Strata unit storm damage claim denied under gradual deterioration and defective workmanship exclusions
Text of the determination
Case No: 319623 Determination Page 1 of 12
Case number: 319623
General Insurance - Domestic Insurance - Residential Strata Title - FSP
Decision - Denial of Claim – Policy Exclusion
24 April 2014
Summary
Description:
This dispute concerns a claim by the Applicant under a Residential Strata
Policy for storm damage to his unit.
Basis for Determination:
The material presented does not persuade me that the damage in unit 8 was
caused by a storm as defined. Rather, I am satisfied that the damage was
caused by gradual deterioration of the render which allowed rain water into
the unit. This cause of damage is excluded from cover under the policy.
Determination:
The FSP is entitled to deny the claim.
Background
1. I have reviewed all the material submitted by the parties and save where I
make note specifically, I am satisfied the Background as set out in the
Recommendation is accurate and is as follows.
2. The Applicant is an owner of a unit in a strata-titled complex, which was
insured under a Residential Strata Policy issued by the Financial Services
Provider (FSP).
3. On 7 November 2012, the Applicant, through his broker lodged a claim for
structural cracks around the windows on the second floor of his unit, said to
have occurred on 2 August 2012.
4. The FSP refused the claim on the basis that they were excluded from cover
under exclusions 1(c), 1(d) and 2(b) of the policy.
5. The Applicant disputes the FSP‟s denial and seeks full indemnity for the
disputed damage, totalling $4,200.
Determination
Case No: 319623 Determination Page 2 of 12
6. As the Applicant did not agree with the FSP‟s decision, the dispute was the
subject of a Recommendation. The Recommendation was in favour of the
FSP and was not accepted by the Applicant. The FSP accepted the
Recommendation. In the circumstances, the matter has been referred to me
for Determination.
Summary of Applicant’s p osition
7. I have reviewed all the material submitted by the parties and save where I
make note specifically, I am satisfied the Applicant‟s position as s et out in
the Recommendation is accurate and is as follows.
8. The severity of the storm events experienced in the area in August 2012,
has caused the cracks in the render around the second floor windows of his
unit. The balcony is a separate issue. It was damaged in December 2011
and there is no claim for this event.
9. No visible defect was indentified during the pre-purchase inspection.
Therefore, any defects identified as being the cause of the water ingress was
not known to him prior to the 2 August 2012 s torm.
10. The property has been well maintained and there is no wear and wear to the
rendering as suggested by the FSP‟s experts.
11. The FSP‟s building inspector‟s conclusion is unreliable as he has incorrectly
identified the apartments‟ numbers in his report. Even when he corrected the
report, he still left errors in the paragraph headed Conclusions.
12. The FSP has not offered any adequate explanation to support its decision
that the windows were not damaged by the storm. He says that the damage
to unit 10 occurred after this storm. Further, damage to the cladding
continues with each storm.
13. The windows were said to be “performing their function ” at the time of the
pre-purchase inspection and the deterioration in the render around the
windows only occurred after the 2 August 2012 storm due to the FSP‟s delay
in authorising repairs.
14. The claim should be accepted as he was not aware of the defect when he
purchased the property. His expert has told him that it is difficult to make a
determination as to the cause of damage when the time between the
inspection and the storm is great.
15. The Applicant rejected the Recommendation. He provided no further
documentary information in support of his position and essentially reiterated
his position. He wrote that he rejected the Recommendation for a number of
reasons. I note he says:
the Recommendation‟s conclusion relied heavily on the two building
reports of the FSP, both of which contain errors in them. The Applicant
Case No: 319623 Determination Page 3 of 12
has pointed out the errors before, namely that the report from (A) says
that he informed A that the water ingress through the cracks around the
windows to the master bedroom and study had been happening for
years and causing damage. This is incorrect. This refers to
waterproofing issues with the balcony. This is a separate claim and the
report from RS confuses the numbers of the units and the layout of the
units which should lower confidence in his expert opinion.
The issues with the exact date of the storm which caused the damage
does not have any bearing on the ultimate outcome. The pattern of
rainfall described by the Case Manager‟s r esearch of the BOM is
entirely consistent with the assertion that the initial damage occurred
with a single storm event, with resultant degradation to the cladding
occurring over time after this initial event.
The Applicant does not know exactly when the initial event occurred.
He was not alerted to the fact that damage to his and the next door's
property had occurred until he spoke to the Owners Corporation
Managers in late August. He concludes that the initial damage occurred
in the storm activity between 26 July and 1 August 2012.
Further, damage to the external cladding then continued over time after
the initial damage occurred.
He refers to the definition of storm from the FSP ‟s policy and notes it is
„ a violent wind sometimes combined with thunder, heavy falls of rain,
hail or snow. ‟
The inspections carried out on behalf of the FSP were too far after the
event to be able to reliably confirm that the damage did not occur as
the Applicant has stated.
The evidence is that prior to the storm event, the cladding was intact
and performing its function, then seven months after the event, the
damage had occurred with resultant degradation to the cladding which
continues due to the FSP‟s fai lure to act.
If the cladding had been deteriorating over time from the date of the
pre-purchase inspection in March 2008, there was no evidence of this.
The Recommendation relies on the Applicant‟s report which concludes
that the most likely cause of the water ingress was the deteriorated
parapet wall cladding. This is irrelevant to this claim but relevant to the
balcony claim.
Summary of FSP’ s position
16. I have reviewed all the material submitted by the parties and save where I
make note specifically, I am s atisfied the FSP‟s position as set out in the
Recommendation is accurate and is as follows.
Case No: 319623 Determination Page 4 of 12
17. The available expert evidence suggests the damage has been occurring
over a period of time and is not the result of a single insurable event such as
water inundation from a storm occurrence.
18. Water is not entering the building due to an insured event but rather a failure
of the building to cope with heavy rain.
19. The cracks in the render were caused by gradual deterioration, lack of
maintenance and general wear and tear.
20. The quote is to do work to the windows to prevent water entering the
building. The policy specifically excludes the rectification of such faults.
21. The inspection done by (PS) was done in 2008 and there was no visible
damage to the cladding then (FSP emphasis).
22. The damage claimed does not fall within the scope of the policy. The FSP is
entitled to deny the claim based on the following policy exclusions:
“ Policy 1 – Insured Property
Policy 1 is a „broad form‟ accidental loss and damage insurance contract in
terms of the Insurance Contracts Act, 1984.
What we insure
We insure You up to the Sum Insured shown for Policy 1 on the Schedule,
against ACCIDENTAL LOSS or DAMAGE to Your Insured Property which
occurs during the Period of Insurance.
Exclusions – what we do not insure
1. We will not pay for loss or damage;
...
c Caused by lack of maintenance, rust, oxidation, corrosion,
wear, tear, fading, gradual corrosion or gradual deterioration,
concrete or brick cancer, developing flaws, wet or dry rot, or
failure to maintain Your Insured Property in a reasonably good
state of repair.
d Caused by non-rectification of an Insured Property defect,
error or omission that You were aware of, or should reasonably
have been aware of.
2. We will not pay for:
...
b the cost of rectifying faulty or defective materials or faulty or
defective workmanship” .
23. The FSP accepted the Recommendation and did not provide any further
documentary information in support of its position save to rebut the
Applicant‟s further submission as follows:
It repeats that the alleged errors in the FSP's expert reports do not alter
the substance of the reports and their conclusions ; and
Case No: 319623 Determination Page 5 of 12
The Applicant concedes in his further response that there was a
degradation of the cladding occurring over time. However, the Applicant
states that this degradation was initially caused by a storm e vent. As
such, it appears that there is no dispute that the cladding was subject to
degradation. Accordingly, the Member reasserts the exclusion which
states that the Member w ill not pay for loss or damage “ caused by lack
of maintenance, rust, oxidation, corrosion, wear, tear, fading, gradual
corrosion or gradual deterioration…”
Issue
24. Whether the FSP is entitled to deny the claimed loss.
Reasons for decision
25. There has been an exchange of material between each party and I am
satisfied each party has had an opportunity to reply to the issues raised.
26. Each FOS case is decided on its merits, taking into account the facts of the
case. I have reviewed all the material submitted by the parties both before
and after the Recommendation was issued in order to reach my decision. I
will only refer to the relevant submissions and materials raised.
Material provided by the parties
Certificate of Insurance
27. The building was insured from 30 July 2012 - 30 July 2013.
The claim 7 November 2012
28. The broker lodged a claim for water damage to units 8 and 10 at the
property. The date of loss is 2 August 2012. The claimed loss to unit 8 is
$4,200. The claimed loss to unit 10 is $4,342.50.
29. The work required is to the bedroom and study windows in unit 8 and to
paint and install timber floors in unit 10.
30. By email dated 12 November 2012, the claim was denied regarding unit 8
because of exclusions but a settlement cheque less excess, was offered for
the painting in unit 10.
Loss adjuster A ‟s report 5 March 2013
31. As the Applicant did not accept the offer, the FSP appointed A, a loss
adjuster. A inspected the property at unit 8 on 1 March 2013. He inspected it
with the Applicant. A notes the following:
The property was built as a nursing home and converted later to
residential apartments;
Case No: 319623 Determination Page 6 of 12
There is a cement sheet cladding with a rendered finish;
There are flat clip lock roofs with box gutters;
The building is about 30 years old; and
The building is in average condition.
32. A took photographs of the building and damage and he wrote the following:
“[The Applicant] informed us he had occupied the unit for several years, and
informed us that during that period there have been several severe storm
related events where water had made its way into particularly Unit 10 which is
immediately next door to his unit. Unit 10 is a single story unit, whereas his is
built over two storeys. He claims that during heavy rains, water makes its way
in around windows to the north side of his unit, particularly the master
bedroom and a spare room. That water then makes its way down through the
wall and into Unit 10.
We conducted an inspection of those windows, and we attached photographs
for your attention. The windows are timber framed awning windows. They are
set into cavities around the cement sheet clad rendered walls and sills. You
will see from the photographs the condition of the render which is cracked and
broken. This is particularly evident along the top of a window wall between the
two rooms of Unit 8. We found no evidence, however of other insurable
damage to the outside of the building.
In our discussions with the owner, he claimed there had been several severe
storm events over the last two or three years which had resulted in water
making its way down into the unit below. He considered the insurers should
contribute to the cost of removing and replacing the windows and any other
damage inside the walls to ensure the building was water-tight against severe
weather events.
We informed the owner we could find no evidence of the need to replace the
windows or conduct other work to seal and make external parts of the building
water-tight was evident due to any insurable cause. We explained that if water
was making its way in during heavy storm events that was simply a failure of
the building to cope with such events. We also advised it was not the
responsibility of insurers to conduct preventative maintenance or deal with
wear and tear”.
Pre-purchase report from PS
33. In response, the Applicant provided a pre-purchase inspection report from
PS who inspected the property on 17 March 2008. I note the following:
The building is two storey and has aluminium windows and rendered
finish cladding;
The scope of the report was building defects only; and
It is a visual inspection report only.
34. Relevant extracts of PS‟s report state:
“ BEDROOM 1 AND 2 AND STUDY
Window/s Ok, the item described is performing the function it was
designed for and this condition is very typical for its age.
Case No: 319623 Determination Page 7 of 12
...
Cladding
Painting Ok, the item described is performing the function it was
designed for and this condition is very typical for its age
Damp ... Nil, No evidence of damp damage was found
Mouldings Ok, the item described is performing the function it was
designed for and its condition is very typical for its age
Deck/s... Ok, the item described is performing the function it was
designed for and this condition is very typical for its age
Steps/Stairs Ok, the item described is performing the function it was
designed for and its condition is very typical for its age.
Future Inspections
PS recommends “regular competent inspection should be carried out at least
on an annual basis ...”
Building consultant (RS) report 21 July 2013
35. In light of the information contained in the Applicant‟s pre -purchase
inspection report, the FSP engaged a building consultant (RS) to provide a
causation report. RS inspected unit 8 and unit 10 on 20 July 2013, with the
owner of unit 10 and the Applicant. RS noted that;
The walls that exhibit leakage are 75mm foam cladding with render
over;
Alterations have been made to the building in the last 10 years; and
He recommended that the rendered lightweight cladding on the upper
levels be rectified to stop water ingress, the flashings be provided and
the balcony be replaced to comply with the Australian Standards.
36. In an amended report, RS said (refer report attached to letter dated
28 August 2013. The letter confirms that RS has confirmed that apartment 8
and 10 are located beside each other and that apartment 8 has an upper
level which is above apartment 10):
“Inspection revealed that there is sever (sic) deterioration of the rendered
lightweight cladding around the windows outside the upper level of apartment
8, and particularly sever (sic) deterioration of the top horizontal surface of the
window wall that is constructed on foam cladding and render over.
There was no evidence of a flashing detail under the windows or flashing
around the windows in accordance with Building Code of Australia
requirements that have been applicable since 1996.
There was considerable cracking and deterioration around the aluminium
windows set into the rendered lightweight cladding, that would allow the
penetration of water into the space behind the cladding, and then into the
apartment below (apartment 10).
A Survey master Protimeter Dual-Function moisture meter was used to
determine that there was excessive moisture present in the timber reveals
and sills of the windows in both first floor bedrooms of apartment 8, thus
Case No: 319623 Determination Page 8 of 12
indicating continued water ingress due to the deterioration of seals around the
windows, and the cracking and deterioration of the rendered lightweight
cladding external to the windows.
An inspection was made of the apartment 10, and a Survey master Protimeter
Dual-Function moisture meter was used to test for possible water ingress to
the walls and floor below. It was noted that in some areas along the north wall
of the living room underneath the window of apartment 8 above, there was
excessive moisture present in both the plasterboard linings and the skirting
board, with minor indications of excessive moisture in the new timber flooring.
It was also noted that the window to apartment 8 has been built higher than
the internal finished floor level, and the internal walls and skirting around the
window were also tested and found to have excessive moisture present, thus
indicating a failure of the waterproofing to the window, and allowing water
penetration to the areas below, and possibly also into the areas of apartment
10 below.
...
Conclusion
Apartment 10
There is no evidence to suggest that the water ingress through the windows
and from the window is caused by or related to a storm or other singular
event, but rather a failure of the waterproofing to the window, and gradual
deterioration of the cladding around the windows, and to the gradual
deterioration to the sealants and joins in the framed sections of the windows.
Apartment 8
The (sic) is evidence to suggest that there is ongoing continued water ingress
into apartment 8, caused by water ingress through and around the windows of
apartment 10 above, and related to the gradual deterioration of the cladding
around the windows, and to the, gradual deterioration to the sealants and
joins in the framed sections of the windows; as well as leakage from the
window caused by a deterioration or failure of the waterproofing to the
window”
Inspection report from PS dated 7 November 2013
37. The Applicant provided a second report from PS after he inspected the
property on 7 November 2013. He also took photographs and his comments
are set out below.
38. PS says:
“ Special Purpose Inspection Report Leak Source to external cladding
...
General:
Inspection of the external rendered cladding & window penetrations for areas
of potential water/rain ingress
Items
Cracking was noted to the rendered window penetrations of both bedrooms
Case No: 319623 Determination Page 9 of 12
Significant deterioration to the cladding render finish of the window parapet
(frame & lightweight clad) wall.
Cracking was noted to the north east corner of the upper level cladding render
finish.
Moisture damage was noted to the painted internal sills of both bedroom
windows.
This could be attributed to either moisture ingress from the deterioration
rendered work to the exterior areas, or from internal condensation.
A section of glazing retention moulding was noted to be missing from the
second bedroom window assembly.
Other comments:-
This inspector undertook the initial pre-purchase property inspection for the
owner in 2008, and that report noted no visible cladding deterioration or
cracking, or any internal signs of moisture ingress to the relevant boundary
wall areas, or window penetration, at that time.
...
Conclusion:-
There doesn‟t seem to be any visual evidence of „faulty workmanship‟ as
suggested, to the window installations. The presence, or not, of appropriate
window flashings and or sealants, is obscured by the application of the render
coat to the exterior.
It is the opinion of the inspector that, although there are signs of some
moisture ingress around the window penetrations, the most likely
cause/source of the water ingress to the adjacent lower apartment is the
deteriorated parapet wall cladding.
This inspector has advised the owner of No 8 that in his exper ience, the
maintenance & upkeep of the external areas of these types of apartment
buildings has always been the responsibility of the relevant body corporate, so
he should obtain & read his Body Corporate document to clarify his right &
responsibilities”.
BOM Extracts
39. The Applicant has provided extracts from BOM which show:
A total of 70mm in the month of August 2012, which is above the
median of 54mm;
There is no rain recorded on 2 August 2012;
It rains a little most days of the month; and
On 10 August and 18 August there was 13.6mm and 15.4mm recorded.
40. The Case Manager reviewed BOM records and noted there was continuous
rainfall between 26 July 2012 and 1 August 2012 (seven days preceding the
date of loss). The accumulated rainfall recorded for these seven days was
33.4 millimetres.
Case No: 319623 Determination Page 10 of 12
41. She also notes the BOM‟s record show that the area experienced several
significant rainfalls in the preceding months. In particular, the monthly rainfall
recorded for May 2012 was 88.4 millimetres.
Analysis
42. It is an accepted principle of general insurance law that an insured bears the
onus to establish on the balance of probabilities that they have suffered a
loss caused by an event to which the policy responds. This is known as a
prima facie claim. Once so established, the onus shifts to the insurer to
prove on the balance of probabilities that an exclusion applies if it seeks to
deny or limit its liability for the loss.
43. Accordingly in this matter, the Applicant must prove on the balance of
probabilities that the accidental loss or damage claimed was caused by an
insured event such as storm. The damage or loss must occur during the
period of insurance. If that is established, the onus shifts to the FSP to prove
on the balance of probabilities the loss was caused by an exclusion such as
wear and tear and deterioration.
44. The policy defines storm to mean “a violent wind sometimes combined with
thunder, heavy falls of rain, hail or snow.”
45. Having considered all the material and the photographs carefully I accept
that:
the property was inspected by PS on 17 March 2008. It was a visual
inspection only. Nonetheless, he noted no defects in the windows or
cladding at that time. He did recommend regular inspections of the
property to detect defects. No evidence of regular inspections
thereafter is adduced by the Applicant.
the period of insurance began 30 July 2012;
the Applicant first claimed the date of loss was 2 August 2012;
after the Recommendation, the Applicant says he does not know
exactly when the initial event occurred as he did not know of the
damage until late August 2012. He concludes the damage occurred in
the storm activity (referred to by the Case Manager) between 26 July
and 1 August 2012.
BOM records show rain in May 2012 was 88.4mm; rain: 33.4mm
between 26 July 2012 and 1 August 2012; no rain on 2 August 2012;
rain on 10 and 18 August 2012; and 70mm of rain in August 2012.
A inspected the property on 1 March 2013. A said the render along the
top of the window wall between the two rooms is cracked and broken.
He said that if water was coming into the building during storms this is
the failure of the building to cope with the storms.
RS inspected the building on 20 July 2013. He also noted severe
deterioration of the cladding around the windows in unit 8 and the top
horizontal surface of the window wall. He noted flashing detail is
Case No: 319623 Determination Page 11 of 12
missing under and around the windows. He said water would come in
the cracking which would damage both units 8 and 10 and the damage
is not related to a storm or other singular event.
PS inspected the property again on 7 November 2013. PS also noted
cracking and deteriorated render work to the exterior areas. He said
this was not seen in 2008. PS could not comment on the window
flashings and sealants as they were obscured by rendercoat.PS
thought the most likely cause of water in unit 10 was the deteriorated
cladding on the balcony. PS said the maintenance and upkeep of the
external areas of these types of apartment buildings is with the Body
Corporate.
46. Having considered all the material, I am not satisfied that the Applicant can
establish on the balance of probabilities that the damage to unit 8 was
caused during the period of insurance by an insured event such as storm as
defined.
47. First of all, the Applicant is unable to identify when the loss and damage
occurred. He concludes the damage occurred in the storm activity (referred
to by the Case Manager) between 26 July and 1 August 2012. Although
there is evidence of some rain between 26 July and 1 August 2012, he has
not established that there was a violent wind as the policy definition of storm
requires.
48. Nor has he established that there was a storm in the period of insurance that
caused the damage. I am not satisfied that there was damage caused by a
storm as defined on or after 30 July 2012 when the insurance cover
commenced.
49. Further, the Applicant must establish a storm event of violent wind and
heavy rain not merely rain continuing over a number of days.
50. In short, I am not satisfied that the Applicant has established that the
damage to the windows in unit 8 was caused by an insured event as defined
in the policy. Rather, I am persuaded from the material and the photographs
that on the balance of probabilities the damage to the windows was caused
by the cracked and broken render which has allowed water to enter the
building when there was rain and this has caused the damage.
51. I accept that this was not the visible state of the building at the time of
inspection in March 2008. However, over four years passed since that
inspection and the time the Applicant says the damage occurred. The
obvious inference is the render deteriorated during this time. The Applicant
has adduced no persuasive evidence that a storm event as defined
happened in August 2012 that caused the render to crack or deteriorate.
52. PS does not actually comment on the cause of the damage to unit 8 just the
cause of the damage to unit 10. He does however confirm that there was
cracked and deteriorated render work which was not there in 2008.
Case No: 319623 Determination Page 12 of 12
53. PS infers that this is the responsibility of the Body Corporate but even if I
were to accept this was the case, this does not disentitle the FSP to rely on
the policy exclusion that it will not pay for loss and damage caused by
gradual deterioration whoever is responsible for the upkeep of the render.
54. RS also said that damage may have also been caused by inadequate
flashing and sealant around the windows. This opinion is not rebutted by PS
as he said they were obscured by rendercoat. I accept therefore that the
FSP can also rely on another policy exclusion to defeat the claim which is
that it does not have to pay for the cost of rectifying faulty or defective
workmanship.
55. The Applicant says that the FSP‟s expert opinions should be disregarded
because they made mistakes in their reports. I note the errors but I do not
accept that the errors make the reports totally without credit. The totality of
the reports together with the photographs persuades me of the correctness
of the experts‟ view even acknowledging the mistakes.
56. As for the oral advice given by PS to the Applicant that the time that has
elapsed between the damage and the inspection is such that there is
difficulty in making a determination about the cause of the damage, even if I
were to accept this oral submission, I only have to make a finding on the
balance of probabilities. I accept that the experts engaged by the FSP have
the requisite expertise to comment on the subject matter even if their
inspection is not contemporaneous with the claimed loss or event that
caused the loss.
Determination
57. On the basis of the available information and for the reasons stated, I
determine that the FSP is entitled to deny the Applicant‟s claim for rectifying
the disputed damage to unit 8.