Denial of fire damage claim to air conditioning condenser unit under wear and tear exclusion
Summary
The applicant claimed for an air conditioning condenser unit he said was damaged by fire, and the FSP denied it as wear and tear. AFCA accepted the assessor and consultant evidence that the damage was caused by deteriorated copper piping and found the FSP entitled to deny the claim.
The dominant or effective cause of the damage was age-related deterioration, which falls within the wear and tear exclusion even if a fire did occur.
Subjects and remedies
home or building damageno remedy
Text of the determination
Case No: 318550 Determination Page 1 of 6
Case number: 318550
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of claim
20 September 2013
Background
1. This Determination follows the review of a Recommendation issued on
behalf of the Financial Ombudsman Service (FOS) on 7 August 2013. The
Recommendation was rejected by the Applicant.
2. The Applicant held a home building and contents insurance policy with the
Financial Services Provider (FSP), which was current at the time of the loss.
3. On 17 January 2013, the Applicant lodged a claim under the policy for fire
damage to a refrigerated air conditioning condenser unit attached to the side
of his home which occurred in early January.
4. The FSP declined the claim on the basis that the damage was not caused by
fire or any other event insured under the policy, but was due to wear and
tear and maintenance issues.
5. The Applicant disputes the FSP’s decision to decline the claim and seeks
indemnity for the damage to the air conditioning unit.
Summary of Applicant’ s position
6. The Applicant has been assisted by his son in relation to this dispute. For the
purposes of this Determination, submissions made by the Applicant’s son
will be treated as having been made by the Applicant.
7. The Applicant says that:
on a warm day in early January, he and his wife were at home with the
air conditioning turned on;
he heard a strange, loud noise coming from the side of the house and
when he went outside he saw that the air conditioning unit was on fire,
with flames rising into the air; and
he managed to put out the fire with water from the garden hose,
thereby preventing damage to any other part of the house.
Determination
Case No: 318550 Determination Page 2 of 6
8. The Applicant disputes the FSP’s position that there was no fire and that
what he perceived to be smoke was in fact refrigerant escaping from the air
conditioning unit. The Applicant says that he and his wife saw actual flames
coming from the unit. He says that it is possible that his quick actions in
putting out the fire have resulted in there being little to no evidence of fire
damage and therefore he is being punished for doing the right thing. He says
that the FSP has effectively accused him and his wife of not telling the truth.
9. The Applicant says the FSP is relying on technicalities to deny his claim. The
Applicant has obtaine d a report from his own consultants (“W”) which
supports his position that the air conditioning unit was damaged by a fire.
Accordingly, he should be entitled to indemnity under the policy.
10. The Applicant seeks reimbursement for the costs he has incurred in
purchasing a replacement air conditioning unit.
Summary of FSP’s position
11. The FSP says that the onus rests with the Applicant to establish, on the
balance of probabilities, that the claimed damage was caused by fire or by
another event insured under the policy. The FSP does not believe that the
Applicant has been able to establish this.
12. The FSP relies on reports from its assessor (“CS”) and its consultant (“AR”)
who each found that there was no evidence of fire damage to the air
conditioning unit. This is supported by the available photographic evidence.
In contrast, the report prepared by the Applicant’s consultant (W) is brief and
is not supported by photographic evidence.
13. The FSP says that it has also assessed whether the Applicant’s claim falls
under th e cover for damage to electric motors. However, AR’s report
confirmed that there was no evidence of fusion to the motor and in any
event, the age of the motor meant that it would fall outside the scope of
cover.
14. Further, the reports obtained by the FSP ha ve confirmed that the damage
arose due to wear and tear. The terms of the Applicant’s policy clearly state
that there is no cover for loss or damage arising from:
wear and tear; or
mechanical, structural, electrical, electronic or other failure or
breakdown.
15. The FSP says that it has not alleged that the Applicant has provided false
information. Its decision to deny the claim is based on the reports provided
by its assessor and external consultant regarding the cause of the damage
to the air conditioning unit.
Case No: 318550 Determination Page 3 of 6
Issue
16. Whether the FSP is entitled to deny the Applicant’s claim.
Reasons for decision
17. I am satisfied that a full exchange of information has taken place between
the parties and that each party has had an opportunity to address any issues
raised therein.
18. The primary issue in dispute between the parties is whether the damage to
the Applicant’s air conditioning unit was caused by the insured event of fire.
Evidence as to cause of damage
19. The Applicant says that he and his wife heard a loud bang and saw the air
conditioning unit on fire with flames rising into the air. The FSP’s file records
state that, when he lodged the claim on behalf of his father, the Applicant’s
son described the air conditioning unit as being “on fire”.
20. Following lodgement of the App licant’s claim, the FSP appointed an
assessor (CS) to inspect the damaged air conditioning unit. CS attended the
property on 23 January 2013 and reported that:
the Applicant had an old York split system air conditioner. The claimed
damage was to the external compressor component;
the Applicant had reported seeing smoke coming out of the unit, which
he had hosed down as a precaution;
a visual inspection found no evidence of smoke or fire damage to the
casing, motor or fan of the air conditioning unit and this was confirmed
by a review of photographs of the damage; and
a specialist should be engaged to confirm the cause of damage.
21. In accordance with the assessor’s recommendation, the FSP appointed a
consultant (“AR”) to confirm the cause of the damage. AR insp ected the air
conditioning unit and provided a brief report dated 6 February 2013 which
stated that his inspection had revealed a gas leak in the condenser coil in
the unit. AR found that there was no fusion evident and concluded that the
damage to the unit was due to wear and tear. AR noted that the repair of the
unit was not recommended as applying heat to the old pipework would just
create more damage and leaks, while removing the condenser would cause
the pipework to crack.
22. The FSP subsequently sought further clarification from AR in relation to the
basis on which he had determined that the damage to the air conditioner unit
had been caused by wear and tear. In response AR advised that:
Case No: 318550 Determination Page 4 of 6
the Applicant’s air conditioning unit was assessed to be between 25
and 30 years old. A good life expectancy for similar air conditioning
units is around 15 years and anything beyond that is exceptional;
units of this kind should be serviced by an authorised technician every
12 months and the owner should make sure that the filters are cleaned
regularly between servicing;
the condenser coil leakage could have been caused by a number of
factors such as wear and tear on the system, a build up of
contamination over 25 years and vibrations of the unit over time. AR
considered that the main reason for the damage was likely to be wear
and tear due to the walls of the pipe work carrying the gas becoming
thinner and rupturing as the unit aged, or fracturing due to the vibration
of the unit;
the main signs of wear and tear on the A pplicant’s unit were rust on
particular components, build up of dust, corrosion of the condenser fins
and wearing of copper piping (which caused the copper to become
fragile, resulting in the pipe cracking and the unit losing refrigerant);
there were no signs of fire damage to the unit. The damage consisted
of deterioration of the copper piping, which had resulted in the
refrigerant leaking out under pressure and caused the unit to fail under
low pressure and shut off. The refrigerant leaking from the coil of the air
conditioner at high pressure would have looked a lot like a cloud of
smoke to the untrained eye;
when the Applicant dowsed the unit with water from the hose, this
would have done more harm than good, either by contaminating the
system or causing electrical burnout. However, AR had subsequently
tested the system and confirmed that, as the fan and compressor were
running, there was no burnout evident; and
the coil fins of the system condenser had a dark stain, which showed
where the refrigerant had leaked out. The pictures also show the
excessive build up of dirt and grime in the unit.
23. AR confirmed that, in summary:
there was no sign of induced voltage to the input or primary mains and
therefore no electrical damage was evident;
there were no signs of motor burnout – both motors were connected
and functioning; and
there were no signs of fire damage, only evidence that the refrigerant
had leaked via a ruptured gas line.
24. The Applicant has provided a copy of an invoice from his repairer (“W”)
dated 18 February 2013, for the replacement of the damaged air
conditioning unit. The invoices states that:
“Upon inspection of your existing ... reverse cycle ducted system unit we
found the unit to be beyond reliable repair due fire damage causing electrical
fus ion”.
Case No: 318550 Determination Page 5 of 6
25. The Applicant says that W’s invoice supports his position that the damage to
the air conditioning unit was caused by fire.
Analysis of evidence
26. The Applicant says that the damage to the air conditioning unit was caused
by fire, on the basis that he observed flames coming from the unit at the time
the damage occurred. He says that the reference to “fire damage” in W’s
invoice provides further evidence in support of his position.
27. On the other hand, the FSP says that inspections by its assessor (CS) and
consultant (AR) did not identify any fire damage, and AR’s report attributes
the damage to a gas leak in the condenser coil of the unit resulting from
deterioration of the copper piping.
28. The courts have determined that in order to identify whether particular
damage is covered by a policy of insurance, it is necessary to establish the
proximate cause of the damage. This is generally done by determining the
dominant or effective cause of the damage.
29. I have carefully reviewed the evidence provided by both parties, including
the photographs of the air conditioning unit taken by the FSP’s assessor
(CS) and consultant (AR), which show both the interior and exterior of the
unit.
30. I consider that AR’s report (together with his subsequent email) provides a
logical and consistent explanation of the underlying factors which caused the
leak in the gas condenser coil, being the deterioration of the copper piping
due to the age of the unit.
31. I note that both CS and AR inspected the unit closely for the purpose of
investigating the cause of damage, and stated that they did not observe any
evidence of fire damage. AR also confirmed that there was no evidence of
fusion or motor burnout, and the motors had been tested and were
functioning properly despite the incident.
32. The i nvoice prepared by the Applicant’s repairer (W) refers to the air
conditioning unit as having sustained “fire damage causing electrical fusion”.
Accordingly, W’s statement is clearly inconsistent with the conclusions
reached by CS and AR in relation to the cause of the damage.
33. W’s invoice does not include any further information regarding the basis on
which he reached his view, nor does it include any photographs of the
damage which would support his conclusion. This is perhaps not surprising,
as it appears from the information provided that the primary purpose of W’s
attendance at the Applicant’s property was to quote on the replacement of
the air conditioning unit, rather than to carry out a detailed investigation into
the cause of the damage.
34. Having considered all of the available evidence, I consider that it is
appropriate to rely on AR’s report in determining the cause of the damage. It
Case No: 318550 Determination Page 6 of 6
is clear from his report that AR has conducted a thorough inspection of the
air conditioning unit, carried out tests to confirm whether there has been any
damage to the motors and given detailed consideration to the factors giving
rise to the damage observed. Further, I have inspected the available
photographs and consider that they provide support for AR’s conclusions.
35. Accordingly, I am satisfied, on the balance of probabilities, that the
underlying cause of damage to the air conditioning unit was the deterioration
in the copper piping of the gas condenser coil over the life of the unit which
results in a gas leak. I note AS’s comments that it is usual for copper piping
to deteriorate over time given the stresses to which it is subject, which is
particularly relevant given the age of the Applicant’s unit.
Application of policy
36. The Applicant’s policy contains general exclusions for loss or damage
caused by:
wear and tear, rust, deterioration or corrosion; or
mechanical, structural, electrical, electronic or other failure or
breakdown (other than damage caused by electric current to an electric
motor if the motor is less than ten years old and is in a piece of fixed
domestic equipment forming part of the insured building).
37. Given my findings that the underlying cause of damage was the deterioration
in the copper piping of the gas condenser unit, I consider that the claimed
damage falls within the exclusion for wear and tear. Even if the primary
cause of the damage were considered to be mechanical, structural,
electrical, electronic or other failure or breakdown, it would be excluded
under the policy as the motor was more than ten years old.
38. I note that the Applicant’s policy provides cover for loss or damage caused
by “fire (burning with flames)”. However, even if a fire did occur as a result of
the relevant incident, where the underlying cause of the damage was the
deterioration of the copper piping, the exclusion for wear and tear would still
apply.
Determination
39. On the basis of the available information I determine that the FSP is entitled
to deny the Applicant’s claim.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.