Home / Financial Firm (Unknown - Insurer) / Determination 338795
Determination 338795
Denial of water damage claim - no insured event and policy exclusion
Summary
The applicant claimed for flooring damage from pool pump discharge and a leaking kitchen pipe, which the FSP denied. AFCA found an insured event and ordered the FSP to cash settle 50% of the repair cost after a new scope of works.
The loss was an insured event, but the faulty design of the home extension contributed to the damage, so the FSP may limit its liability to 50% of the loss.
Issues
- Claim denial primary · not upheld“I am satisfied that the Applicant has established that there was an insured event under the terms of the policy.”
- Inadequate claim investigation secondary · upheld“The FSP chose not to investigate this part of the claim and challenged the Applicant to lodge a separate claim.”
Subjects and remedies
home or building damagepay claim
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
Claim - Water Damage - No Insured Event/Policy Exclusions
Determination
Case No: 338795 Determination Page 1 of 7
Case number : 338795 1 6 June 2014
1 Overview
1.1 Dispute
The Applicant made a claim on his home building insurance policy for damage to
the flooring in his home incurred on or about 5 December 2012. He attributes the
damage to the removal of and failure to properly replace a filter from his pool
pump, which he believes caused up to 10,000 litres of water to flow under the
property and cause damage which affected the flooring in the home. His expert
later identified a leaking pipe under the home as well.
The Financial Services Provider (FSP) investigated and denied the claim on the
basis that it was not satisfied that there was a flow of pool water under the home
sufficient to cause damage and/or construction and other issues were the cause
of the sub-floor moisture problems that may have led to the flooring damage.
1.2 Issues and key findings
Was the loss caused by an insured event?
The loss was caused by the build up of moisture under the home, which was at
least in part attributable to the leaking pipe under the kitchen and possibly the
water from the pool pump. These events, individually and collectively, serve to be
an insured event on the basis that I accept that this water was the likely source of
the moisture that was the cause of the damage to the flooring.
Was the loss excluded under the terms of the policy?
The most applicable exclusion is for the apparent faulty design of the home and I
am satisfied that this contributed to but was not the sole reason for the damage
caused. In accordance with what is fair, I am of the view that the FSP is entitled to
reduce its liability for the claim to pay only 50% of the Applicant’s damag e.
1.3 Determination
This Determination is partially in favour of the Applicant.
The FSP must contribute 50% to the cost of the damage to the flooring in the
home, which may be paid by way of a cash settlement after a new scope of works
is completed by a repairer chosen by the FSP.
Case No: 338795 Determination Page 2 of 7
2 Reasons for Determination
2.1 Was the loss caused by an insured event?
There is limited evidence to suggest that the loss was caused by the pool
discharges
Whilst the Applicant considers that up to about 10,000 litres of water affected his
home, his expert (“WC”) claims that it was affected by up to 20,000 or 30,000
litres of water through the sub floor vent adjacent to the pool solar pump.
The available photographs of this area suggest that it was dry at the time of
inspection and th e FSP’s expert, “JM” confirms that there was no noticeable
moisture related damage in the sub-floor of this area, situated underneath the
study. The Applicant claims that the floor in the study was one of the first areas
affected.
Certainly there is evidence that water leaked from the pool pump and that this
allowed a discharge of water to somewhere on the property. The exact amount of
leakage is not able to be accurately estimated and the extent of any damage
directly attributable to it is difficult to determine.
The FSP’s policy provides cover for damage caused by an escape of water from a
swimming pool. The difficult part is assessing the extent to which water from this
pool affected the home.
Damage is certainly present to the floors in the home and this is accepted by the
parties. There is insufficient direct evidence to link this damage to any discharges
from the pool.
Key to my consideration of the matter is the apparent lack of moisture related
damage underneath the property adjacent to the pool pump. If this was the
access point for water to get under the property, it would appear likely that the
closest area of the home to the pump (being the study) would show strong signs
of water damage. This does not appear to be the case.
It is conceivable that the area has since dried out, or that the flow of water into
this area was more moderate than was thought by the Applicant and his expert.
There is arguably a link that can be drawn between the damage to the flooring
and the discharges from the pool pump but I am not convinced that water from the
pool was the proximate cause of the damage to the flooring.
It is not disputed that there was a leakage from a kitchen pipe
WC identified a second possible source of water leakage under the home, being
from a split pipe under the kitchen. This had apparently been discharging water
for some time but has since been repaired.
The FSP chose not to investigate this part of the claim and challenged the
Applicant to lodge a separate claim for this loss. This should not be necessary,
noting that the chief reason for the claim was the damage caused to the floors of
Case No: 338795 Determination Page 3 of 7
the home and not simply the discharge of water underneath the home (which was
noted as the likely cause).
The leak from the kitchen pipe is not denied by the FSP and noting that it is an
undisputed part of the claim, I accept that this would be an insured event if it can
be established that it caused damage.
There is no apparent disagreement that the excessive moisture in the subfloor of
the property is the reason for the flooring problems in the home. To this end, the
leaking pipe presents as a very likely source of this moisture (quite possibly
occurring in conjunction with the discharges from the pool pump) and that the
build up of this moisture served to cause problems with the flooring in the home.
Whilst the FSP attributes the moisture under the home purely to the alleged
inadequacies of the construction of the extension, I am not satisfied that this
should be preferred to the evidence submitted that water was discharged directly
into this area. This can even cause damage to an immaculately constructed
home.
On this basis, I am satisfied that the Applicant has established that there was an
insured event under the terms of the policy.
2.2 Was the loss excluded under the terms of the policy?
Loss contributed to by the poor construction of the extension
It is not in dispute that there is evidence of moisture difficulties under the home,
although it is open to question as to how much of this moisture was directly
caused by the discharges from the pool and/or the leaking pipe and whether such
discharges would have had any effect at all if the home had been adequately
ventilated.
In this instance, it would appear that the construction of the extension of the home
was not of a standard which was optimal for protecting against the build up of
sub-floor moisture problems.
Whilst conceding that discharges from the pool pump area may have had an
impact, noting the dryness of the adjacent sub-floor area when investigated, I am
of the view that any impact from these discharges was likely minimal.
With the sub-floor area being not adequately ventilated and therefore not suited to
properly handle water problems under the home, there is a question of whether
this apparent structural defect may have been responsible for the failure of the
water to disperse naturally. This problem is also complicated by the nearby
stormwater pits not being adequately clear to allow for the effective drainage of
excessive water.
Notwithstanding these issues, the two identified causes of water discharge under
the property were not normal and there is a consideration as to whether an
adequately ventilated sub-floor area would have been capable of properly
handling such a problem.
Case No: 338795 Determination Page 4 of 7
Put another way, if the sub-floor had been adequately ventilated would the
damage still have occurred?
The fact that WC has attended to additional work since the report of the claim,
including introducing and expanding on the ventilation options under the floors, is
suggestive that the original work to extend the home was not of a sufficient
standard.
In all likelihood, a combination of the water from the pool, the leaking pipe and
possibly the inadequate ventilation conditions underneath have contributed to the
damage sustained to the Applicant’s floors.
The policy has exclusions in place that serve to allow the FSP to avoid payment
of the claim in certain circumstances.
I accept that the home extension was not designed as well as it could or should
have been. This is the cornerstone of the FSP’s denial of the claim.
JM’s view as to this is centred on the belief that there was no event to account for
an excessive amount of water to flow under the home. JM certainly raised doubt
as to whether any water penetrated the sub-floor from the pool, although on
balance I accept that at least some water has likely got through.
The greater issue is the matter of the pipe leakage.
JM’s analysis of the situation did not factor in discharges from the fractured pipe,
other than to suggest that it was a builder-related issue. This may or may not be
so but it does not exclude the Applicant from consideration under the policy. It
also limits the value of JM’s reports as they clearly have not taken into account all
possible causes of the water inundation.
This is not to say that the design problems of the home have not played a role in
contributing to the damage. I am of the view that they did, although the extent of
this needs to be considered.
There is no accurate way to measure the extent of the contribution of the likely
faulty design of the building. I do not accept that it was total (as proposed by JM)
and therefore I am of the view that some deduction should be made from the
overall level of cover.
In accordance with what is fair in all the circumstances, I determine that the FSP
is entitled to limit its settlement of the claim to 50% of the loss.
Wayne Tank considerations
The FSP relies on the Wayne Tank Principle as an alternate argument to avoid
the claim.
If it is accepted that the leakages under the home worked in conjunction with the
structural shortfalls of the property to cause the resultant damage and that neither
cause was a dominant cause of the subsequent loss, then the FSP is entitled to
deny the Applicant’s claim by relying on the exclusio n for faulty design of the
home.
Case No: 338795 Determination Page 5 of 7
I am not satisfied that evidence establishes that the two issues worked
concurrently and cooperatively (within the meaning established under the Wayne
Tank principle) to cause the loss. It is entirely conceivable that had the home
been adequately ventilated that it might have still sustained damage due to the
discharge of water from the pipe under the home (if not the water from the pool).
There are not sufficient grounds to argue that the exclusion works to defeat the
claim as I am satisfied that the proximate cause of the damage was likely the
discharge from the water leak under the kitchen.
Settlement of the claim
The FSP should arrange for an expert of its choosing to survey the resultant
damage that has occurred to the home and to estimate a repair amount for this
damage. The FSP will then be entitled to cash settle the Applicant for 50% of this
repair estimate.
3 Supporting information
3.1 FOS approach to this dispute
A full exchange of the relevant information has taken place between the
respective parties and each party has had the opportunity of addressing any
issues raised.
All of the provided material has been read and considered. The parties have
raised numerous issues in their submissions to the Service. For the purpose of
this Recommendation, commentary is restricted to only those issues considered
relevant to the outcome.
There is an onus on an insured to establish on the balance of probabilities that a
claim fits the definition of an insured event. This is known as a prima facie claim.
Should this onus be discharged, it is then the responsibility of the insurer to
establish the application of any exclusion on which it relies to deny the claim.
To be entitled to cover from the FSP, the onus therefore rests with the Applicant
to establish that his loss fits within the scope of what is covered by the FSP’s
policy.
The policy provides cover for a series of defined events as outlined in the PDS. It
does not provide blanket cover for all types of loss.
It was established by the court in Wayne Tank & Pump Co Ltd v Employers
Liability Assurance Corp Ltd [1974] QB 57 (the “Wayne Tank principle”) that
where two concurrent causes can be attributed to an insured loss, one of which is
covered by the policy and one of which is not, the excluded event takes
precedence in the consideration of the claim.
Case No: 338795 Determination Page 6 of 7
3.2 Expert reports
Record Key points
FSP’s expert ( “UB” )
Assessor re port
15 March 2013
Damage caused to flooring throughout the home due to
water sitting beneath the flooring. This has caused the
flooring to swell, move and lift in areas of the house
The flooring in the insured home requires replacement
The stated cause of the loss occurred more than three
months prior to the inspection
It was recommended that an engineer attend to inspect the
footings/foundations of the property
The estimated cost of repairs (excluding any issues with
the foundations) was $28,555.12
FSP ’s expert ( JM )
Engineer’s report
19 May 2013
Noted as interim report only as subfloor had not been
inspected
Home about 60 years old, with an extension completed at
the rear in 2011. Floor levels at the rear of the home are
lower than the external ground levels in the rear yard
Extension of home not compliant with Building Code of
Australia (BCA) – surface drainage i n particular is not
graded away from the building
Subfloor ventilation is also not sufficient and non compliant
with the BCA. Floor level of the rear extension should have
been raised by about 300mm
Pool pump water overflow not “considered to have
contribu ted significantly (if at all) to the alleged floor
damage to the rear extension”
Subfloor could not be inspected as no access to this area
was made possible by the builder.
FSP ’s expert ( JM )
Engineer’s report
18 June 2013
Subfloor ventilation at the rear of the home is inadequate
and the builder has tried to improve this retrospectively. It
is adequate in the front areas of the home
Pool filter overflow located nearest to the study and this is
where the worst of the damage should be. This is not the
case, with the floor of the study “not excessively damp”
compared to other area. This implies that the moisture
damage might be attributable to other factors
The excessive dampness present under the home is due
to poor drainage at the rear of the home
Evidence of mould and possible rot also present in areas
away from the study
Significant rectification work is needed to address the
building issues.
Applicant’s expert (WC)
Builder’s report
28 July 2013
Under the home it is not ventilated properly and that
includ es the older front section. The building has a “severe
mould and a moisture problem”
The pool solar pump sent about 20,000 - 30,000 litres of
water out of the pool after the filter basket had not been
Case No: 338795 Determination Page 7 of 7
fitted properly and this went through the adjacent sub fl oor
vent
A stormwater pit was located within about 1.5m from the
pump, although dirt and leaves covering this area
prevented any escaping water from draining into this area
There was a split water pipe discovered under the kitchen
which appears to have bee n leaking over a prolonged
period, causing “increased levels of moisture” under the
extended part of the home
The area under the extension is dryer and has less mould
than most of the home, suggesting that “the damage is
caused by either the pool [releases ] or the broken water
pipe”.
FSP ’s expert ( JM )
Engineer’s report
11 August 2013
He disputes that the drainage at the property is adequate
The evidence that the drainage at the front of the home is
adequate is deduced from the lack of apparent
deterioration to this area
There damage under the property is not consistent with an
alleged discharge of 20,000 - 30,000 litres water under the
property
If the plumber retained for the extension failed to connect
the pipes properly, this is an issue for the contractor as the
work would still be subject to the builder’s warranty
The failure of the builder to comply with the BCA for the
sub - floor ventilation has been the dominant cause of the
problems at the home.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.