Home / Financial Firm (Unknown - Insurer) / Determination 329865

Determination 329865

Denial of strata claim for damaged main electrical cables under wear and tear exclusion

FirmFinancial Firm (Unknown - Insurer)
Decided2014-07-08
ProductGeneral Insurance · Strata
OutcomeFor the firm
Amount awarded—
Non-financial loss—
Amount claimed—
SourceAFCA PDF

Summary

A body corporate claimed under its strata policy for damage to main electrical cables and sought compensation and legal costs. The FSP denied the claim under the wear and tear exclusion. AFCA upheld the denial and declined compensation and legal costs.

The proximate cause was an installation defect and 30 years of deterioration, which falls within the gradual deterioration and wear and tear exclusion; FOS terms preclude compensation for consequential loss excluded by the policy.

Issues

Subjects and remedies

no remedy

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Determination General Insurance - Domestic Insurance - Residential Strata Title - FSP Decision - Denial of Claim - Exclusion/Condition Determination Case No: 329865 Determination Page 1 of 5 Case number : 3 3 29865 7 July 2014 1 Overview 1.1 Dispute The Applicant is the manager of a body corporate which held a residential strata title policy with the Financial Services Provider (FSP). The policy was current at the time of the loss and provided cover against accidental damage. The Applicant lodged a claim for the damage to main electrical cables (the cables), related costs and legal costs. The FSP denied the claim because it considered the damage was caused by wear and tear. The Applicant disagrees with this outcome and wants the FSP to pay the claim in full. 1.2 Issues and key findings Is the FSP entitled to deny indemnity for the claimed loss? The FSP is entitled to deny indemnity for the claimed loss because:  the evidence on balance indicates the proximate cause of damage was a defect in the initial installation of the cables followed by slow deterioration in the protective sheath which ultimately permitted water penetration  the policy exclusion relating to lack of maintenance … corrosion, wear, tear … gradual corrosion or gradual deterioration applies  the cables are not covered under the machinery breakdown policy. Is the Applicant entitled to compensation and/or legal costs? The Applicant is not entitled to compensation and legal costs because:  the Financial Ombudsman Service (FOS) cannot consider compensation for consequential financial losses when this is expressly excluded in the policy  the circumstances of the dispute do not warrant the need for legal costs. 1.3 Determination This Determination is in favour of the FSP.  The FSP is entitled to deny indemnity for the claim and is not required to take further action.  The Applicant is not entitled to compensation or legal costs. Case No: 329865 Determination Page 2 of 5 2 Reasons for Determination 2.1 Is the FSP entitled to deny indemnity for the claimed loss ? The evidence indicates the proximate cause of damage was a defect in the installation of the cables which over 30 years deteriorated thereby permitting water penetration, which caused the cable to ‘short’ The parties‟ experts have differing views on what was the cause of damage: Expert Key conclusions on what the cause of damage is Applicant ‟s repairer ( C )  The lack of appropriate protection of the cable.  The weight of concrete over the years.  Water intervention  Potentially, electrical surges and lightning strikes. FSP‟s expert (A)  The lack of appropriate protection of the cable.  Age related wear and tear.  Water intervention Case law provides the proximate cause is not determined by identifying the last event or final trigger, but by determining what is the dominant or effective or operative cause, whether or not the last in time or the sole cause. Although both experts identify different causes, they coincide in that the “lack of appropriate protection of the cable” was one of the causes of damage. A review of the experts‟ opinions indicates the proximate cause of damage was the lack of this protection, followed by 30 years of wear and tear and concrete weight which ultimately allowed water to penetrate the cables ‟ outer sheath, thereby producing a „short‟. As to the possibility of the power supplier (EX) causing the damage while replacing the fuses, the evidence indicates both parties‟ experts agree the damage to the cables had already occurred during the first incident and prior to EX‟s involvement. The policy exclusion for damage caused by gradual corrosion or gradual deterioration, wear, tear … applies The FSP relies on the “wear and tear” exclusion contained in the Product Disclosure Statement (PDS) to deny the claim. The Panel, on the balance of probabilities, accepts this exclusion applies to the totality of the circumstances surrounding the damage and accordingly as the exclusion is proven, the FSP is entitled to deny the claim. In these circumstances, Section 46 of the Insurance Contracts Act 1984 (the Act), does not apply and the Panel need not address that issue further. However, for the sake of completeness, the Panel is satisfied that Section 46 of the Act only has application to an exclusion clause that refers to the condition of Case No: 329865 Determination Page 3 of 5 the cables at a time prior to the inception of the policy. The exclusion clause has no such reference and thus Section 46 of the Act, does not apply. The cables are not covered under the machinery breakdown policy There is cover provided under the machinery breakdown policy. However, the PDS specifically excludes cover under this policy for “reticulating electrical wiring”. This type of main supply power cables is considered “reticulating electrical wiring”. Further, these cables are not considered “machinery” under a plain Engli sh definition. Accordingly, there is no cover under the machinery breakdown policy for the damage to the cables. 2.2 Is the Applicant entitled to compensation and legal costs? FOS cannot consider compensation for consequential losses when this is expressly excluded in the policy Under clause 9.3 of the FOS Terms of Reference (TOR), FOS may consider the awarding of compensation for consequential financial loss and non-financial loss. However, the TOR precludes FOS from awarding compensation where an insurance policy expressly excludes such liability. The Applicant has requested payment for “disimbursements [sic] and own expenses” but has not identified the specific expenses he refers to. Nevertheless, it is clear from this wording that he refers to a financial loss as a result of the claimed damage. As the PDS clearly excludes “consequential loss, loss of use or depreciation”, FOS is not in a position to provide compensation to the Applicant. The circumstances of the dispute do not warrant the need for legal costs Under clause 9.4 of the TOR, FOS may consider an Applicant‟s legal costs to be contributed to by the FSP. In accordance with the Operational Guidelines to the TOR, when legal costs are claimed, a consideration has to be made as to what is fair in the circumstances, whether the dispute raised legal issues which reasonably required legal advice, the complexity of the dispute and whether the Applicant genuinely required expert assistance. The Applicant argues statutory interpretation is not within the capability of the Applicant and this dispute involves significant body corporate/collective owner money and is subject to a statutory regime. However, the basis for the outcome of this dispute relies mainly on the expert opinion of C and A, and the interpretation of the PDS, which are common issues in FOS disputes. Case No: 329865 Determination Page 4 of 5 The Applicant‟s argument for legal costs focuses on the high monetary value in dispute and the standard FOS process. These are insufficient grounds on their own to award legal costs. For these reasons, the Applicant is not entitled to legal costs. 3 Supporting information 3.1 FOS approach for this dispute This dispute has not been the subject of a FOS Recommendation. Due to its nature, FOS has considered it appropriate to proceed directly to Determination in line with the Operational Guidelines to the FOS Terms of Reference. This decision has been made by a Panel consisting of an Ombudsman and two Panel members with extensive experience in insurance industry matters and consumer claims. There has been a full exchange of the relevant material between the parties and each party has had the opportunity to address the issues raised. The Applicant is represented. For the sake of brevity and clarity in this decision, both the Applicant and his representative have be en referred to as “the Applicant”. 3.2 Key points from relevant supporting material Material Key points Applicant ’s repairer ( C ) Quotation 3 Jan 2012 Report 16 Jan 2013  The original installation of the consumer mains (power cables) did not comply with the Au stralian standards of the time (1991).  Mechanical protection was not afforded to the consumer mains (power cables) at the main switchboard end and t he single core double insulated conductors were directly buried and covered in concrete.  Over time, the weig ht of the concrete penetrated the outer and inner sheath of the conductors. The electrical current would have then started leaking into the garden but it was not until two phases leaked that the underground explosion occurred.  In the last 20 years, electrical surges or lightning strikes could have assisted in the deterioration of the cables.  The weight of the concrete over the years was the cause of damage. FSP’s loss assessor ( E ) Report 4 Jan 2012  C does not believe EX is responsible as the cables would most likely have been damaged prior to EX replacing the fuses.  There has been no machinery breakdown but simple cable failure. FSP’s expert ( A ) Report 16 Jan 2012  The power cables ru n underground from the transformer through a garden , through a hole cut out on a concrete wall of the underground car park and onto the switchboard room.  The hole cut into the wall would have had steel reinforcement, which would have had to be removed to allow the consumer mains to pass through the hole and gain access to the switchboard. Case No: 329865 Determination Page 5 of 5 Emails 20 Jun 2012 12 Jul 2012 24 May 2014  No protection was provided to the cabl es entering the car park via this hole , which is in a “jag ged state” with exposed cut stee l from the concrete reinforcement.  It is plausible the fact the cables were resting on this abrasive surface for approximately 30 years damaged the outer sheath and inner insulation of the cables due to vibration, expansion and contraction of the wall through normal cycles of heating and cooling.  This exposure of the i nsulation would have eventually led to a grounding of the cables and a “phase to phase short”, rupturing the fuses in the transformer.  The cables were not adequately protected, which is in breach of the Australian standards of the time (1981). The failure is a direct result of inadequate protection installed to the consumer mains during the initial construction of the building.  The proximate cause of loss is mechanical damage (vibration, expansion and contraction of the abrasive concrete area surrounding th e cable) , which is age related “wear and tear”.  The most likely cause of damage was that the cables were resting on open and exposed reinforcement and not given adequate mechanical protection. Over a number of years, the cable insulation has broken down du e to the lack of mechanical protection, being pressed on top of the reinforcement by concrete and earth.  The short circuit had nothing to do with EX. At the time EX arrived, the damage was already done to the cables.  The evidence leaves no doubt the failur e of the cables was due to the installation process of the mains in the past.  The act of re - energising an electrical installation from the point of a dedicated transformer is identical to restoring power from a mains‟ failure. EX‟s re - energising of this electrical installation did not pose an unacceptable risk to the safety of the electricians or the building. 3.3 Other information relied upon  The Product Disclosure Statement effective on 1 September 2007, pages 18, 31, 32 and 51.  The Renewal Certificate for the period 31 January 2011 to 31 January 2012.  Insurance Contracts Act 1984 , section 46.  Electrical Safety Act 2002 (QLD) .  Body Corporate and Community Management Act 1997 (QLD) .  Body Corporate a nd Community Management (Accommodation Module) Regulation 20 08 (QLD) .  Greg Nelson v The Hollard Insurance Company Pty Ltd [2010] NSWSC 199.  The parties‟ submissions.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.