Determination 305274

Denial of kitchen floor damage after burst pipe; granny flat damage in dispute

FirmFinancial Firm (Unknown - Insurer)
Decided2013-09-23
ProductGeneral Insurance · Home building and contents
OutcomeFor the complainant in part
Amount awarded$1,265
Non-financial loss—
Amount claimed$21,578
SourceAFCA PDF

Summary

The applicants claimed $21,578 for water damage after a burst pipe, including kitchen floor tiles and granny flat ceiling. AFCA denied the kitchen floor claim as caused by faulty installation, but ordered repair or $1,265 cash for the granny flat with interest, and a sub-floor reassessment.

The proximate cause of the floor tile damage was faulty installation, not the burst pipe, but the granny flat water ingress had two interdependent causes and so was covered.

Issues

Subjects and remedies

home or building damagepay claimpay interestreassess claimrepair or rectify

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Case No: 305274 Determination Page 1 of 10 Case number: 305274 General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of claim 19 August 2013 Background 1. This dispute follows the review of a Recommendation issued on behalf of the Service on 23 May 2013. The Recommendation was rejected by the Applicants. 2. The Applicants held a home insurance policy with the Financial Services Provider (FSP), which was current at the time of the loss. 3. On 3 November 2011 the Applicants lodged a claim with the FSP for water damage to their kitchen from a burst pipe under the sink in the island bench. The Applicants reported that water had also leaked through the tiles and the kitchen sub-floor, damaging the ceiling of the granny flat below. 4. The FSP accepted the Applicants’ claim for damage to the kitchen cabinets and bench top, but denied the Applicants’ claim for damage to the kitchen flooring. The FSP relied on its engineer’s report to conclude that the damage to the flooring was pre-existing and caused by poor installation of the kitchen tiles, not by water flooding from the burst pipe. 5. The Applicants dispute the FSP’s decision to decline their claim for damage to the kitchen floor and the ceiling of the granny flat. The Applicants say that this damage was caused by the burst pipe and therefore should be indemnified under the policy. 6. The Applicants seek indemnity for the cost of repairs totalling $21,578 to restore the home to its condition prior to the burst pipe. Of this amount, $13,663.50 relates to repair of the disputed damage. Summary of Applicants ’ position 7. The Applicants say that:  the inspection report which they obtained before they purchased the property in September 2011 does not refer to any existing damage to the kitchen tiles; Determination Case No: 305274 Determination Page 2 of 10  there was one cracked tile before the pipe burst. The water inundation from the burst pipe caused three additional tiles in the flooded area to crack and the grout deteriorated over the course of the following few weeks;  the building consultant engaged by them to inspect the damage confirmed that there was significant damage to the floor tiles, with cracked, lifting and loose tiles and damaged grout;  their building consultant also confirmed that the base particleboard flooring in the kitchen was significantly swollen, consistent with heavy water spillage to the kitchen floor area; and  since the kitchen floor dried out, there has been no further cracking damage to the kitchen tiles. Further, there is no cracking damage to the tiles in other parts of the home, including high traffic areas. If the cracking was due to the quality of the tiles, further damage would be expected throughout the tiled area. 8. The Applicants say that, given the above, it is reasonable to conclude that the damage to the tiles was caused by inundation from the burst water pipe. The Applicants say that the FSP has misinterpreted its engineer’s report to deny this part of their claim. 9. The Applicants note that the relevant building standards do not require kitchen floor tiles to be waterproofed, and say that therefore their floor should not be considered to be faulty. 10. The Applicants believe the FSP does not want to indemnify them for the damage to the kitchen tiles as this would involve replacing all the tiles in the area. Summary of FSP’s position 11. The FSP says that the Applicants’ policy is a defined events policy which provides cover for events including “liquid escaping suddenly and unexpectedly from a fixed pipe.” However, the policy clearly states tha t it does not cover damage or loss caused by, arising from or involving wear and tear and/or structural failure or breakdown. 12. The FSP acknowledges that water from the burst pipe leaked through the tiles. However, the FSP says that the damage to the tiles was not caused by water from the burst pipe but is due to wear and tear and a structural defect. The FSP says that the tiles have not cracked as a direct result of the water but have become unstable due to poor installation and the Applicants’ failure to rectify this and maintain the area. 13. The FSP relies on the reports of its assessor, its builder and its engineer in support of its position. Case No: 305274 Determination Page 3 of 10 14. Accordingly, the FSP says that it is entitled to rely on the terms of the policy to deny the Applicants’ claim for dam age to the kitchen floor and the ceiling of the granny flat. Issue 15. Whether the FSP is entitled to deny the Applicants’ claim for damage to the kitchen floor and the ceiling of the granny flat. Reasons for decision 16. I am satisfied that there has been a full exchange of material between the parties and that each party has had an opportunity to address the issues raised therein. 17. There is an onus on an insured to establish on the balance of probabilities that a claim fits the definition of an insured event. This is known as a prima facie claim. Should this onus be discharged, it is then the responsibility of the insurer to establish, on the balance of probabilities, that an exclusion applies. 18. The issue in dispute between the parties concerns the cause of the damage to the kitchen flooring and the resulting damage to the granny flat when water leaked through the kitchen tiles. Cause of damage to kitchen flooring Evidence regarding damage 19. Following lodgement of the Applicants’ claim, the FSP appointed an assessor (“SW”) to assess the damage. SW attended the property on 27 November 2011 and reported that:  there was swelling around the base of the island bench and three tiles in front of the bench were “spongy” and loose;  there was evidence of previous patching of the kitchen floor tiles with a grout/silicon mixture, with at least 20 patches to the grouting observed throughout the kitchen, dining and entry areas. The grout throughout these areas was loose and some tiles were lifting, while others were cracked;  in SW’s view, the damage to the tiles was caused by either building movement or defective installation. However, SW recommended that a building report be obtained to confirm the cause of the damage and identify whether there was any structural damage to the kitchen flooring which had caused the tiles to become spongy; and  the Applicants indicated that they were seeking to have all the tiles replaced. However, given that the problem appeared to be pre-existing, Case No: 305274 Determination Page 4 of 10 SW considered that the repair should provide for re-gluing of the loose tiles only. 20. SW’s report attached photographs which show swelling of the laminate on the island bench and the kickboards in front of the sink, patches to the grouting in a number of places, tiles lifting in the dining area (unrelated to the burst pipe) and two cracked tiles (one of which was in front of the fridge and has been acknowledged by the Applicants as pre-existing). 21. To assist the FSP’s investigations, the Applicants provided a copy of a pre- purchase inspection report dated 24 June 2011 prepared by a building consultant (“JP”) before the Applicants purchased the property. I have reviewed the pre-purchase inspection report and note that:  it is stated to comply with the relevant Australian Standard and appears to be reasonably comprehensive;  the property is classified for the purposes of the report as having a high level of major and minor defects, compared to equivalent properties of a similar age;  the grouting of the bathroom shower tiles is noted as having deteriorated and the shower as needing to be retiled and re-grouted; and  no issues are identified in relation to the tiles or grouting in the kitchen, dining and entry areas. 22. As recommended by the FSP’s initial assessor, SW , the FSP appointed a builder (“AJ”) to re port on the cause of the damage and provide a scope of works. AJ’s report dated 14 December 2011 states that:  the male Applicant advised that when the pipe burst, the water was only on the floor for about twenty minutes;  the damage to the kitchen floor tiles appeared to be historic and to have occurred over an extended period of time, as the grouting had been loose and missing for a long time. The missing grout allowed water from general mopping to penetrate the floor, causing the majority of the damage to the substrate, which in turn caused the tiles to become loose. Tiles were lifting in both the kitchen and dining room; and  some of the tiles on the opposite side of the sink bench were cracked, indicating that the recent leak was not a contributing factor to the damage to the kitchen floor. 23. On 23 January 2012, the FSP advised the Applicants that, based on the reports of SW and AJ, it considered that the damage to the tiles was the result of wear over time. The Applicants queried this on the basis that the only tiles which were spongy were those around the island bench where the leak occurred, which was inconsistent with there being a long -term maintenance issue. After reviewing the pre-inspection report provided by the Applicants, the FSP agreed to arrange for a second opinion as to the cause Case No: 305274 Determination Page 5 of 10 of the damage. However, the FSP subsequently decided not to seek a second opinion and instead recommended that the Applicants obtain their own report. 24. Accordingly, the Applicants engaged a building consultant ( “TI” ) who inspected the property on 12 June 2012 and prepared a brief report. In his report, TI states that:  he inspected the kitchen and dining room for water damage and observed significant damage to the floor tiles with cracked, lifting and loose tiles and damaged grout;  the base particleboard flooring had swollen significantly and suffered water damage consistent with heavy water spillage in the kitchen floor area from the island bench to the surrounding floor tiles; and  at the time of inspection, electronic moisture readings in the damaged areas were low. 25. The photographs provided with TI’s report show cracks to two tiles and several other tiles lifting. 26. Given the apparent conflict between TI’s report and AJ’s report, the FSP appointed an engineer (“JH”) to re port on the cause of the damage. JH inspected the property on 9 August 2012 and reported that:  when the kitchen was renovated three years earlier and the new floor tiles were laid, an entire section of the floor was cut out and replaced with new particlebo ard sheeting. The new tiles were then “direct fixed” to the surface of the new particleboard floor with an adhesive, but without a secondary underlay material to cushion the surface of the new particleboard. This caused the thinner tiles to fit unevenly against each other in several locations;  the lack of a secondary underlay material allowed the tiles to flex and move under pedestrian traffic. This isolated the movement of the particleboard floor away from the new floor tiles and caused the cement grout between the tiles to crack and become dislodged, to the point where in many areas there was no grout left at all. Grout was also missing in areas of the kitchen and dining area which were not affected by the burst pipe;  the missing grout allowed the flooding water from the burst pipe to get under the tiles and drain into the ceiling of the granny flat. The male Applicant stated that, after the water on the surface of the tiles was mopped up and the leak repaired, water continued to be “squeezed” out from beside the tiles in the areas where the grout was missing. In JH’s view, this indicated that once water got under the tiles, the weight of pedestrian traffic was sufficient to force it back out of the holes formed by the missing grout;  the pattern of cracks in the tile in front of the refrigerator (which the Applicants acknowledged predated the burst pipe) was indicative of sub-floor movement not having been isolated by an underlay material; Case No: 305274 Determination Page 6 of 10  the additional three tiles which cracked since the flooding event were all in a straight line running parallel to the kitchen sink cupboards, just in front of the cupboards. The cracks in these tiles were consistent with the location of a large timber beam supporting the floor frame. The upper level of the house was “bowing” slightly over the top of this beam, which had placed the particleboard in a slightly bent and tensile state, thereby contributing to the floor tiles in this area becoming stressed;  the fact that the floor became saturated due to the burst pipe had little to do with the cracks in the tiles, as timber does not lose its strength when it gets wet. The problem was the absence of an appropriate underlay material to compensate for any movement of the floor frame. In addition, if the grout joints had been fully intact and the edges of the tiles sealed, this would have prevented the water getting under the floor tiles. Floor tiles are designed to get wet without cracking or losing grout and will normally only crack if subjected to bending pressure or movement from an unstable or semi-rigid base, which had occurred in this case. Analysis of evidence 27. As outlined above, the FSP’s builder (AJ), the Applicant’s building consultant (TI) and the FSP’s engineer (JH) have all expressed differing views as to the cause of the damage to the kitchen floor tiles. I have reviewed the reports provided by each consultant. Of the three reports, I consider that JH’s is the most persuasive for the following reasons:  JH’s report provides a detailed step by step analysis of how the damage to the tiled flooring occurred, supported by photographs illustrating the issues identified in his report. JH specifically identifies the factors which he considers caused or contributed to the relevant damage and offers cogent explanations for his conclusions. By contrast, the reports prepared by AJ and TI state their findings relatively briefly, without offering much additional insight as to the reasons behind them;  as both a qualified engineer and a registered master builder, JH is appropriately qualified to assess the cause of this type of damage. While it appears from their reports that AJ and TI are both registered builders, it is not clear what other qualifications they hold; and  based on the reports and photographs provided, it appears that J H carried out a more detailed inspection than either AJ or TI. The photographs included in JH’s report indicate that he pulled back the edge of the carpet abutting the kitchen area to determine how the floor tiles had been installed. JH also removed the light fittings in the downstairs granny flat so that he could visually inspect the underneath of the particleboard flooring. 28. Accordingly, I consider that the FSP is entitled to rely on JH’s findings in assessing the cause of the damage to the Applicants’ kit chen floor. Case No: 305274 Determination Page 7 of 10 29. On my reading of his report, JH determined that the underlying cause of the damage to the kitchen tiles was the fact that they had been incorrectly installed when renovations to the kitchen were carried out three years earlier. Specifically, J H considered that the tiler’s failure to place some form of underlay material on top of the new particleboard meant that the tile floor flexed and moved in isolation from the particleboard. This caused the grout to crack and dislodge. JH considered that the floor tiles located above the large beam supporting the floor frame had been subject to particular stress, as the upper level of the house had “bowed” slightly over the beam. 30. While JH acknowledges in his report that water leaked through the floor tiles, he states that the fact that the kitchen floor became saturated due to the burst pipe had little to do with the cracks in the tiles. 31. I accept that the Applicants consider that JH’s conclusions are inconsistent with the pre-inspection purchase report and their observations of the damage to the property. The Applicants also say that JH did not adequately investigate the condition of the particleboard. However, I note that:  the absence of any reference to damage to the kitchen tiles in the pre - purchase inspection report is not conclusive, as such damage could have been missed, or may have arisen subsequently (as in the case of the single cracked tile which the Applicants acknowledge predated the burst pipe);  both the FSP’s assessor (SW) and builder (AJ) , observed issues with the grout and lifting of tiles in areas of the kitchen and dining room floor which would not have been affected by the burst pipe. These issues are evident from the photographs taken by the various consultants;  the state of the grout and the attempted patch repairs (as shown in the photographs) supports JH’s view that the grout has deteriorated over a period of time, rather than over a shorter period following the burst pipe, particularly as the Applicants have confirmed that the water was mopped up within about twenty minutes. The fact that the relevant building standards do not require the kitchen floor to be “waterproofed” does not alter the fact that the proper installation of a tiled floor requires adequate grouting which will remain in place for a reasonable period of time (subject only to normal deterioration);  it may be that the cracks to the tiles have occurred first in areas which are subject to the greatest pressure or movement – as noted by JH, the susceptibility of tiles in particular areas may be affected not only by the incidence of heavy traffic, but also by matters such as the presence of structural beams. This may explain why no damage has been observed to other areas of high traffic; and  while JH did not conduct intrusive investigations of the particleboard, based on his report it is reasonable to assume that he observed the “bowing” of the tiled surface. As noted above, JH’s investigations of the particleboard were more thorough than those of the other consultants. Case No: 305274 Determination Page 8 of 10 Application of policy 32. The Applicants’ policy provides cover for loss or damage “caused by” certain defined events including “liquid escaping suddenly and unexpectedly from a water main, drain [or] fixed pipe”. 33. The courts have determined that in order to identify whether particular damage is caused by a specified event, it is necessary to establish the proximate cause of the damage. This is generally done by determining the dominant or effective cause of the damage. 34. For the reasons outlined above, I consider that JH’s report establishes that the proximate cause of the damage to the kitchen tiles was poor installation, which led to subsequent movement and cracking of the tiles. JH’s report establishes that water inundation from the burst pipe was not the sole (or even an additional) proximate cause of this damage. 35. Accordingly, the damage was not “caused by” the defined event of liquid escaping from the pipe and therefore is not subject to cover under the policy. 36. Given this, the operation of the policy exclusions is not directly relevant to the issue of damage to the kitchen floor. However, for completeness, I note that I do not consider that the faulty installation of the tiles falls within any of the general exclusions under the policy. The relevant policy exclusions apply to loss or damage caused by, arising from or involving:  wear and tear, rust, deterioration or corrosion;  mechanical, structural, electrical, electronic or other failure or breakdown; or  an unreasonable failure by the insured to properly maintain or repair the insured property. 37. I consider that damage resulting from a failure by the tiler to install an appropriate underlay is qualitatively different from damage caused by “wear and tear” or “deterioration” which occurs in the ordinary course of events. Further, I consider that the issues associated with the faulty installation of the tiles do not fall within the ordinary meaning of “structural ... or other failure or breakdown”. Finally, I do not consider that the Applicants should be considered to have unreasonably failed to properly maintain or repair their property, given that they did not own the house at the time the tiles were installed, and the available evidence (including the pre-purchase inspection report) indicates that the issues with the tiles had not previously come to their attention. Damage to granny flat 38. The parties do not dispute that the flooding water from the burst pipe entered under the kitchen tiles, into the kitchen sub-floor and through the light fitting in the granny flat below. Case No: 305274 Determination Page 9 of 10 39. On the basis of the available evidence, I consider that the water from the burst pipe was able to enter under the kitchen tiles because the grouting between the tiles had deteriorated as a result of movement of the tiles caused by inadequate installation. 40. Accordingly, the influx of water into the granny flat can be considered to have two proximate causes (the faulty installation and the burst pipe) which operated interdependently to allow the water to enter. 41. The inundation by water from a burst pipe falls within a defined event under the policy. However, the faulty installation of the tiles does not fall within this or any of the other defined events covered under the policy. Further, for the reasons outlined in paragraph 37 above, I do not consider that the faulty installation falls within any of the exclusions under the policy. Accordingly, the policy is silent as to the effect of damage caused by faulty installation. 42. In circumstances where there are two proximate causes of damage, one of which is within the scope of cover and the other of which is not expressly excluded, the courts have determined that the insured is entitled to recover. 43. Accordingly, I consider that the Applicants are entitled to indemnity under the policy for the damage to the granny flat. 44. I note that conflicting views have been expressed as to the extent of this damage. JH’s report stated that the water which entered th e granny flat was not sufficient to cause “any real damage” to the plasterboard ceiling lining of the granny flat. JH also considered that the ceiling itself, along with the cornice and the plaster setting, all remained in a reasonable and serviceable condition. 45. However, the Applicants have provided photographs taken on the day the pipe burst, which clearly show water markings on the ceiling of the granny flat. The FSP’s assessor (SW) and builder (AJ) also accepted that there was damage to the ceiling and t he light fitting, and AJ’s quote includes amounts for a painter, plasterer and electrician which appear to relate to the repair of damage to the granny flat. 46. Based on this, I accept that there was some cosmetic damage to the ceiling of the granny flat and that the light fitting was also damaged. Given that AJ observed and quoted on the damage, I consider that the FSP should either arrange for the repair of the damage or cash settle the Applicants for $1,265, being the amount allowed in AJ’s quote for the p ainting, plastering and electrical works. 47. I consider that the cause of the damage remained unclear until the FSP received the engineer’s report. Accordingly, I consider that the FSP should be required to pay interest on any cash settlement amount from 7 September 2012 (being 7 days after the date the report was received) until the date of payment. Case No: 305274 Determination Page 10 of 10 Damage to sub-floor 48. In the same manner as for the granny flat, the water ingress to the timber sub-floor occurred due to the deterioration of the grouting between the tiles (as the result of poor installation) and the water flooding from the burst pipe. Accordingly, for the reasons outlined above, any resulting damage should be covered under the policy. 49. When the Applicants’ building consultant (TI) inspected the kitchen in June 2012, he observed that the particleboard flooring had swollen significantly and suffered water damage. However, it is not clear whether TI observed the particleboard directly. 50. When the FSP’s engineer (JH) attended the property in August 2 012, he inspected certain areas of the particleboard flooring by removing the downstairs light fittings, and observed no evidence of any water staining or water marks to indicate that it had ever become wet. Accordingly, JH concluded that the particleboard floor and the timber floor frame supporting the upper level of the house had not sustained any water damage. 51. In light of the conflicting observations of TI and JH, I consider that the FSP should re-assess the damage to the timber sub-floor and, if necessary, arrange for the repair of the sub-floor or cash settle the Applicants for the cost of the repairs. Determination 52. On the basis of the available information I determine that:  the FSP is entitled to deny the Applicants’ claim for damage to the kitchen floor;  the FSP should arrange for the repair of the damage to the ceiling, cornices and light fitting of the granny flat or cash settle the Applicants for the amount of $1,265 in respect of such damage. The FSP should pay interest on any cash settlement amount calculated in accordance with section 57 of the Insurance Contracts Act 1984 (Cth), from 7 September 2012 until the date of payment; and  within 21 days of each party accepting this Determination, the FSP should re-assess the damage to the timber sub-floor and if necessary, arrange for the repair of the sub-floor or cash settle the Applicants for the cost of such repairs, within 14 days of receiving the assessment.