Applicants would have been aware of the water entry
during the four years since they purchased the property.
His earlier comments about the need for a b ox barge were
based on the manufacturer’s specifications.
The water stains directly underneath the filler foam indicate that
it was installed to prevent water entry, not vermin.
He observed corrosion on all of the lifted roof tiles. The
corrosion was significant and not at an early stage.
Applicant’s builder
(CB)
Report – July 2013
The Applicants’ unit required re - roofing as there were panels
that had lifted and could be blown off in the event of future high
winds. Water was entering through these areas causing further
damage.
The timber trims, external cladding and eave lining had become
wet and damaged and were leaking due to water entering
through the roof. These items would require replacement.
Water was possibly being blown in around the window s
because the flashings and/or sealants were leaking.
Applicant’s roofing
contractor (VT)
Report - undated
He inspected the roof on 23 May 2013 and again on 8 October
2013 .
His i nternal inspection revealed the roof to b e in good condition
for its age, oth er than eight metal roof tiles which had been
lifted during the storm.
He disagrees with the FSP’s contractors that the flashing has
been poorly designed and notes that b ox barge flashing could
not be used due to the fact that the external wall for the upper
level intersec ts with the roof cladding at right angles . The
installation of a lead apron flashing at this junction was
standard practice at the time the units were built .
The roof tiles in the area of the dividing wall between the units
Case No: 352257 Determination Page 8 of 10
Report Key points
we re not re quired to be turned up , as the high point of the roof
tile acts as the turn up . The lead overlaps the high point,
preventing water from entering the ceiling cavity. Th is design is
widely used for tiled roofs of this type .
There was m inor deterioration of the roof tiles at the rear of the
property where the tiles overlapped, causing condensation to
travel between the two pitches. This deterioration was to be
expected considering the age of the building but was not
present throughout th e entire roof.
The tiles had lifted as a result of nails being dislodged during
the storm and not due to corrosion.
Applicant’s
e ngineer (JH)
First report – 28
January 2014
His inspection of the roof tiles on the A frame section of the
building was limit ed to a visual inspection from the top of a
ladder, due to the extreme pitch of this section of the building.
His v isual inspection of the rear section of the roof revealed that
the m ajority of the tiles were well anchored by nail fixings along
the ir bott om edge.
There were o nly a couple of isolated areas toward the top of the
roof where the bottom edge of a couple of sheets of tiles had
been dislodged from their nail fixings . This is a direct result of
the extreme wind pressure associated with ex - tropica l cyclone
Oswald.
The tiles at the base of the roof near the gutter had slight
rusting along their bottom edge, which was caused by
electrolysis between the bottom of the tile and the gutter.
Due to their nature, the bottom row of tiles were “face - fixed”
with a flat - head nail through the top face of the tile into the
timber batten.
In several locations , the se nails were found to be loose and
easily extracted by hand indicating the y had lost co nnection into
the batten s (either because the batten was in the wrong
position or due to wood rot ). As a result, the front edge of the
bottom row of tiles was loose. This was a maintenance issue
unrelated to the storm.
His inspection of the r oof tiles from inside the roof confirmed
that they were in very good condition and free of any corrosion ,
especially at the side and bottom laps .
There were other isolated areas whe re the bottom edge of the
tiles had been pulled away from their nail fixing. In one case ,
the loose tile edge could be separated from the timber batten
by hand. The location of the old nail hole showed that the tile
had originally been firmly fastened.
There was e vidence of serious water ingress in unit 1 in at least
two places, both of which were due to poor and gaining lead
flashings on top of the roof . In both locations, the metal tiles
had been “flashed” against an adjacent external wall with long
strips of lead, which had developed stress fractures at the turn -
up from the roof tiles to th e wall face over the years.
Some roof maintenance ha d been undertaken to seal these
Case No: 352257 Determination Page 9 of 10
Report Key points
fractures using filler foam , which appeared to be working under
normal rain con ditions. However, the severe weather conditions
in January 2013 would have exceeded the capacity of the
repaired flashings , allowing water to enter .
The lead flashing was not of the correct weight for the location
and had been installed in too long a length. New lead flashing
should be installed to provide a water tight seal.
There was n o evidence of any separation of the timber roof
battens from the tops of the roof trusses , as a result of
excessive wind force during the storms in January 2013 .
Applicant’s
engineer (JH)
Second r eport – 31
March 2014
(prepared for the
FSP)
He had re viewed his previous findings after considering EP’s
and SW’s reports.
The a reas of internal water damage are located directly under
the gable walls where they extend up past the pitch of the roof.
The c ause of the water leaks was poor installation of the
flashing s , with the flashings not properly extended through the
thickness of the wall and installed over too long a length. The
storm event merely highlighted the inadequacy of the flashings.
The roof had been leaking in the same areas long before the
storm event in Jan 2013. The installation of filler f oam under the
flashings was undertaken by the previous owner and therefore
the attempted repairs were at least 4 years old.
The s evere water stain s visible on the timber trusses and
beams in these locations confirmed that the water leaks had
been an ongoing problem for many years.
T he roof tiles had not been correctly installed at the gables , so
as to prevent wind - driven rain from being blown sideways
across the surface of the tile and spilling off the edge u nder the
flashings .
The installation of the lead flashing was not undertaken in
accordance with the manufacturer’s recommendations (as at
the time of construction).
There was n o real evidence of any batten lift.
He disagrees with SW’s finding that corrosion was responsible
for the lifting of tiles and considers that this was due to the
extraction of the face - fitted nails holding the tiles to the timber
batten.
He considers that the areas where corrosion was identified did
not correspond with the lo cations of water entry.
However, this had not been caused by the storm in January
2013, given it was already apparent in the Google street view
image from 2010.
3.4 Section 46 of the Insurance Contract Act 1984
Section 46 Pre-existing defect or imperfection
46 (1) This section applies where a claim under a contract of insurance (other than a
contract of insurance that is included in a class of contracts declared by the
Case No: 352257 Determination Page 10 of 10
regulations to be a class of contracts in relation to which this section does not
apply) is made in respect of a loss that occurred as a result, in whole or in part,
of a defect or imperfection in a thing.
46(2) Where, at the time when the contract was entered into, the insured was not
aware of, and a reasonable person in the circumstances could not be expected
to have been aware of, the defect or imperfection, the insurer may not rely on a
provision included in the contract that has the effect of limiting or excluding the
insurer's liability under the contract by reference to the condition, at a time before
the contract was entered into, of the thing.