Denial of water damage to investment apartment under gradual deterioration exclusion
Text of the determination
Determination
General Insurance - Domestic Insurance - Residential Strata Title - FSP Decision -
Denial of claim-Exclusion/ condition
Determination
Case No: 340453 Determination Page 1 of 7
Case Number: 340453 1 September 2014
1 Overview
1.1 Dispute
In May 2013, the Applicant lodged a claim under a residential strata title insurance
policy with the Financial Services Provider (FSP) which provided cover for his
investment apartment. The Applicant’s claim was for water damage to the timber
flooring and skirtings in his apartment, which he said was caused by heavy rainfall
in May 2012.
The FSP denied the Applicant’s claim on the basis that the damage occurred over
an extended period of time and was caused by factors which were excluded
under the policy, such as faulty materials or workmanship, gradual deterioration
and/or lack of maintenance.
1.2 Issues and key findings
Is the water damage covered under the policy?
The engineers’ reports obtained by both the Applicant and the FSP establish that,
on the balance of probabilities, the water damage to the Applicant’s apartment
was caused by a combination of gradual deterioration and lack of maintenance
and not by the storm events on 2 May 2012. Damage caused in this manner is not
covered under the policy.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is not liable for the Ap plicant’s claim.
Case No: 340453 Determination Page 2 of 7
2 Reasons for Determination
2.1 Is the water damage covered under the policy?
Application of policy depends on cause of damage
Section 1 of the strata title policy provides cover for accidental damage to the
Applicant’s investment apartment, subject to the conditions and exclusions set out
in the policy.
The cover provided under Section 1 is subject to specific exclusions for damage
arising directly or indirectly out of or in any way connected with:
faulty materials or faulty workmanship;
lack of maintenance or any other failure to keep the building in good repair; or
wear and tear, gradual deterioration, normal upkeep or making good.
The Applicant says that the damage to his apartment occurred as a result of
torrential rainfall on or around 2 May 2012, which, together with a blockage in the
building’s drainage system , caused water to overflow into the apartment,
damaging the timber floating floor and wall skirtings in several rooms.
However, the FSP says that the damage was not caused by a si ngle incident but
occurred over time due to a combination of the breakdown of the sealants in the
window/wall joint and poor maintenance of the balcony drainage systems.
Accordingly, it is necessary to determine the proximate cause of the water
damage to t he Applicant’s apartment (that is, the real, effective or predominant
cause). As the FSP is seeking to rely on a policy exclusion to deny the Applicant’s
claim, it bears the onus of establishing that, on the balance of probabilities, the
relevant exclusion applies.
Damage was caused by factors excluded under the policy
Although water entered the Applicant’s apartment during one or more rainfall
events, the available information establishes that, on the balance of probabilities,
the real or effective cause of the damage was gradual deterioration and a lack of
adequate maintenance.
The consulting engineer (O) appointed by the FSP to inspect the damage
concluded that it had been caused over an extended period of time by a
combination of:
the failure of the seals between the windows, walls and balcony paving due to
gradual deterioration and inadequate maintenance and repairs, which had
allowed water to enter through the joins in these areas; and
poor maintenance of the balcony drainage systems, which had allowed leaves
and other debris to build up, particularly around the air conditioner
condensers , thereby preventing effective drainage .
I consider that, as an engineer, O is suitably qualified to determine the cause of
the water entry to the Applicant’s apartment . O’s report is detailed and
comprehensive, and was prepared following a thorough inspection of the
Case No: 340453 Determination Page 3 of 7
property. O’s report separately c onsiders each of the areas in which water
damage was identified and provides a logical and reasonable explanation as to
how water entry occurred in each case. O’s explanation is consistent with the
nature and location of the damage as shown in the photographs provided.
The Applicant disputes O’s findings as to the cause of the damage. He says that
the damage occurred during the storms on 2 May 2012 when strong winds blew
leaves and other debris onto the roof of the building, where they blocked the box
gutter which, together with the torrential rain, caused the water table in the box
gutter to rise and overflow inside the apartment via the roof cavity between the
box gutter and the roof decking. The Applicant says that water then travelled
alongside the internal wall before coming to an end where the floor meets the
wall, resulting in damage to the floorboards and skirtings.
However, I do not consider that the information provided by the Applicant is
sufficient to refute O’s findings and establish that the damage was caused in the
manner he has described. In this regard, I note that:
O expressly dismissed the suggestion that the damage had been caused
solely by the storm events on 2 May 2012. While the Applicant says that O did
not give sufficient weight to the extent of rainfall which occurred, it is apparent
from O’s report that he accepted that the re had been considerable rainfall in
the local area on the relevant date;
the Applicant’s position that the damage was caused solely by the storms on
2 May 2012 is inconsistent with the fact that there was still significant moisture
in the skirtings in June 2013 (as shown by the moisture tests carried out by
the FSP’s builder (S )); and
while the Applicant has provided photographs of the box gutters showing a
build-up of leaves and debris, these photographs are undated and there is
nothing to indicate that this build-up occurred solely as a result of the storms
on 2 May 2012, rather than on an ongoing basis due to lack of maintenance
(as indicated by O).
The Applicant has provided a relatively brief report from his own engineer (P)
which states that the claimed damage was caused by the failure of the waterproof
membrane at the junction between the concrete slab in the common landscaped
area of the building and the precast wall and waste outlet. However, P’s
conclusion as to the cause of damage is not consistent with the explanation
provided by the Applicant. Further, even if P’s vi ews are accepted, the damage
would still be excluded from cover under the policy exclusions for gradual
deterioration and lack of maintenance (or, if the original installation of the
waterproof membrane was faulty, under the exclusion for faulty materials or
workmanship).
Accordingly, for the reasons outlined above, I am satisfied that, on the balance of
probabilities, the real, effective or predominant cause of the water damage to the
Applicant’s apartment was not the storm events of 2 May 2012, but the factors
referred to above which are excluded under the policy.
Case No: 340453 Determination Page 4 of 7
3 Supporting information
3.1 Terms of policy
Subject Terms
Cover provided
under Section 1
Subject to the terms, conditions, exclusions and limitations
applying to Section 1 (including those applying to all Sections of
the Policy), We agree to indemnify You in accordance with the
Basis of Settlement applicable to Section 1, up to the Limit of
Liability applicable to Section 1, agains t Damage to:
Any Building and
Common Area Contents ...
occurring during the Policy Period.
Definition of
Damage
Any accidental physical loss, destruction or damage to Insured
Property that has the result of lessening its value.
Section 1
exclusions
In addition to the general exclusions applying to all Sections of the
Policy, We will not pay for ...
4. Damage arising directly or indirectly out of or in any way
connected with …
faulty materials or faulty workmanship ...
lack of maintenance or any other failure ... to keep any
Insured Property in good repair
wear and te ar, corrosion ... gradual deterioration or
developing flaws ... normal upkeep or making good
3.2 Reports
Report Key points
Plumber appointed by
building manager (C)
Report – 26 June 2012
(as referred to in M’s
report (see below))
His inspection revealed that the seal between the balcony and
the building had perished and needed replacing.
He cleaned, dried, taped and re - sealed the area.
He also drained the box gutter and removed a bucket load of
polystyrene and plastic from a blocked downpipe.
FSP’s managemen t
services company (M)
(incorporating
assessment by builder
(S))
Report – 13 June 2013
S has confirmed that, in the areas where water had entered
the apartment, the floor of the apartment was higher than the
balcony floor. According ly, it is unlikely that water has entered
through these areas.
Further, S has confirmed that moisture readings of the
affected skirting boards (for example, in the living room) show
that they a re still saturated. As the area between the balcony
and the building was re - sealed by C in June 2012, this cannot
be the cause of the water entry .
S considered it more likely that rainwater had entered the
apartment through the un sealed vertical join s where the
Case No: 340453 Determination Page 5 of 7
Report Key points
window frame meets the pre - cast concrete panels of the wall ,
rather than through the seals between the balcony floor and
the building (as indicated by the plumber (C)) .
FSP’s engineer (O)
Report – 12 July 2013
The building is approximately 11 years old.
The damage to the lounge room starts adjacent to the down
pipe / floor waste unit on the balcony next to the window and
runs for 5 metres along the west wall. The damage in the
master bedroom appears to have been caused by moisture
travelling across/under the wall plate from the lounge room
side.
The damage in these areas was most lik ely caused by water
entering through the building facade via the junctions of the
window frame and the facade and terrace. This area of the
facade is the most exposed to prevailing winds and rain. The
fact that the water damage starts next to the windows,
together with evidence of recent resealing in this area,
suggests a causal connection.
The moisture readings carried out by M indicate that the
problem in this area has not been corrected by the repairs
carried out by P in June 2012. While the vertical joi nt between
the window jamb and the pre cast wall was resealed, this is
probably faulty and will need stripping out and resealing. The
caulking under the window sill should also be replaced.
There is water damage in bedroom 2 in and around the corner
window , which faces onto the north - east terrace where the
balustrade at this end of the terrace is set back from the wall.
The gap is also at a low point in the terrace and surface water
tends to migrate across to this opening and drop over the side
at the end o f the terrace. There is a build - up of dirt and moss
growth along the length of the window sill, which has created
an effective pathway for moisture to migrate from the terrace
under the window sill and into the apartment.
There is an air conditioner conden ser at the other end of the
window in bedroom 2, which has an extensive build up of
debris and a significant amount of water around it. There is no
evidence of a dedicated condensate drain point / floor waste.
The location of the damage points to the conde nser as the
likely cause.
His experience of similar buildings suggests that poorly
maintained terraces and water points contribute to the
downgrading of the drainage systems, allowing water to enter
apartments. In this case, the build up of organic matter and
misdirected water back to the sill line has in all probability
provided a pathway for water into the bedroom. The absence
of any obvious sealant to the vertical joints at the window
jambs may also have contributed to the problem, although to
a limited extent.
There was water damage to the north and east walls of the
upper level TV room extending approximately 3 metres along
Case No: 340453 Determination Page 6 of 7
Report Key points
each wall. The building manager had advised that this area
had been repaired after having previously suffered water
damage.
The dam age to the TV room appears to have been caused by
the location of the air conditioner condenser, the lack of an
effective drainage point and the failure of the sealant between
the wall and the terrace paving, which has contributed to
water getting under th e wall, across the slab and through to
the TV room. There was also a cracked and leaking downpipe
which is likely to have contributed to the water leak into the
north wall.
The water damage to the apartment was not caused by any
one rain event but was the result of many rain events over a
period of time. It was not surprising that damage appeared in
2012, as by that time the original caulking/sealant compounds
used in the construction of the building were over ten years
old. Assuming they were the more com monly used water
soluble type, they would by that time be reaching their normal
life expectancy. For this reason, the facades of high rise
buildings should have their sealants replaced as part of long
term maintenance.
In summary, the main cause of the wat er entry is due to a
combination of a breakdown of the sealants and poor
maintenance of the terrace drainage systems, particularly
around the air conditioner condensers. A lack of maintenance
to the down pipe on the north wall had also contributed to the
w ater problems in that area.
Applicant’s engineer
(P)
Report – 26 February
2014
The water damage is confined to the southern side of the
apartment between the bedroom and living area, adjacent to a
down pipe and floor waste on the upper balcony next to the
windows.
The water damage has affected the plasterboard, skirting and
floating floor. There is also evidence that water in penetrating
through the cracks in the upper balcony slab as seen by the
build - up of efflorescence on the soffit of the balcony slab. It is
also evident that some attempts have been made to reseal
some of the external joints between the paver and the wall
and the window sills to the balcony slabs. However, this would
be only a short term solution.
For the type of construction (with exte rnal floor areas), the
slabs need to have a waterproof membrane applied to the
external surface to prevent entry of storm water and overflow
from sprinklers in the garden beds.
It is likely that the entry of water into the Applicant’s apartment
is as a res ult of the failure of the waterproof membrane at the
junction of the common area slab to the precast wall and the
outlet waste.
Case No: 340453 Determination Page 7 of 7