Home / Financial Firm (Unknown - Insurer) / Determination 348411
Determination 348411
Claim denial: storm damage to garage under faulty design or structural defect exclusion
Summary
The insurer denied a storm damage claim for a garage as caused by faulty design or structural defect. AFCA found the insurer had not proved that exclusion and ordered the claim paid, plus container storage costs and 50% of the engineer's report cost.
The insurer bore the onus of proving the exclusion, and its evidence did not establish that the garage failed to meet building standards when built.
Subjects and remedies
home or building damagenatural disasterpay claimpay compensation
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
Claim
Case number : 348411 10 August 2015
1 Overview
1.1 Dispute
The Applicant lodged a claim for storm damage to his garage.
The Financial Services Provider (FSP) denied the Applicant’s claim on the
grounds the garage caused by faulty design and structural defect.
The Applicant disputes the FSP’s decision to deny his claim. He seeks to have his
claim accepted and repairs to his property paid for by the FSP. The Applicant also
seeks reimbursement of his costs associated with:
obtaining an engineer’s report
the cost of hiring a shipping container to store the contents of his garage while
awaiting the FSP’s decision.
1.2 Issues and key findings
Has the Applicant established a claim under the terms of the policy?
The Applicant has established a claim under the terms of the policy as the policy
is an accidental damage policy and there is no dispute that the Applicant’s
property was damaged following a storm.
Is the FSP entitled to refuse the claim?
The FSP is not entitled to refuse the claim. The FSP has not established on the
balance of probabilities, the application of the exclusion relating to faulty design or
structural defect.
1.3 Determination
This Determination is in favour of the Applicant.
The FSP is liable to meet the Applicant’s claim, including any relevant repairs to
bring the property up to current standards.
Subject to the Applicant providing relevant invoices the FSP is to pay the
Applicant’s costs of hiring a shipping container and 50% of the cost of the
engineer’s report.
Case No: 348411 Determination Page 2 of 7
2 Reasons for Determination
2.1 Has the Applicant established a claim under the terms of the
policy?
The Applicant has established a claim under the terms of the policy.
The Applicant’s policy provides cover for accidental damage subject to relevant
exclusions.
There is no dispute that the Applicant’s property was damaged during a storm on
28 November 2012.
The Applicant advised the Assessor he believed a lightning strike at the front of
the house during the storm caused the damage. The Assessor found no visible
marks where the lightning had struck, but acknowledged impact damage. He
could not confirm it was a lightning strike as the main power was not affected. The
Applicant subsequently provided an invoice from an electrician confirming the
need to reinstate the electricity following the lightning strike.
I also note that the FSP’s structural engineer KC indicated it was hard to
determine whether the damage was caused by the lightning strike or storm,
although he believed the Applicant’s statements add credibility to the Applicant’s
claim. He confirmed that the wind forces would also have caused damage.
Regardless of whether the damage was caused by the lightning strike or high
winds, the damage would be assessed under the terms of the policy as accidental
damage being damage that was sudden, unintended and unexpected.
The onus is therefore on the FSP to establish the application of an exclusion if it is
to refuse payment of the claim.
2.2 Can the FSP refuse payment of the claim?
The FSP has not established the application of an exclusion
The FSP maintains that the damage sustained to the Applicant’s garage was a
result of the failure to secure the roof truss with bottom cord tiles. The FSP
maintains that this is defective building work and seeks to rely upon the general
exclusion that relates to:
a defect in an item, faulty workmanship, structural defects/faulty design
A building consultant SG considered that the roof truss did not have bottom cord
ties and that this was a failure to meet the appropriate Australian standards. In his
initial report, SG referred to standards introduced in 1997 which related to timber
roof trusses. SG recommended a structural engineer be appointed.
The FSP appointed KC to undertake relevant structural engineering
investigations. KC identified the garage roof system as being a light weight steel
truss with steel sheet roofing. The trusses ran parallel with the garage door and
he noted there was cross bracing located underneath the roof sheeting, supported
Case No: 348411 Determination Page 3 of 7
by a hard wooded beam running across the brick piers. The beam was tied down
to the brickwork via a galvanised steel strap. He noted that normally a strut or
multiple struts would be provided at the bottom cord of the truss.
SG provided a supplementary report on 21 August 2013. On this occasion, SG
referred to the relevant standards for domestic metal framing. There is no
reference in those standards requiring a light gauge steel truss to be secured by
bottom cord ties. SG believed industry best practise at the time the garage was
built in 1995/1996 would be to have bottom cord ties. On this basis, he did not
believe the roof had been braced in accordance with domestic Australian
standards.
I note from the supplementary report he confirms that there were brick tie downs
and dynabolts hanging from the truss that were removed as part of the clean up.
Significantly, in an email to the FSP, SG concedes that the relevant Australian
standards relating to the bracing do not specify what is required in order to comply
with the standards and in these circumstances, it may therefore be difficult to
determine whether the construction does comply.
The Applicant provided a report from his own engineer WB, an engineer of 38
years experience. WB disagreed with the findings of SG but did not comment on
the use of bottom cord ties on the truss.
I do not accept that the evidence from SG establishes that there was no bracing.
There is evidence of brick tie downs and dynabolts hanging from the trusses,
evidence of cross bracing underneath the roof sheeting and evidence that the
truss was supported by a hard wood beam.
The Applicant has provided evidence that the work on the property was approved
by the council and following inspection of the roof frame in April 1996, the building
was considered suitable for occupation.
In the circumstances, I am not satisfied the evidence as presented by the FSP is
sufficient to establish on the balance of probabilities that at the relevant time when
the property was built, it did not reach relevant building standards.
I am not satisfied the FSP has established that the damage sustained was due to
a defect, faulty workmanship, structural defects or faulty design.
Other matters
The Applicant has sought, in addition to the cost of repair of the home, the costs
of having to purchase a shipping container to store items and the costs of
engaging an engineer.
I accept that the Applicant has incurred the additional cost to store the items. I am
satisfied that the Applicant is entitled to be reimbursed for such costs incurred in
accordance with the terms of the policy, subject to the Applicant providing a
relevant invoice for those costs prior to payment of the same.
Case No: 348411 Determination Page 4 of 7
Insofar as the Applicant’s claim for the cost of the engineering report, paragraph
9.4 of the Terms of Reference provide that FOS may decide an FSP contribute to
such professional costs incurred in the course of a dispute.
In determining whether an FSP should contribute to such costs, it is appropriate to
consider the complexity of the issue in dispute, whether the expert assistance was
required and whether it assisted in the dispute.
The report from WB was brief. Whilst he disagreed with SG, he did not address
the main issue that is, whether the roof required the truss be secured by bottom
cord ties.
The report was of limited assistance in resolving the dispute. In the
circumstances, I am of the opinion the FSP should contribute 50% of the cost of
obtaining the report subject to the Applicant providing the invoice to the FSP.
Case No: 348411 Determination Page 5 of 7
3 Supporting information
3.1 Policy wording
The following wording from the Product Disclosure Statement is relevant to this
matter:
“ Accidental Damage cover
What is covered
…
We will cover your buildings and your cont ents for accidental loss or accidental
damage. There is some loss or damage we will only cover under specific conditions.
…
What we will not pay for
We will not cover your buildings and your contents for any accidental loss or
accidental damage caused by:
…
A defect in an item, faulty workmanship, structural defects or faulty design.
…
Additional things we will pay for when you have insured your buildings
If you have cover for your buildings, the following will be paid in addition to the sum
insured as listed on your schedule.
We will pay these costs when they relate to loss or damage caused by or arising from
accidental loss or accidental damage that is covered by this policy:
…
We will pay the costs necessary to meet the requirements of any statutory
authority in connection with rebuilding or repairing the buildings at the situation.
We will not pay any costs which re sulted from any notice which a statutory
authority served on you before loss or damage to your buildings occu rred.
The most we will pay in any on period of insurance is $25,000.”
3.2 Expert evidence
Record Key points
Council Approval
Documents
Dated 1994 - 1996
Part A indicates the property was inspected by a building
surveyor and approval was granted subject to conditions,
on 31 May 1995. One of those conditions was “Engineer
details of roof trusses being submitted to council prior to
loading roof.”
Part C shows records of inspection. The only further
inspection relevant to the roof was 26 April 1996. This
reads: “Roof frame inspection. O.K. Spoke to owner re -
flashings in wet areas.”
The building surveyor permitted occupation of the
premises on 9 August 1996.
FSP’s Builder ( RG ) House was not structurally stable and a make - safe was
Case No: 348411 Determination Page 6 of 7
Report
12 December 2012
undertaken. The Applicant had removed the damaged
roller doors and some bricks.
House has been impacted by something, probably not
lightning.
Substantial damage done to garage and interior fittings.
Recommend a structural engineer to attend.
FSP’s Buildin g
Consultant ( SG )
Report
14 March 2013
Three roller doors and brickwork were observed as
damaged and piled adjacent to the front of the garage.
There was no evidence of a lightning strike to the building.
The garage was constructed of single skin brick wal ls with
engaged piers on a concrete slab.
Metal roof sheeting was supported by light gauge welded
trusses at approximately 900mm centres.
There were no bottom cord ties from the steel truss at the
front of the garage which would have tied it to the
remai ning roof trusses.
The front wall of the garage had brick columns supporting
three steel lintels over the roller doors which support five
rows of double brickwork. The top of the double brickwork
was tied to the bottom cord of the truss.
Australian Standar d (AS) 4440 details the installation of
nailplated timber roof trusses, including appropriate
bracing. The Applicant’s garage roof does not meet this
standard.
The cause of the damage is due to racking forces from
strong winds caused the partial collapse of the front wall of
the garage due to failure of the installation of bottom cord
ties attached to the bottom cord of the truss in accordance
with AS 4440, section 4, clause 4.4.1.
SG Supplementary
Comments
Report
21 August 2013
The correct AS applying to this property is AS 3623 – 1993
and states: “This Standard sets out the performance
requirements, in terms of structural adequacy and
serviceability, for the framing of domestic buildings of up to
two storeys in height and roof pitches of up to 35 .”
Sect ion 2 of AS 3623 – 1993, part 2, clause 2.7.1 states,
“Permanent bracing shall be designed to resist the wind
forces specified in AS 4055. Bracing shall be as evenly
distributed as practi cable and shall be provided in two
orthogonal directions.”
SG is of t he opinion industry best practice before, during
and after construction of the Applicant’s property is bottom
cord ties are to be installed so the entire roof truss system
is rigid and can resist racking by wind forces.
All truss manufacturers have required bottom cord ties
since light weight trusses were first manufactured.
The roof truss installation is defective building work.
FSP’s Engineer (KC)
Report
1 March 2013
The damage noted is consistent with a storm event.
Due to the way the roof frame was constructed, no
restraint was provided to the brick lintel at ceiling height
Case No: 348411 Determination Page 7 of 7
which allowed the lintel to deflect inwards under wind
pressures. The wall eventually collapsed during the storm
event in question.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.