Text of the determination
Case No: 330864 Determination Page 1 of 14
Case number: 330864
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of claim – Section 46 Insurance Contracts Act 1984
18 February 2014
Summary
Description:
This dispute concerns a claim by the Applicants for storm damage
under a home buildings and contents insurance policy.
Basis for Determination:
The Applicants have not established on the balance of probabilities that
the damage was caused by a storm as defined but rather the evidence
is that the damage was caused by events which are excluded for cover
under the policy.
Determination:
The FSP is entitled to deny the claim.
Background
1. The Applicants held a Home Building and Contents Insurance Policy (the
policy) with the Financial Services Provider (FSP).
2. A claim was lodged under the policy on 28 January 2011 arising from the
partial collapse of the external skin of the western brick wall of the insured
building.
3. The FSP declined the claim on the basis the damage was not the result of
an insured event rather it was due to a contribution of several factors which
were excluded from cover.
4. The Applicants remain dissatisfied with the FSP‟s decision to decline the
claim and maintain that the proximate cause for the loss were storm
conditions in January 2011. They are seeking, at least, a contribution of
$35,000 - $40,000 towards the total cost of repairs for the damage noted as
$78,000.
Determination
Case No: 330864 Determination Page 2 of 14
Summary of Applicants ’ position
5. The Applicants do not accept the FSP‟s decis ion to decline their claim on the
basis of “soil movement and wear and tear”. They are of the view that the
proximate cause for the partial collapse of the wall (the damage) was the
weather conditions over the 7, 8 and 14 and 15 January 2011.
6. Particularly the rainfall between 14 and 15 January 2011 was 52.6mm which
was greater than the average total January rainfall of 47.7mm. Wind gusts
reached a speed of 72km/h which is three times greater than the average. F
does not address the coincidence of the storm.
7. On 28 January 2011, part of the outer skin of the western boundary brick
wall of their home collapsed. The Applicants advise that in hindsight, they
heard sounds of masonry giving away from 19 January 2011 when they
returned from interstate.
8. The loss was sudden and unexpected. Their home was well maintained. The
partial collapse was due to the storm event, a fact the FSP‟s original
assessment as well as an appeal of the assessment failed to consider.
9. The concerns the Applicants have with the FSP‟s appointed engineer “F”„s
report are:
The Applicants did not report, as alleged, that there had been seasonal
ongoing movements over the previous years. Rather, they advised F
that house movements had been minimal which was evident from the
lack of cracking in the plasterwork.
Further the movement was not in the immediate vicinity of the wall. And
the movement observed by F occurred at the time of the collapse of the
wall not before.
The house was not re-blocked and re-levelled as alleged although the
Applicants did seek advice. When renovations were completed to the
home in 2007, the stumps were found to be in good condition and only
two stumps were replaced with minimum re-levelling.
The fall of the NE corner of the house in the direction of the neighbour‟s
large tree is not relevant as this is in the opposite direction to the fall of
the wall.
The action of trees is not relevant as they are located on the opposite
side of the house and trees near the drain are offset by the water in the
drain.
F did not take into account the storm forces and storm water runoff and
the proximity of the storm water drain. The wall runs along a Council
storm drain.
F has referred to irrelevant building codes that were not in place at the
time the wall was constructed.
F did not recommend a complete rebuild.
Case No: 330864 Determination Page 3 of 14
None of the consultants, including F, commissioned by the parties
checked the footings and foundations of the wall and assumed that
rotation or other movement of the footings had occurred in the past.
Any cracking from this assumed moment had been fixed.
No one saw cracking.
10. The Applicants maintain when the wall was rebuilt in 2012 (after lodgement
of the claim) the builders who undertook the works did not observe any
foundation rotation, cracking, soil movement, rotation or subsidence.
11. The Applicants acknowledge that the wall ties may have been subject to
some corrosion, however, they dispute that this can be accepted as the
proximate cause of the claimed damage.
12. Further, they refute the FSP‟s position that there was a failure to m aintain on
their part. They could not reasonably have been aware of the corroding wall
ties until such stage that the wall failed as these are installed within the wall.
13. The evidence provided by the consultant engineers “D” who were appointed
by the Applicants supports their position that the action of strong winds
during mid January 2011 caused the ultimate collapse of the wall.
14. The Geotechnical expert “H” found that the channelling of stormwater in the
adjacent drain had impacted on the foundations of the wall.
15. “R” (also commissioned by the Applicants) formed the opinion that the
foundations had rotated and this had occurred well before the Applicants
purchased the property.
16. The Applicants are seeking indemnity for the damage done. They contend
the FSP should be obliged to cover the cost of the remedial action
recommended by its consultant F. This would involve reconstructing the
external skin of the wall. Their engineers recommended a complete rebuild
rather repair of the wall.
17. The Applicants say they have had the works done at a cost (not including
cost of footings and renovations of internal fittings) of $78,000 (inclusive of
GST). They consider a settlement in the amount $35,000 - $40,000 is a
reasonable contribution by the FSP to their financial loss.
Summary of FSP’s position
18. The policy in question is a „Defined Events‟ policy of insurance that provides
indemnity for the listed insured events and does not cover all types of risks.
19. It is an accepted principle of insurance law that the onus rests with the
insured to establish, on the balance of probabilities, that the loss claimed
falls within the cover available under the policy.
Case No: 330864 Determination Page 4 of 14
20. The policy provides cover for loss or damage resulting from storm and
rainwater. None of the reports says that the damage was a direct result of
the January storms.
21. The FSP maintains that the report submitted by consultant F provides that
the damage claimed is the result of a number of contributing factors with
evidence of long term foundation movement.
22. The reports of the experts mention a number of causes including:
the footings were of insufficient depth;
the footings moved causing the walls to lean;
the wall ties were inadequate;
the foundations moved over time due to the highly reactive soils;
The soil has reacted due to it being exposed to the water in the drain
and then the drought like conditions and the tree roots of the nearby
palms.
23. F further provides that the damage claimed is not due to heavy rainfall/storm
as claimed by the Applicants. The Applicants‟ own preferre d consultants D
confirmed the soil had dried out and the lean of the wall had developed over
time. Also, adjacent palm tree(s) contributed to the drying of the soil.
24. R confirmed that foundation rotation had occurred 8-10 years prior to the
loss and which had contributed to the lean in the wall and subsequent failure
of wall ties.
25. The FSP maintains that on the basis of all the available evidence the
proximate cause of the damage was the rotation of the foundation soils. The
policy clearly excludes loss or damage arising from soil movement.
26. The FSP contends there was no insured event giving rise to the damage
claimed. It is also clear that the policy does not cover loss or damage arising
from wear and tear, rust, corrosion, structural defect or breakdown.
27. Accordingly, the Applicants have not fulfilled the onus they have to establish
the damage is covered under the policy and the FSP was entitled to decline
indemnity to the Applicants.
28. The FSP relies on the following policy provisions:
“ This Product Disclosure Statement provides information about the product
we offer: the [FSP name] Home Building Insurance Policy. When we agree to
insure your building, your policy comprises this booklet and your policy
schedule which shows the detail of the policy particular to you. See page 40.
This policy does not cover some events, circumstances and situations
As you read through this policy, you will see there are some events,
circumstances and situations it does not cover. To make sure you are aware
Case No: 330864 Determination Page 5 of 14
of these exclusions, please read the whole policy carefully including the
section „What we do not cover - general exclusions‟ beginning on page 14.
…
What we do not cover – general exclusions page 14
You are not covered under any section of the policy for damage, loss, cost or
liability caused by or arising from or involving:
…..
wear and tear, rust, deterioration or corrosion,
mechanical, structural, electrical, electronic or other failure or breakdown,
other than as provided for under „Damage to electric motors‟ on page 22,
…..
soil movement or settlement,
…..”
Issues
29. Whether the Applicants have established the loss/damage claimed was due
to an event insured under the policy.
30. Whether the FSP was entitled to decline indemnity to the Applicants in line
with the policy.
Reasons for decision
31. As advised to the parties, due to the nature of the dispute, the Financial
Ombudsman Service (FOS) has considered it appropriate to expedite the
dispute to Determination in accordance with the Operational Guidelines to
the FOS Terms of Reference
32. I am satisfied that a full exchange of information has taken place between
each party and that each party has had the opportunity to address any
issues raised.
33. I have reviewed the submissions of the parties in relation to the terms and
conditions of the policy and will only refer to the relevant submissions and
materials raised.
34. I am satisfied it is not in dispute that:
The Applicants held a current home building insurance policy with the
FSP at the time of the loss.
The FSP provided and the Applicants received the relevant policy
documentation including the Product Disclosure Statement (PDS) prior
to the loss.
The external skin of the insured building‟s western brick wall partially
collapsed on 28 January 2011.
Case No: 330864 Determination Page 6 of 14
There occurred rain and winds in the month of January 2011 in the
days leading up to the loss.
Each party have sought the services of and rely upon the evidence of
their preferred consultants.
The policy is a defined events contract of insurance which provides
indemnity for loss or damage arising from specified insured events
subject to the noted policy limitations/exclusions.
The Applicants have proceeded to authorise reconstruction of the
collapsed wall at a cost exceeding $78,000 (inc. GST).
35. I am satisfied that each party has had full access to the material on which
the other party bases its case, and also has had an opportunity to reply to
matters raised by each other. In the circumstances, it is unnecessary to
restate the material in any detail unless required. The available consultants‟
reports state in part:
C’s Report dated 7 February 2011
C undertook an assessment of the insured building but wanted an
engineer to look at the wall for safety reasons.
C concluded that water damage had occurred to the wall and
foundations due to the effects of footing rotation due to climatic change
and heavy rains and a high volume of water in the storm water drain
next to the wall.
He said the minor and older settlement in the building is not a cause.
He said the footings had recently rotated under soil pressure from the
drain side. This was due to a combination of previously dry subsoils
now expanded because of the now high storm water runoff.
F’s (Engineer) Report dated 23 Febru ary 2011
F undertook an assessment of the insured building on 10 February
2011. He also photographed the property and the damage.
The assessment was a visual inspection and a level survey of the floor.
The dwelling is a single storey residence estimated to be at least 90
years old. There appeared to be no underground stormwater and/or
sewerage drains at the property.
There is a large (approx. 10m high) tree located in the neighbouring
property to the north east of the insured building.
The clay soils at this site are expected to be highly reactive (Class H).
He made some observations about the property including that the
cavity wall ties were completely corroded and he noted some cracking
in the family room and a 2mm gap in the hallway.
Case No: 330864 Determination Page 7 of 14
The owners advised they had been residing at the insured property
since 2003. Further, there had been seasonal ongoing movement
resulting in distress to the building over the past years.
Renovation works had been undertaken at the insured property in 2006
as well as the home was re-blocked and re-levelled.
A levels survey noted a uniform fall to the NE corner to the large tree.
Having completed the assessment F formed the opinion that the
collapse of the external skin of the western brick wall was caused by a
number of contributing factors, these being:
Inadequate lateral resistance due to the corroded/failed brick
wall ties.
Inadequate spacing between brick ties with current codes
requiring 600mm x 600mm spacing.
Very poor quality mortar and external cover providing
inadequate durability protection to wall ties.
Long term foundation movement due to inadequate footing
depth for the type of soil, soil drying from nearby trees and the
changes in the soil due to the drought.
In F‟s opinion the wall collapsed because of the failure of the wall ties
combined with the outward rotation of the wall both of which have
occurred over a long time.
The heavy rain events in January 2011 did not cause, or contribute to,
the resultant damage as the soil would have been expected to swell not
shrink with rain resulting in local heave. The levels contours did not
indicate local heaving in the surrounding affected areas.
F recommended the entire external skin of the damaged wall be
demolished in order for it to be reinstated with appropriate wall ties.
D’s (Engineer) Report dated 30 April 2011
An inspection was undertaken on 25 March 2011.
Mortar in the wall was found to be weak with it probably being lime
mortar.
Some galvanised wall ties had completely corroded through at the inner
face of the outer skin of brickwork, while others had pulled out of the
outer skin.
A section of the wall tilted to the west by 50mm over a 1.8m length.
He noted the adjacent drain and the large palm tree growing in the
neighbour‟s property relatively close to the failed w all.
Soil tests completed at the time the extensions were undertaken at the
insured property classified the silty clay as highly reactive with rock
being encountered at 750-800mm below ground level.
Case No: 330864 Determination Page 8 of 14
The entire gravity of the outer skin brickwork would be offset from
47.2mm from its centre.
On 7, 8 and 14 January 2011 maximum wind gust speeds of 74, 63 and
72km/hr from the north were recorded. These winds would have
created suction forces on the wall and may have caused the outer skin
of the wall to lean more than previously, leaving it in a condition
susceptible to collapse.
As some of the wall ties were corroded and there was weak mortar, this
allowed other ties to pull out of the wall and the outer skin was not
adequately restrained.
Presumably, on the day of collapse, the wind suction forces were
enough to cause the collapse of the outer skin.
Some of the lean of the wall would have developed over time. It was
noted that the inner skin of the west wall had been clad with
plasterboard prior to the Applicant s‟ purchase and would be to conceal
cracks and make the lean less obvious.
The tilting of the wall was caused by its footing rotating outwards. This
has been caused by the drying out of the highly reactive clay soil under
the footing resulting in soil shrinkage. As well as, roots from adjacent
palm trees contributing to the dry soil causing settlement and rotation of
the footing.
After a check of the soil conditions by H, D recommended the entire
west wall be rebuilt with the footings down to solid rock. He also said
the Council should regrade the drain and the neighbour should remove
the large palm trees.
D concluded that prior to the winds on 7, 8 and 14 January 2011, the
outer skin of the west wall was getting close to failure because of its
lean, weak mortar and corroded wall tiles. The wind exerted a suction
force on the wall increasing the lean and putting it in an unstable state
so very little force caused it to fail.
H’s (Geotechnical) Site Inspection Report dated 16 May 2011
H inspected the insured property on 10 May 2011.
The investigation included drilling three boreholes conducted with hand
augers and the exposure of existing footings in two locations.
H noted the bluestone paved spoon drain located directly adjacent to
the brick boundary wall footings and the site has poor surface drainage.
The site is classified as CLASS P due to abnormal moisture conditions
intersected on site. The clay soils are highly reactive (CLASS H2) and
basalt rock is non-reactive (CLASS A).
Based on the subsurface profile intersected, and nature of the cracking
observed, H considered that foundation movement of the residence
was primarily due to a combination of:
Case No: 330864 Determination Page 9 of 14
1) Volumetric change in the highly reactive foundation zone soils
due to water pooling within the drain and moisture being
delivered directly to the foundation zone soils causing foundation
soils to shrink and sell.
2) The footings being of inadequate construction and insufficient
depth for the structure to accommodate the reactivity of the site
(the current code specifies deeper foundations for the type of
structure at the site with reinforced concrete footings).
H recommended that the existing wall be removed and replaced with a
new wall.
R’s (Civil Engineer) Report dated 9 June 2011
An inspection was completed at the insured property on 7 June 2011 to
overview the technical opinions by others and, if possible, to determine
the most likely sequence and therefore cause and effect for the failure
of the wall.
Reading the reports indicated a reasonably consistent approach to the
likely cause and effect situations, which to varied degrees R agreed
and/or disagreed with their interpretation. R then proceeded to provide
his own overview as to the cause and effect.
The wall ties between the skins of brick work had rusted out to an
extent they were not restraining the outer skin.
R attributed the collapse to the rotation of the foundation, thereafter the
outward lean of the wall and thereafter the failure of the wall ties, this
sequence being most important.
In R‟s opinion what occurred is that the wall is eccentrically loading the
footing that some stresses built up on the outside of the footing and, as
a consequence, it had settled. This being in addition to the fact that it
gets wetted up and softened by the drain and localised drying out by
trees on a long term basis.
This, in the longer term (and well before the Applicants‟ purchased the
property) has resulted in rotation of the foundations.
Based on the evidence R formed the opinion that the wall had a lean
from the time the Applicants purchased the property. Arising from the
fact the foundations had moved (prior to the purchase) almost to the
same extent as they were now the causation would not have been
obvious or in the knowledge of the Applicants.
R provides that to the best of his knowledge there is no maintenance
program relating to the fixing/maintenance of wall ties within a wall. He
notes qualified people were engaged by the Applicants to complete the
renovation and no concerns with respect to the wall were raised at that
time.
Case No: 330864 Determination Page 10 of 14
The rotation occurred well before the wall ties failed and therefore the
actual initiator of the collapse was the failure of wall ties which failure
could not have reasonably been detected.
BOM weather observations for January 2011
On many days there is no rain at all but the overview says it was the
wettest January on record for Victoria. The following entries are noted:
“ Australian Government Bureau of Meteorol ogy
Mel bourne Victoria
January 2011 Daily Weather Observations
Max wind gust
Date Rain
mm
Dirn Spd
Km/ h
7 0 N 74
8 0 N 63
12 15.4
14 28.2 N 72
15 22.4
DOL
28
0 SSW 35”
Analysis
36. The Applicants are seeking a benefit under the policy and therefore have the
burden of establishing, on the balance of probabilities, that the cause for the
damage claimed falls within the cover provided by the policy, that is, was
due to an event insured under the policy. If the Applicants are successful in
establishing this, the onus shifts to the FSP to establish, on the balance of
probabilities, an entitlement to decline/limit liability to the Applicants under
the policy.
37. Accordingly in this matter the Applicants must prove the damage was
caused by a storm. In this policy storm is defined to mean a violent wind...or
a heavy fall of rain.
38. I have carefully considered the evidence made available by the parties as
well as the numerous consultants‟ reports commissioned and relied upon by
the parties to this dispute. Having considered the reports I am satisfied that:
Each of the appointed consultants is adequately qualified to undertake
the assessment of the insured property and provide their opinion with
respect to the cause and extent of the damage claimed.
There exists a reasonable consistency in the reports made available by
the consultants in terms of the cause and extent of the damage.
There is a consistent view with respect to the rotation of the west wall‟s
foundations which led to the lean in west wall over an extended period
of time and that the wall ties were corroded and failed.
The wall ties were found to be in a deteriorated and corroded condition
and were not serving their purpose i.e. securing the external skin of the
brick wall.
Case No: 330864 Determination Page 11 of 14
The lean in the wall arising from rotation of the foundations had been
present for many years and on balance was also present prior to the
Applicants purchasing the property and prior to policy inception.
There are a number of factors which have been determined to have
contributed to the resultant lean in the wall which ultimately led to the
failure of the wall ties and the wall‟s partial collapse. Some of these
factors include:
highly reactive clay soils;
shrinkage, swelling and settling of the soils over the years due to
not only the inadequate footing depth but also soil drying from
nearby trees and the drought;
the presence of trees in the vicinity of the wall which contributed to
the drying and therefore shrinking of foundation soils;
rotation of the foundations;
insufficient depth of the foundations;
weak or poor mortar;
failed wall ties which had corroded:
insufficient spacing of wall ties;
wear and tear/gradual deterioration; and
the effect of the rain and wind in January 2011.
39. I acknowledge the Applicants‟ concerns regarding the FSP‟s reference to
current building codes and/or standards. I accept it is not reasonable to
apply current standards to the manner in which the west wall was
constructed as these standards were not in place at the time of construction.
I note the FSP appears to accept this too in its IDR letter dated 24 August
2011.
40. I also accept the Applicants‟ position that it is not reasonable to expect them
to have maintained the wall ties as these were not apparent (being inside the
wall) and noting R‟s comments that maintenance of wall ties is not a service
readily and/or available at all.
41. However, in order to establish indemnity under the policy, the Applicants
must establish on the balance of probabilities that the damage claimed was
the result of a storm as defined in the policy. In addition to the indication that
the lean (which resulted in the collapse of the wall) had been occurring
gradually over an extended period of time it is evident there were several
other contributing factors to the collapse which factors fall within the general
exclusion provisions of the policy.
42. I have consider ed the Applicants‟ contention that the January 2011 storm
conditions were the proximate cause for the damage claimed. It is not in
dispute that there was wind with maximum wind gusts of up to 74, 63 and
72km/hr on 7, 8 and 14 January 2011. There was not much rain in January
Case No: 330864 Determination Page 12 of 14
2011 but there was recorded 3 days of rain of note on 12, 14 and 15 January
2100 when there was 15.4, 28.2 and 22.4mm of rain respectively.
43. The wall actually collapsed on 28 January 2011. On that day there was no
rain recorded and wind gust up to 35km/hr. There had been no wind gusts of
note recorded for 2 weeks.
44. BOM also provides the “Beaufort Scales (Wind Speed)” which I have
considered carefully. The Scale provides an indication of the effects of wind
at certain speeds. The scale provides an indication of the effects of wind
speeds between 62 – 74km/hr which is relevant to this matter:
8 34 - 40
knots
62 - 74
km/hr
39 - 46
mi/hr Gale
Moderately high waves
(5.5 m), crests break into
spindrift.
Difficult to walk against
wind. Twigs and small
branches blown off trees.
45. According to the above Scale (which I am satisfied provides a reasonable
indication of the effects of wind speeds), the effect of a weather event with
wind speeds between 62-74km/hr is that it becomes difficult to walk against
the wind and twigs and small branches may be blown off trees. Accordingly,
I am not satisfied that on the balance of probabilities that the three days of
wind in January 2011 (which 3 days were well before the day the wall
collapsed) were strong enough to be described as violent wind as is required
under the policy terms and strong enough to be the sole proximate cause for
the collapse of the western wall‟s exterior skin.
46. I note the opinion of D that the winds on the 3 days in question created
suction forces on the wall and may (my emphasis) have caused the outer
skin of the wall to lean more which left it in a condition susceptible to
collapse. However this statement is insufficient to persuade me on the
balance of probabilities that the wall collapsed solely because of the wind.
Rather the totality of his opinion is that the wall was already susceptible to
collapse as it was already tilting and it was tilting as the soils under the
footing had dried out and shrunk. This cause is clearly excluded from co ver
under the policy.
47. Even R who examined all the reports agreed the collapse was due to the
rotation of the foundation and that this is caused by soil movement from the
drying out by trees and then the softening of the soil from water from the
nearby drains. In other words from soil movement which is excluded under
the policy.
48. I also accept the expert evidence of F which is that the rain did not cause the
damage. He says this as the soil would have been expected to swell not
shrink with rain resulting in local heave. I accept this and I note also his
inspections which showed the levels contours did not indicate local heaving
in the surrounding affected areas.
49. Rather I am satisfied that the available evidence establishes, on the balance
of probabilities, that the western wall had a lean for many years prior to its
ultimate collapse due to a number of contributing factors as discussed
Case No: 330864 Determination Page 13 of 14
above. Accordingly, I am not satisfied the Applicants have been successful
in establishing, on the balance of probabilities, that the damage claimed was
the result of the insured event of storm under the policy.
50. Further even if I were to accept the damage was caused by storm as
defined, the principle set down in the Wayne Tank and Pump Co Ltd v
Employers Liability Assurance Corporation Ltd [1974] QB 57 acts to defeat
the Applicants‟ claim. That case establishes the principle that if there are
concurrent causes of a loss where one is subject to cover and the other is
not, an insurer is not liable for the loss.
51. Therefore even if it is accepted that wind and/or rain in January 2011 was a
proximate cause of the loss, as the failure of the ties and the soil movement
were also proximate causes of the loss and these are excluded under the
terms of the policy, then the exclusion claus es apply to defeat the Applicants‟
claim.
Section 46 of the Act
52. I note there has been reference to the fact that the Applicants would not
have been reasonably aware of the issues with the wall. Further, that effort
had been made prior to the purchase of the insured property to conceal
and/or temporarily attend to the e xtent of the lean in the wall. Also, that it
would not be reasonable to expect the Applicants to have been aware of the
corroding wall ties and therefore arrange for maintenance works to be
completed.
53. Section 46 of the Insurance Contracts Act 1984 (the Act) prevents an insurer
from relying on an exclusion clause that refers to the condition of a thing
before the contract was entered into , if the insured (or a reasonable person)
was not aware of the defect or condition which wholly or partly caused the
damage claimed for.
54. The case of Nelson v The Hollard Insurance Company Pty Ltd [2010]
NSWSC 199 states that Section 46 of the Act does not apply to an exclusion
of an event which makes no reference to when the event occurs. It is only
exclusions which refer to a condition existing before entry into the contract of
insurance which are affected by Section 46 of the Act.
55. In this dispute, the exclusion clauses relied upon by the FSP apply generally
and are not temporal in nature. The exclusion clauses are not directed to
defects which pre-existed the commencement of the policy. Accordingly, I
am not satisfied that Section 46 of the Act assists the Applicants in this
dispute.
Case No: 330864 Determination Page 14 of 14
Determination
56. On the basis of the available information and for the reasons stated, I
determine that:
The Applicants have not been able to establish, on the balance of
probabilities, that the loss claimed falls within the scope of cover
available under the policy; and
The FSP was entitled to decline indemnity to the Applicants pursuant to
the exclusions in the policy.