Home / Financial Firm (Unknown - Insurer) / Determination 340487
Determination 340487
Denial of claim for internal and external wall and ceiling cracking after a storm
Summary
The applicants claimed about $50,400 for wall and ceiling cracking they attributed to a January 2011 storm, and the FSP denied it. AFCA accepted the FSP engineer's evidence that design and construction defects caused the damage, so the claim was denied.
Where a pre-existing defect is the dominant cause, a storm that only hastens the damage is not an insured event, and the exclusion prevails under the Wayne Tank rule where there are contributing causes.
Subjects and remedies
home or building damagenatural disasterno remedy
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
claim
Determination
Case No: 340487 Determination Page 1 of 5
Case number : 340487 1 5 July 2014
1 Overview
1.1 Dispute
The Applicants lodged a claim on 13 February 2011 with the Financial Services
Provider (FSP) under their home building insurance policy. The Applicants said
they had noticed significant internal and external cracks to the walls and ceilings
of their home after a storm on 10 January 2011.
The engineer, who assessed the house for the FSP concluded the damage
resulted from structural deficiencies and not from the storm, although he said the
storm would have exacerbated the situation. The FSP denied the Applicants’
claim.
The Applicants, who asked another engineer to assess the damage, say that the
FSP’s decision is incorrect. The Applicants contend the damage resulted from the
storm and are seeking $50,400, which includes engineering inspections and
reports, in addition to building and landscaping works.
1.2 Issues and key findings
What was the cause of the damage to the Applicants’ home?
The damage to the Applicants’ home was not due to a storm event because:
both engineers involved in assessing the home commented on the
inadequacies of design and poor building practices which were the reasons for
the cracking.
Was the cause of damage covered under the policy?
The FSP was entitled to deny the claim because:
the damage to the home was not the result of an insured event.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is entitled to deny the claim.
Case No: 340487 Determination Page 2 of 5
2 Reasons for Determination
2.1 What was the cause of the damage to the Applicants’ home ?
The damage to the home was due to design inadequacies and poor building
practices
The parties to the dispute obtained their own engineers’ reports as to the likely
cause of the damage to the Applicants’ home. The damage was in the form of
significant cracking to both external and internal walls of the home.
An engineer (SW) inspected the Applicants’ property for the FSP and provided a
report dated 10 May 2011, including photographs in support. The engineer noted
that restumping had occurred in late 2010, but that only the internal stumps had
been changed to steel supporting posts. No underpinning works were carried out
to the engaged brick piers at the perimeter of the dwelling. He concluded the
damage resulted from:
inadequate surface drainage
absence of waterproofing membrane between the soil and the masonry wall
inadequate ventilation for the sub-floor area
no stabilisation to the edge piers
inadequate design, poor building practices, incorrect strategies of
underpinning.
SW said the recent storm activ ity would only have exacerbated the “inevitable
problem of movement of the structure”. His conclusion was that the issue has
been developing since the completion of the dwelling (around 1972) and the event
was not “of a sudden, unexpected or catastrophic nature”.
The Applicants asked “LR”, an engineer, who had provided a pre -purchase report
for them in March 2010, to respond to SW’s report. His report dated 8 December
2011, concluded the damage occurred “as a result of a sequence of events”:
the original brick posts would almost certainly have subsided due to long term
drying out of soils beneath the building
the damage was not present in March 2010
the replacement of the brick stumps only served to make the occasional need
for re-levelling easier
this work “would reasonably have re - levelled the floor at that time”
large volumes of water due to extreme rains and overland flows/flooding
would have surcharged the available external drainage system
the most movement occurred above the timber floored section
the damage related to entry of water into the sub -floor space in January and
due to soil moisture related effects around the house’s exterior.
SW responded to LR’s report. SW’s response on 5 January 2012 , reiterated a
number of earlier conclusions and stated that the issue of water seepage had
been developing over years and was not the result of a single storm event. He
also stated the lack of adequate ventilation for the sub-floor area meant the
moisture was kept in the area for a prolonged period and therefore the drying out
process would have resulted in the damage to the vertical supporting piers.
Case No: 340487 Determination Page 3 of 5
LR provided another report (dated 13 July 2012) after excavations were
undertaken at the Applicants’ home. These excavations exposed part of t he
footing which supports the brickwork. LR made the following assessment:
the footing was poorly constructed and that section of the home is particularly
susceptible to soil moisture related ground movement
the damage is generally considered to be related to soil moisture related
movement effects
the soil previously against the outside brickwork has imposed lateral loading
effects to the brick wall
the footing is severely fractured in at least three locations
the damaged footings are beyond repair.
Having considered the various reports, I prefer those of SW as I regard the
conclusions contained therein to be thorough, logical, compelling and importantly,
supported by the photographic evidence.
The evidence before the Service indicates, on the balance of probabilities, the
damage to the home resulted from poor building practices and deficiencies in
design. The storm of 10 January 2011, would have exacerbated the inevitable
problem of movement of the home’s structure.
2.2 Was the cause of damage covered under the policy ?
The damage to the home was not due to an insured event
The onus is on the Applicants to establish a valid claim under the policy. This is
called a prima facie claim. This means the Applicants need to prove the cracking
to their home was the result of an insured event, namely, the storm event which
occurred on 10 January 2011.
Both engineers have identified the inadequacies in the home’s design and the
poor business practices used in the home’s construction. The part played by the
storm was that of hastening the inevitable as the cause was in existence long
before the storm’s occurrence.
Since the damage was not the result of an insured event, such as a storm, the
FSP is therefore entitled to deny the Applicants’ claim.
Even if it could be said that the storm played a contributing role, the rule in the
Wayne Tank legal decision provides that where there are two contributing causes
and one is excluded from coverage under the policy, the exclusion prevails and
the FSP is entitled to deny the claim.
Case No: 340487 Determination Page 4 of 5
3 Supporting information
There has been a full exchange of material between the parties and each party
has had the opportunity of addressing the issues contained within the material
exchanged.
In reaching this Determination, I have taken into account all of the material
exchanged and various submissions made by the parties.
Policy Provisions
What is not covered under any part of your policy
We do not cover loss or damage:
Erosion or subsidence
Caused by or as a result of erosion, vibration, subsidence, landslip, landslide, mudslide,
collapse, shrinkage or any other earth movement but we will cover
Subsidence damage to your home if it is caused by:
- insured event 2 (burst pipes, leaks and overflows)
- contents items insured by portable cover
- thes e insured events if the damage occurs within 72 hours of the event
happening:
insured event 1 (storm and flood)
insured event 8 (explosion)
insured event 11 (earthquake and tsunami)
Seepage of water through the earth
Caused by water seeping or running:
- through the earth (sometimes called hydrostatic water seepage)
- through or down the sides of earth or earth fill that is up against your home
- down the sides or underneath swimming pools or spas causing them to move,
change shape or lift or leaking through their hydrostatic valves
- against or through retaining walls and forcing them to move or crack.
Failing to establish an insured incident
Loss or damage without you being able to reasonably establish an insured incident took
place at a certain time and date.
Defect, structural fault or design fault
Caused by a defect, structural fault or design fault that you knew about (or should
reasonably have known about) and did not fix before the loss or damage occurred (eg. If
there are signs that a defect previously caused damage, we will not pay a later claim for
further damage from this defect).
Case No: 340487 Determination Page 5 of 5
Key Information
SW’s report dated 10 May 2011, along with accompanying photographs
LR’s report dated 8 December 2011 and accompanying photographs
SW’s report, with photographs, dated 5 January 2012
LR’s report dat ed 13 July 2012 and accompanying photographs.