Home / Financial Firm (Unknown - Insurer) / Determination 329179
Determination 329179
Storm damage claim to pool denied under hydrostatic pressure and earth movement exclusions
Summary
Landlords claimed storm damage to their pool after flooding in 2012, and the insurer denied the claim as caused by excluded hydrostatic pressure and earth movement. AFCA found the insurer entitled to deny the claim and ordered nothing.
On the balance of probabilities the damage was caused by hydrostatic pressure from flooding of the backyard, and under the Wayne Tank concurrent causation principle the excluded cause defeats the claim.
Subjects and remedies
home or building damagenatural disasterno remedy
Text of the determination
Case No: 329179 Determination Page 1 of 8
Case number: 329179
General Insurance - Domestic Insurance - Home Building - Storm - FSP
Decision - Denial of Claim - No Insured Event - Exclusion/Condition -
Hydrostatic Pressure - Earth Movement
15 April 2014
Summary
Description:
This dispute concerns a claim by the Applicants under a home insurance
policy for storm damage to their pool.
Basis for Determination:
The material provided entitles the FSP to deny the claim as it supports its
contention that the damage to the pool was caused by hydrostatic pressure
which cause is excluded from cover.
Determination:
The FSP is entitled to deny the claim.
Background
1. The Applicants held a landlord insurance policy with the Financial Services
Provider (FSP), which covered the home building for listed insured events.
2. On 14 August 2012, the Applicants lodged a claim for storm damage to their
pool.
3. The FSP denied the claim on the basis the pool was damaged by hydrostatic
pressure and earth movement, both of which are excluded from cover by the
policy. The Applicants disagree with this outcome and want their claim paid.
Summary of Applicants ’ position
4. The Applicants say:
Determination
Case No: 329179 Determination Page 2 of 8
The pool has withstood different weather conditions over the years
since it was built not long after May 1988, so something specific must
have happened in 2012, to cause the damage.
It cannot be explained what the circumstance that ca used the damage
was but they are confident their tenant (DG) did not allow water levels
to fall and the damage was not due to hydrostatic pressure.
The neighbouring properties both within two metres of the pool are
lower than the Applicants’ pool yet their pools were not damaged.
Their engineer (WD) says the pool was installed correctly. The back fill
around the pool did not slump.
They question why the FSP would say a pool approved for construction
in 1988 is governed by a building standard of 1994.
The damage was possibly due to a combination of severe rainfall, a
king tide and the pool’s water level being low at the time.
Summary of FSP’s position
5. The FSP says:
A loss assessor (CL) and an engineer (U) were engaged to report on
the cause of damage.
Based on their reports, it considers that prior to the storm event the
backfill of the pool had been moving over time compromising the
structural integrity of the pool walls and floor, which was further affected
by hydrostatic pressure.
The backfill material for the pool did not comply with Australian
Standards. The damage would not have occurred had there been no
slumping of the backfill. Further, WD has not ruled out hydrostatic
pressure and has said the hydrostatic valve may not have been
working to its optimum.
The pool was damaged by a failure to comply with Australian
Standards, hydrostatic pressure as well as earth settlement and
expansion, all of which are excluded under the policy. It is entitled to
rely on these exclusions to deny the claim.
6. The FSP relies on the following policy provisions contained within the
Product Disclosure Statement:
“ 2. General exclusions.
We do not insure you for any loss or damage that is caused by or arises from:
wear and tear, gradual deterioration, or fading
…
settling, expansion, shrinkage or any earth movement other than
earthquake.
Case No: 329179 Determination Page 3 of 8
…
3.4 Residential Home and Contents Insurance insured events.
We will insure your building and contents at the site against loss or damage
caused by the following events if they occur during your period of insurance.
…
Storm
…
We won’t cover
loss or damage caused by or resulting from:
− hydrostatic pressure. ”
Issue
7. Whether the FSP is entitled to deny the Applicants’ claim under the terms
and conditions of the policy.
Reasons for decision
8. As advised to the parties, due to the nature of the dispute, the Financial
Ombudsman Service (FOS) has considered it appropriate to expedite the
dispute to Determination in accordance with the Operational Guidelines to
the FOS Terms of Reference.
9. I am satisfied a full exchange of relevant information has taken place
between the parties and each party has had the opportunity to address the
issues raised.
10. In making this decision, I have considered the entire file, including all
communications with and between the parties, some of which I will not
mention individually.
11. To support their position, the Applicants have provided a report, a letter and
an email from WD, a statutory declaration from DG and images and videos
of the demolition of the pool, which show part of the backfill still in place.
12. To support its position, the FSP has provided reports from CL and U and a
statutory declaration and “handwritten notes” from a CL staff member who
initially attended the site to assess the loss.
13. I have carefully reviewed the parties ’ materials. I note the following:
The Applicants’ tenant
He said he had lived at the property for six years and was used to
looking after the pool. He said he had no problem prior to these floods.
Case No: 329179 Determination Page 4 of 8
He insists he told the adjuster that the pool was damaged only by one
incident – the March 2012 floods.
He says the adjuster took no notes when she talked to him.
The adjuster CL
CL’s adjuster says the tenant DG told her at the site inspection on 24
August 2012, that during the March 2012 storms, he had noted the
water level of the pool dropping but he continued to refill it. He said
mud was entering the pool too via the hydrostatic valve. The water level
continued to drop and then cracks became apparent in the swim ledge
and DG told the Applicants.
DG told the adjuster that the flood waters covered the front garden and
entered the home. The water entered the back yard but was not as
deep in the back yard. Flood water lay over the paved area beside the
pool until the following morning.
The adjuster inspected the pool and noted the walls were cracked and
bulging inwards. The pool floor had lifted. The paved area on one side
of the pool had subsided.
The adjuster needed to engage an expert to provide advice on
causation.
Her file notes are produced and attached to a Statutory Declaration and
she swears to what she was told by the tenant which is summarised
above.
The FSP’s expert U
He inspected the pool on 15 October 2012. He provides a report and
rebuts the contentions of the Applicants’ engineer.
He based his report on what he was told which was that during heavy
rain in November 2011 there was movement in the paved areas which
increased over the ensuing months and then the pool lost water.
He describes the pool and its surrounds and notes the pool is
surrounded by paving and gardens which are 100mm above the
pavers. He estimates the normal water level is about 50 to 100mm
below the surrounding area. He says it is the level of the immediate
pool surround that is the concern and not the levels of adjacent
properties.
He notes a large void beneath the paving next to the pool. He also
notes the backfill material had no cement stabilisation and the floor of
the pool had been pushed up about one metre. There were cracks in
the wall and floor. Photographs show this as well as the bulge in the
walls and floor.
U concluded the bedding material was not properly compacted when it
was installed and the backfill was not stable as cement was not in the
backfill. This did not comply with Australian Standards (he quoted 1994
Standards). He later concedes that there is no guarantee that the
Case No: 329179 Determination Page 5 of 8
stabilisation of the backfill would have prevented the problem from
occurring at all.
The standard also requires that the normal pool water surface level be
at least 50mm above the surrounding ground so that the pressure at
the floor level inside the pool is always greater than the pressure under
the pool.
Based on the extent of the void, he says the backfill has slumped
towards the bottom of the pool and has caused inward bulging of the
pool.
The pool relies on the support of the backfill to withstand the
hydrostatic forces within the pool. Without this support, the walls flex
outwards and stress the interface between the wall and the floor. The
outward buckling of the walls also makes the pool floor next to the wall
curve up slightly which makes the pool susceptible to the effects of
trapped air under the floor when the groundwater level rapidly rises.
And over time this causes the floor to crack.
Repeated flexing over the years has resulted in fatigue of the shell and
cracks eventually formed along the interface between the walls and
floor as there was insufficient support which was further influenced by
differential hydrostatic pressures during periods of rapid ground water
rises.
U says it is highly unlikely that a flexible material like fibreglass will
catastrophically fail under the influence on one rainfall event.
U says he does have the expertise to comment. He is a civil engineer
and has reported on more than 30 pool failures in 15 years. The FSP
produced his resume which it says details his extensive civil and
structural engineering experience along with his 19 year insurance
claims experience.
The Applicants’ expert WD
WD says that he is an expert as he has installed over 2000 fibreglass
pools (some recently) and ran a factory for two years that made these
pool shells. In his signature after his name is (Mech. Eng), so I assume
he is a mechanical engineer.
He rebuts the findings of U and says that if the backfill was incorrectly
comprised and the bedding material had been improperly compacted,
that this would be apparent within a few days of installation.
He says the slumping of the backfill material did not cause the walls to
buckle and the pool did not fail due to a progressive failing over time.
He says the walls only pull in when the floor lifts and that if backfill
slumps behind the walls of a fibreglass pool, some outward bowing can
occur.
If the void behind the walls become considerable, WD says the
pressure of the water can break the walls. But it is not physically
possible for the outward movement of the walls to cause the floor to
buckle. For this to happen, the outward pressure on the walls would
Case No: 329179 Determination Page 6 of 8
need to be greater than the weight of the water in the pool. He says
that a void was created when the floor lifted and pulled the walls in. The
backfill then slumped into the void.
He was there when the pool was demolished. Usually the concrete
beam or collar remains intact and this was the case with this pool. He
has provided photographs and a video of the demolishment of the pool.
The Australian Standard referred to by U provides that backfill around a
pool needs to be stabilised. The floor or bedding material never has
cement. It is to be free draining material. He acknowledges the
Standard does require cement stabilisation in the backfill but that lots of
pools were built without it.
In any event, the Standards referred to were only in force after the pool
was installed. When this pool was built, cement stabilised backfi ll was
not considered.
He saw the pool when it was demolished and the backfill was sand
which he says usually compacts when watered in.
WD notes the surrounding areas of the pool. He says the neighbours’
grounds are 100-200mm drop below the operating level of the pool so
the water in the ground around the pool could not be higher than the
water in the pool under normal conditions.
WD says that repeated flexing over the years does not cause fatigue to
the fibreglass shell, but has not explained the reason why this is so.
He says that he has witnessed a failure by one event on multiple
occasions.
He notes this pool has been operating without compromise for over 20
years and concludes the pool failed because of a specific out of the
ordinary event. It caused the floor to lift and the walls of the pool to
collapse. He notes in his conclusion:
The pool level could have been low at the time (and a tenant or
owner usually does not like to admit this);
The rain could have quickly raised the ground water level;
The rain event may have combined with a high tide (a high water
table was noted when the pool was removed); and
The hydrostatic valve now many years old may not have been
working to its optimum or could not cope with the unusual
conditions.
Analysis
14. There is an onus on an insured to establish on the balance of probabilities
that a claim fits the definition of an insured event. This is known as a prima
facie claim. If this onus is discharged, the onus shifts to the insurer to
establish the application of any exclusion on which it relies to deny the claim.
Case No: 329179 Determination Page 7 of 8
15. The FSP does not dispute a storm occurred or that the pool was damaged.
The issue in dispute is whether the pool was damaged by an insured event
(storm) or by excluded events (earth movement or hydrostatic pressure).
16. U says he bases his opinion on what he was told , which was that after a
November 2011 rain event, the paved area started moving and it was not
until the March 2012 event, that the pool started to fail. It is not clear from
where this information emanated although the Applicants often refer in
emails to damage caused in November 2011.
17. I do note however, that the tenant DG is adamant the damage was caused in
March 2012.
18. Further, WD notes the pool was built before the building standard mentioned
by U was in place. I do not accept that it is reasonable to retroactively apply
and rely on standards and expect the pool installer to comply with them. For
this reason, I am not satisfied that the FSP can rely on this argument. In any
event, I note that U in his last report, concedes that there is no guarantee
that the stabilisation of the backfill would have prevented the problem from
occurring at all.
19. However, the FSP can still rely on the policy term which says that it does not
cover loss or damage resulting from hydrostatic pressure. Considering the
statement of DG, I am satisfied that the house and garden were flooded in
the storm event and that the flood water came into the backyard and lay on
the paved area beside the pool until the following morning.
20. I am also satisfied that this would have resulted in the water level outside the
pool being above the water level inside the pool even if the tenant kept filling
the pool. He says he did but he also says the water level continued to drop.
U says that this imbalance would affect the hydrostatic pressure in the pool. I
accept that is the case.
21. DG also says that mud was entering the pool via the hydrostatic valve. The
Applicants’ expert WD , also notes the hydrostatic valve allowed mud into the
pool during or after the March 2012 event. He says the hydrostatic valve
may well have not been working to its optimum. I accept this proposition
when one considers the observations made by DG and the age of the pool.
22. WD also says in his conclusion that the pool at the time of the damage could
have been inordinately low. Further, he also notes when the pool was
removed for replacement, there were issues with a high water table.
23. Considering the relevant material, I am satisfied on the balance of
probabilities that the damage was caused to the pool because of the flooding
to the back yard, which affected the hydrostatic pressure of the water in the
ground compared to the water in the pool and the valve in the pool did not
operate to its optimum to level the hydrostatic pressure.
Case No: 329179 Determination Page 8 of 8
24. Accordingly, I am satisfied the FSP can establish on the balance of
probabilities the damage was caused by hydrostatic pressure and thus it is
entitled to rely on the policy exclusion to deny the claim.
25. Even if I were to accept the storm caused or contributed to the damage, I am
satisfied the evidence indicates this would be a scenario where both storm
(covered event) and hydrostatic pressure (excluded event) would have
caused the damage concurrently.
26. In this scenario, where there are two concurrent causes of a loss where one
is subject to cover and the other is excluded, an insurer is not liable for the
loss (refer to Wayne Tank and Pump Co Ltd v Employers Liability Assurance
Corp Ltd [1974] QB 57).
27. I am satisfied the Wayne Tank principle would operate in this case to defeat
the claim.
28. Accordingly, I am satisfied the FSP is entitled to deny the claim under the
terms and conditions of the policy.
Determination
29. Based on the available information and for the reasons stated, I determine
the FSP is entitled to deny the Applicants’ claim.