Text of the determination
Case No: 312122 Determination Page 1 of 8
Case number: 312122
General Insurance - Domestic Insurance - Home Contents - FSP Decision -
Denial of claim
23 July 2013
Background
1. The Applicants held a home building insurance policy with the Financial
Services Provider (FSP) which was current at the time of the loss. The policy
covered the Applicants‟ home for a sum insured of $416,200.
2. On 24 September 2012 the Applicants lodged a claim with the FSP in
relation to large cracks in the walls of two bedrooms and a hallway which
they had discovered on or around 20 September 2012. The Applicants
advised that the cracks extended all the way through the double brick wall to
the outside of the house.
3. The FSP declined the claim on the basis that:
the Applicants had failed to establish that the damage to their property was
caused by storm, escape of liquid or any other event insured under the
policy; and
the damage was caused by events excluded by the policy, such as ground
movement and gradual deterioration.
4. The Applicants dispute the FSP‟s denial of their claim .
Summary of Applicants ’ position
5. The Applicants say that the crack in the wall of their property has arisen as a
result of events which fall within the insured event of “Escape of Liquid”
under the policy.
6. The Applicants say that the crack developed because the single downpipe at
the property overflowed during a period of severe rain in early 2011, causing
all the rain water from one side of the roof to flow directly into the soil
between the house and a retaining wall. This occurred directly above a
footing. The Applicants have provided average rainfall data from the Bureau
of Meteorology which indicates that there was unusually high rainfall in 2011,
particularly during March and April.
Determination
Case No: 312122 Determination Page 2 of 8
7. The Applicants say that, following the drainpipe overflowing in early 2011,
they investigated and rectified the drainage issue (at their own cost) so that
water from the downpipe now drains into the street. The Applicants have
also arranged for the installation of additional downpipes. However, when
the soil dried out in 2012, a large crack appeared at the front of the house
next to the downpipe, which worsened over a period of approximately 2
weeks.
8. The Applicants do not agree that the flow of water from the drainpipe
occurred over a period of time when they could reasonably be expected to
be aware of the issue (which would result in the damage falling within a
specific excl usion under the insured event “Escape of Liquid”). The
Applicants say that they acted immediately to address the issue as soon as
they became aware of it.
9. The Applicants accept that reliance on a single downpipe for drainage could
be considered to be a „structural or design fault‟ for the purpose of the policy,
however, they dispute that they could reasonably have been aware of this
fault prior to policy inception. The Applicants say that the inspection report
they obtained before purchasing the property did not refer to this issue and it
only became apparent following heavy rainfall in 2011. In any event, they
have not sought indemnity for rectification of the deficiencies in the drainage
at the property, but for the resulting damage only.
10. The Applicants accept that, prior to the claimed damage becoming apparent,
there were smaller cracks throughout the house which are a usual
consequence of the property having been constructed on mildly reactive
clay. These cracks were listed on the pre-purchase inspection report and
have not worsened since the roof and guttering was replaced in 2008.
However, the Applicants submit that the existing minor cracks are cosmetic
only and therefore can be differentiated from the claimed damage which is
major structural damage and arises from a completely separate issue. The
Applicants have obtained an engineer‟s report which supports this.
11. The Applicants seek indemnity under the policy for $18,600, being the
estimated cost of building works to underpin the property in order to stabilise
the front of the house, and to repair cosmetic damage to internal walls.
Summary of FSP’s position
12. The FSP says that the policy is a defined events policy that is subject to
exclusions and does not provide cover for all types of risks. The Applicants
bear the onus of establishing that the damage was caused by a risk insured
against under the policy. The FSP says that, based on the available
evidence, the Applicants have not established this.
13. The FSP relies on the various reports provided by its assessors and
engineers as to the cause of the wall cracks, in order to decline the
Applicants‟ claim. The FSP considers that information contained in the report
Case No: 312122 Determination Page 3 of 8
of the Applicants‟ engineer and the pre -purchase inspection report, provides
further support for its findings as to the cause of the damage.
14. Specifically, the FSP says that the cracking was caused by movement of the
foundations of the house resulting from changes in the moisture conditions
due to factors such as seasonal weather variations, poor drainage and the
proximity of trees which extract water from the soil.
15. Accordingly, the FSP says that the cracks in the walls of the Applicants‟
property were not caused by:
a single insured event of storm (although the FSP accepts that the expert
evidence indicates that changes in weather conditions was a contributing
factor); and
the insured event of liquid escaping suddenly and unexpectedly, as the
escape of liquid from the drainpipe was a gradual process occurring over a
period of time.
16. Further, the FSP says that policy does not provide cover for a fault that
existed before the loss or damage occurred.
17. Accordingly, the FSP says that it is entitled to deny the Applicants‟ claim.
Issue
18. Whether the FSP is entitled to deny the Applicants‟ claim in accordance with
the terms of the policy.
Reasons for decision
19. As advised to the parties, the Service has considered it appropriate to
expedite this dispute in accordance with the Operational Guidelines to the
Service‟s Terms of Reference, due to the circumstances of the dispute.
Accordingly, this dispute has not been the subject of a Recommendation and
has proceeded directly to Determination.
20. I am satisfied that a full exchange of information has taken place between
each party and that each party has had the opportunity to address any
issues raised therein.
21. The Applicants‟ policy is a defined events policy which does not provide
cover for all forms of risk to their home. The cover provided in relation to
each defined event is subject to both specific and general exclusions.
22. The onus is on the Applicants to establish, on the balance of probabilities,
that they have suffered a loss caused by a risk insured against under the
policy. This is known as a prima facie claim. If such a claim is established,
the onus shifts to the FSP to show, on the balance of probabilities, that the
claim falls within an exclusion under the policy.
Case No: 312122 Determination Page 4 of 8
Terms of policy
23. The Applicants say that the claimed damage arose as a result of rainwater
flowing from a drainpipe directly into the soil between the house and a
retaining wall, which damaged the footing underneath, resulting in cracks
developing in the walls.
24. The policy provides cover for “loss or damage to the building caused by a
storm”, including loss or damage caused by a landslide or subsidence which
occurs within 72 hours of, and directly because of a storm.
25. The Applicants have provided data from the Bureau of Meteorology which
indicates that heavy rainfall occurred in 2011, particularly during the months
of March and April. However, the Applicants have not identified a specific
storm event which they say caused the claimed damage. Further, the
damage did not become apparent until more than a year after the periods of
heavy rainfall referred to by the Applicants. Accordingly, I do not consider
that the Applicants have established that the damage falls within the insured
event of “Storm” for the purposes of the policy.
26. However, the primary insured event on which the Applicants base their claim
is the insured event of “Escape of Liquid”, which covers loss or damage
caused by:
“ liquid leaking, overflowing or bursting from ... any drain, fixed pipes, roof
gutters or guttering and rainwater downpipe s, drainage and sewage systems”
27. Under this insured event, there is a specific exclusion for:
“ wear and tear, or loss or damage by the escape of liquid occurring as a result
of a gradual process of leaking, splashing, dripping or overflowing over a
period of time when you could reasonably be expected to be aware of this
condition ”
28. The insured event of “Escape of Liquid” is also subject to general exclusions
under the policy for damage that is caused by, arises from or i nvolves:
ground movement, being “erosion, vibration, subsidence, landslip,
mudslide, collapse, shrinkage or any other earth movement”, other than
landslide or subsidence which is specifically covered under the insured
events of storm, flood, earthquake and tsunami or explosion;
the roots of trees, shrubs or plants, other than where roots block or
damage drains or pipes, thereby causing liquid to leak or overflow from
them;
wear, tear, rust, fading, rising damp, mould, mildew, corrosion, rot, action
of light or gradual deterioration;
a defect, structural fault or design fault that the insured knew about (or
should reasonably have known about) and did not fix before the loss or
damage occurred (eg if there are signs that a defect previously caused
damage, any later claim for damage arising from this defect will not be
paid); and
Case No: 312122 Determination Page 5 of 8
the insured failing to take reasonable care of the building, failing to keep
the building well maintained and in good condition, or failing to fix faults
and defects as soon as becomi ng aware of them.
29. In order to determine whether the claimed damage has been caused by the
insured event of “Escape of Liquid” and/or falls within an exclusion under the
policy, I will now consider the expert reports obtained by the parties.
Expert reports
30. Prior to purchasing the property in 2008, the Applicants obtained an
inspection report from a building consultant (“JB”). In his report dated 19
February 2008, JB stated that:
the walls generally had numerous cracks, none of which would be
structurally detrimental to the building, as most were minor and the larger
ones did not warrant concern but should be monitored;
damaged guttering could be the worst offender for increasing movement
problems in the future if neglected;
there was rising damp in the internal walls, consistent with the age and
type of construction of the building; and
the property was generally serviceable but rising damp would be an
ongoing problem.
31. Following lodgement of the Applicants‟ claim, the FSP appointed an
assessor (“MB”) to inspect the property. In her report dated 27 September
2012, MB stated that:
extreme cracking was present on the northern wall of bedroom 1,
extending throughout the double brick rendered wall. The female Applicant
advised that this crack had only appeared recently and had since
expanded in both length and width. The female Applicant advised that this
area had previously been subject to rising damp, but additional sub floor
ventilation and downpipes had been installed to rectify this;
cracks were also present on the western and eastern walls of bedroom 1
and bedroom 2, which in each case appeared to be recent and extended
through the double brick wall; and
there was evidence of past attempts to repair cracks, which the female
Applicant advised related to cosmetic cracks which were present when the
Applicants purchased the house and had opened and closed over the
intervening four years. There was also evidence of attempted repairs
where the rendered veranda end had moved away from the house outside
bedroom 1.
32. MB recommended that the FSP engage a structural engineer to inspect the
property and determine the cause of the damage.
Case No: 312122 Determination Page 6 of 8
33. Prior to the inspection by the FSP‟s e ngineer, the Applicants received a
report from their own engineer (“JE”). In his report dated 26 September
2012, JE stated that:
the north corner at the front of the house was sinking, resulting in
extensive cracking to all of the walls in this area. The most probable cause
of this was water entering the soil at the footings due to inadequate
drainage. The steep roof meant that the gutter would overflow during
periods of heavy rainfall and overload the single downpipe at the end of
the gutter. Many of the joints in the downpipe were likely to have a high
pressure leak into the footings. Further, it appeared likely that the wall
footings at the north corner may be at the same level as the footpath
surface. The retaining wall at this area showed cracking whic h indicated
that this wall was failing and therefore removing support for these footings;
the cracks on the south-west side of the house were relatively old but
showed that the south wall had been moving, probably as a result of the
overflow from the inadequate roof gutter;
the cracks at the rear of the house indicated movement of the wall
footings, caused by there being no formed drain from the downpipe which
discharged directly onto the concrete slab abutting the rear of the house.
This would result in water entering the wall footings through the joints
between the concrete slab and the house wall.
34. JE‟s report outlined suggested remedial action to address the cause of the
damage. JE subsequently provided a further report dated 3 October 2012 in
which he revised his conclusions following fuller consideration of his earlier
observations. In his further report, JE stated that:
the reason that the structural damage occurred only recently (and not
during the previous 80 years) was because of water entering the soil
around and under the house footings, due to the inadequate drainage
system which was put in place when the roof and guttering were replaced
(which had occurred relatively recently); and
given the extent of the damage, he now considered that the front and side
walls and the verandah of the house should be underpinned.
35. The FSP engaged an engineer (“DK”) who appointed a structural
engineering firm (“SE”) to inspect the property and report on the cause of the
damage. DK reviewed SE‟s report, JE‟s report and JB‟s pre -purchase
inspection report, and prepared a report dated 23 October 2012, which
states that:
the house was likely to be supported on high level masonry footings
founded on natural clay soils, which are considered to be moderately
reactive;
there were pre-existing cracks, as shown by evidence of previous
attempted repairs and referred to in JB‟s pre -inspection report;
Case No: 312122 Determination Page 7 of 8
in the absence of further information, the internal and external cracking to
the masonry brick walls may be attributed to one or more of the following,
rather than a single defined event:
- foundation movement, due to changes in the moisture condition of the
foundation soil such as from seasonal weather variations, poor
drainage and the proximity of trees, resulting in shrinkage or swelling of
the foundation soil; and
- general building movement, and lack of articulation (jointing);
it was recommended that additional drainage be installed, and further
investigations be undertaken to determine whether underpinning was
appropriate; and
due to the apparent reactive nature of the foundation material, it was likely
that further cracking to brittle finishes would occur in the future as a result
of general foundational movements from seasonal changes in the moisture
condition of the foundations. The installation of expansion joints in the
walls may reduce the extent of such cracking.
36. In addition, SE‟s report dated 23 October 2012, on which DK relied, noted
that:
based on the relevant Australian Standard, most of the cracks would be
classifie d as “slight” to “negligible”, although there were isolated cracks to
the walls in bedroom 1 which would be classified as “moderate”; and
while cracking was normal in the case of houses on high level brick
footings, this may have been exacerbated due to the installation of
additional subfloor ventilation, repair of the single downpipe, maturation of
the trees along the front of the verandah and the relatively drier weather
experienced recently, which could all contribute to a reduced level of
moisture in the soils.
Analysis
37. Each of the experts engaged to report on the cause of the cracking damage,
including the Applicants‟ own engineer (JE), concluded that the damage was
caused by movement of the footings at the property caused by changes in
the moisture content of the foundation soils. DK also identified the lack of
expansion joints as contributing to the cracks in the walls.
38. The Applicant‟s engineer (JE) identified the changes in moisture content as
arising solely due to the inadequate drainage system. Th e FSP‟s engineers,
(DK and SSE) while accepting that the inadequate drainage system played a
role, also identified other factors (such as seasonal weather variations and
nearby trees) as contributing to the changes in moisture content.
39. The courts have determined that in order to identify whether particular
damage is covered by a policy of insurance, it is necessary to establish the
proximate cause of the damage. This is generally done by determining the
dominant or effective cause of the damage.
Case No: 312122 Determination Page 8 of 8
40. Based on my review of the available evidence, I am not satisfied, on the
balance of probabilities, that the sole cause of the increased moisture
content in the foundation soils of the Applicants‟ property was the inadequate
drainage system. I note that:
it is widely accepted that factors such as changes in weather conditions
and the presence of trees affects the moisture content of foundation soils,
particularly in the case of properties constructed on reactive clay soils; and
the presence of pre-existing cracking to the Applicants‟ property shows
that the property was susceptible to ground movement (even if it is
accepted that the claimed damage is more severe than that which had
occurred in the past).
41. Accordingly, I consider, on the balance of probabilities, that the damage to
the Applicants‟ property was caused by earth movement resulting from
several concurrent factors, including (but not limited to) the inadequate
drainage system.
42. The Applicants‟ policy contains a general exclusion for earth movement,
other than where this results from the insured events of storm, flood,
earthquake and tsunami or explosion.
43. It is settled law that where there is more than one concurrent cause of a loss
and one cause is subject to cover and the other is not, the insurer is not
liable for the loss (refer Wayne Tank and Pump Co v Employers Liability
Assurance Corporation [1974] QB 57) (the “Wayne Tank principle”).
44. Accordingly, even if I accept that the leaking/overflowing of water from the
drainage system contributed to the cracking damage to the walls of the
property, the FSP would be entitled to deny the claim in reliance on the
Wayne Tank principle, given that there were other concurrent causes of the
loss which are excluded under the policy.
45. For the reasons outlined above, I consider that the FSP is not liable for the
Applicants‟ claim for cracking damage to the walls of their property.
Determination
46. On the basis of the available information, I determine that the FSP is entitled
to deny liability for the Applicants‟ claim.