Text of the determination
Case No: 305274 Determination Page 1 of 10
Case number: 305274
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of claim
19 August 2013
Background
1. This dispute follows the review of a Recommendation issued on behalf of the
Service on 23 May 2013. The Recommendation was rejected by the
Applicants.
2. The Applicants held a home insurance policy with the Financial Services
Provider (FSP), which was current at the time of the loss.
3. On 3 November 2011 the Applicants lodged a claim with the FSP for water
damage to their kitchen from a burst pipe under the sink in the island bench.
The Applicants reported that water had also leaked through the tiles and the
kitchen sub-floor, damaging the ceiling of the granny flat below.
4. The FSP accepted the Applicants’ claim for damage to the kitchen cabinets
and bench top, but denied the Applicants’ claim for damage to the kitchen
flooring. The FSP relied on its engineer’s report to conclude that the damage
to the flooring was pre-existing and caused by poor installation of the kitchen
tiles, not by water flooding from the burst pipe.
5. The Applicants dispute the FSP’s decision to decline their claim for damage
to the kitchen floor and the ceiling of the granny flat. The Applicants say that
this damage was caused by the burst pipe and therefore should be
indemnified under the policy.
6. The Applicants seek indemnity for the cost of repairs totalling $21,578 to
restore the home to its condition prior to the burst pipe. Of this amount,
$13,663.50 relates to repair of the disputed damage.
Summary of Applicants ’ position
7. The Applicants say that:
the inspection report which they obtained before they purchased the
property in September 2011 does not refer to any existing damage to
the kitchen tiles;
Determination
Case No: 305274 Determination Page 2 of 10
there was one cracked tile before the pipe burst. The water inundation
from the burst pipe caused three additional tiles in the flooded area to
crack and the grout deteriorated over the course of the following few
weeks;
the building consultant engaged by them to inspect the damage
confirmed that there was significant damage to the floor tiles, with
cracked, lifting and loose tiles and damaged grout;
their building consultant also confirmed that the base particleboard
flooring in the kitchen was significantly swollen, consistent with heavy
water spillage to the kitchen floor area; and
since the kitchen floor dried out, there has been no further cracking
damage to the kitchen tiles. Further, there is no cracking damage to the
tiles in other parts of the home, including high traffic areas. If the
cracking was due to the quality of the tiles, further damage would be
expected throughout the tiled area.
8. The Applicants say that, given the above, it is reasonable to conclude that
the damage to the tiles was caused by inundation from the burst water pipe.
The Applicants say that the FSP has misinterpreted its engineer’s report to
deny this part of their claim.
9. The Applicants note that the relevant building standards do not require
kitchen floor tiles to be waterproofed, and say that therefore their floor should
not be considered to be faulty.
10. The Applicants believe the FSP does not want to indemnify them for the
damage to the kitchen tiles as this would involve replacing all the tiles in the
area.
Summary of FSP’s position
11. The FSP says that the Applicants’ policy is a defined events policy which
provides cover for events including “liquid escaping suddenly and
unexpectedly from a fixed pipe.” However, the policy clearly states tha t it
does not cover damage or loss caused by, arising from or involving wear and
tear and/or structural failure or breakdown.
12. The FSP acknowledges that water from the burst pipe leaked through the
tiles. However, the FSP says that the damage to the tiles was not caused by
water from the burst pipe but is due to wear and tear and a structural defect.
The FSP says that the tiles have not cracked as a direct result of the water
but have become unstable due to poor installation and the Applicants’ failure
to rectify this and maintain the area.
13. The FSP relies on the reports of its assessor, its builder and its engineer in
support of its position.
Case No: 305274 Determination Page 3 of 10
14. Accordingly, the FSP says that it is entitled to rely on the terms of the policy
to deny the Applicants’ claim for dam age to the kitchen floor and the ceiling
of the granny flat.
Issue
15. Whether the FSP is entitled to deny the Applicants’ claim for damage to the
kitchen floor and the ceiling of the granny flat.
Reasons for decision
16. I am satisfied that there has been a full exchange of material between the
parties and that each party has had an opportunity to address the issues
raised therein.
17. There is an onus on an insured to establish on the balance of probabilities
that a claim fits the definition of an insured event. This is known as a prima
facie claim. Should this onus be discharged, it is then the responsibility of the
insurer to establish, on the balance of probabilities, that an exclusion applies.
18. The issue in dispute between the parties concerns the cause of the damage
to the kitchen flooring and the resulting damage to the granny flat when
water leaked through the kitchen tiles.
Cause of damage to kitchen flooring
Evidence regarding damage
19. Following lodgement of the Applicants’ claim, the FSP appointed an
assessor (“SW”) to assess the damage. SW attended the property on 27
November 2011 and reported that:
there was swelling around the base of the island bench and three tiles
in front of the bench were “spongy” and loose;
there was evidence of previous patching of the kitchen floor tiles with a
grout/silicon mixture, with at least 20 patches to the grouting observed
throughout the kitchen, dining and entry areas. The grout throughout
these areas was loose and some tiles were lifting, while others were
cracked;
in SW’s view, the damage to the tiles was caused by either building
movement or defective installation. However, SW recommended that a
building report be obtained to confirm the cause of the damage and
identify whether there was any structural damage to the kitchen flooring
which had caused the tiles to become spongy; and
the Applicants indicated that they were seeking to have all the tiles
replaced. However, given that the problem appeared to be pre-existing,
Case No: 305274 Determination Page 4 of 10
SW considered that the repair should provide for re-gluing of the loose
tiles only.
20. SW’s report attached photographs which show swelling of the laminate on
the island bench and the kickboards in front of the sink, patches to the
grouting in a number of places, tiles lifting in the dining area (unrelated to the
burst pipe) and two cracked tiles (one of which was in front of the fridge and
has been acknowledged by the Applicants as pre-existing).
21. To assist the FSP’s investigations, the Applicants provided a copy of a pre-
purchase inspection report dated 24 June 2011 prepared by a building
consultant (“JP”) before the Applicants purchased the property. I have
reviewed the pre-purchase inspection report and note that:
it is stated to comply with the relevant Australian Standard and appears
to be reasonably comprehensive;
the property is classified for the purposes of the report as having a high
level of major and minor defects, compared to equivalent properties of
a similar age;
the grouting of the bathroom shower tiles is noted as having
deteriorated and the shower as needing to be retiled and re-grouted;
and
no issues are identified in relation to the tiles or grouting in the kitchen,
dining and entry areas.
22. As recommended by the FSP’s initial assessor, SW , the FSP appointed a
builder (“AJ”) to re port on the cause of the damage and provide a scope of
works. AJ’s report dated 14 December 2011 states that:
the male Applicant advised that when the pipe burst, the water was
only on the floor for about twenty minutes;
the damage to the kitchen floor tiles appeared to be historic and to
have occurred over an extended period of time, as the grouting had
been loose and missing for a long time. The missing grout allowed
water from general mopping to penetrate the floor, causing the majority
of the damage to the substrate, which in turn caused the tiles to
become loose. Tiles were lifting in both the kitchen and dining room;
and
some of the tiles on the opposite side of the sink bench were cracked,
indicating that the recent leak was not a contributing factor to the
damage to the kitchen floor.
23. On 23 January 2012, the FSP advised the Applicants that, based on the
reports of SW and AJ, it considered that the damage to the tiles was the
result of wear over time. The Applicants queried this on the basis that the
only tiles which were spongy were those around the island bench where the
leak occurred, which was inconsistent with there being a long -term
maintenance issue. After reviewing the pre-inspection report provided by the
Applicants, the FSP agreed to arrange for a second opinion as to the cause
Case No: 305274 Determination Page 5 of 10
of the damage. However, the FSP subsequently decided not to seek a
second opinion and instead recommended that the Applicants obtain their
own report.
24. Accordingly, the Applicants engaged a building consultant ( “TI” ) who
inspected the property on 12 June 2012 and prepared a brief report. In his
report, TI states that:
he inspected the kitchen and dining room for water damage and
observed significant damage to the floor tiles with cracked, lifting and
loose tiles and damaged grout;
the base particleboard flooring had swollen significantly and suffered
water damage consistent with heavy water spillage in the kitchen floor
area from the island bench to the surrounding floor tiles; and
at the time of inspection, electronic moisture readings in the damaged
areas were low.
25. The photographs provided with TI’s report show cracks to two tiles and
several other tiles lifting.
26. Given the apparent conflict between TI’s report and AJ’s report, the FSP
appointed an engineer (“JH”) to re port on the cause of the damage. JH
inspected the property on 9 August 2012 and reported that:
when the kitchen was renovated three years earlier and the new floor
tiles were laid, an entire section of the floor was cut out and replaced
with new particlebo ard sheeting. The new tiles were then “direct fixed”
to the surface of the new particleboard floor with an adhesive, but
without a secondary underlay material to cushion the surface of the
new particleboard. This caused the thinner tiles to fit unevenly against
each other in several locations;
the lack of a secondary underlay material allowed the tiles to flex and
move under pedestrian traffic. This isolated the movement of the
particleboard floor away from the new floor tiles and caused the cement
grout between the tiles to crack and become dislodged, to the point
where in many areas there was no grout left at all. Grout was also
missing in areas of the kitchen and dining area which were not affected
by the burst pipe;
the missing grout allowed the flooding water from the burst pipe to get
under the tiles and drain into the ceiling of the granny flat. The male
Applicant stated that, after the water on the surface of the tiles was
mopped up and the leak repaired, water continued to be “squeezed”
out from beside the tiles in the areas where the grout was missing. In
JH’s view, this indicated that once water got under the tiles, the weight
of pedestrian traffic was sufficient to force it back out of the holes
formed by the missing grout;
the pattern of cracks in the tile in front of the refrigerator (which the
Applicants acknowledged predated the burst pipe) was indicative of
sub-floor movement not having been isolated by an underlay material;
Case No: 305274 Determination Page 6 of 10
the additional three tiles which cracked since the flooding event were all
in a straight line running parallel to the kitchen sink cupboards, just in
front of the cupboards. The cracks in these tiles were consistent with
the location of a large timber beam supporting the floor frame. The
upper level of the house was “bowing” slightly over the top of this
beam, which had placed the particleboard in a slightly bent and tensile
state, thereby contributing to the floor tiles in this area becoming
stressed;
the fact that the floor became saturated due to the burst pipe had little
to do with the cracks in the tiles, as timber does not lose its strength
when it gets wet. The problem was the absence of an appropriate
underlay material to compensate for any movement of the floor frame.
In addition, if the grout joints had been fully intact and the edges of the
tiles sealed, this would have prevented the water getting under the floor
tiles. Floor tiles are designed to get wet without cracking or losing grout
and will normally only crack if subjected to bending pressure or
movement from an unstable or semi-rigid base, which had occurred in
this case.
Analysis of evidence
27. As outlined above, the FSP’s builder (AJ), the Applicant’s building consultant
(TI) and the FSP’s engineer (JH) have all expressed differing views as to the
cause of the damage to the kitchen floor tiles. I have reviewed the reports
provided by each consultant. Of the three reports, I consider that JH’s is the
most persuasive for the following reasons:
JH’s report provides a detailed step by step analysis of how the
damage to the tiled flooring occurred, supported by photographs
illustrating the issues identified in his report. JH specifically identifies
the factors which he considers caused or contributed to the relevant
damage and offers cogent explanations for his conclusions. By
contrast, the reports prepared by AJ and TI state their findings relatively
briefly, without offering much additional insight as to the reasons behind
them;
as both a qualified engineer and a registered master builder, JH is
appropriately qualified to assess the cause of this type of damage.
While it appears from their reports that AJ and TI are both registered
builders, it is not clear what other qualifications they hold; and
based on the reports and photographs provided, it appears that J H
carried out a more detailed inspection than either AJ or TI. The
photographs included in JH’s report indicate that he pulled back the
edge of the carpet abutting the kitchen area to determine how the floor
tiles had been installed. JH also removed the light fittings in the
downstairs granny flat so that he could visually inspect the underneath
of the particleboard flooring.
28. Accordingly, I consider that the FSP is entitled to rely on JH’s findings in
assessing the cause of the damage to the Applicants’ kit chen floor.
Case No: 305274 Determination Page 7 of 10
29. On my reading of his report, JH determined that the underlying cause of the
damage to the kitchen tiles was the fact that they had been incorrectly
installed when renovations to the kitchen were carried out three years
earlier. Specifically, J H considered that the tiler’s failure to place some form
of underlay material on top of the new particleboard meant that the tile floor
flexed and moved in isolation from the particleboard. This caused the grout
to crack and dislodge. JH considered that the floor tiles located above the
large beam supporting the floor frame had been subject to particular stress,
as the upper level of the house had “bowed” slightly over the beam.
30. While JH acknowledges in his report that water leaked through the floor tiles,
he states that the fact that the kitchen floor became saturated due to the
burst pipe had little to do with the cracks in the tiles.
31. I accept that the Applicants consider that JH’s conclusions are inconsistent
with the pre-inspection purchase report and their observations of the
damage to the property. The Applicants also say that JH did not adequately
investigate the condition of the particleboard. However, I note that:
the absence of any reference to damage to the kitchen tiles in the pre -
purchase inspection report is not conclusive, as such damage could
have been missed, or may have arisen subsequently (as in the case of
the single cracked tile which the Applicants acknowledge predated the
burst pipe);
both the FSP’s assessor (SW) and builder (AJ) , observed issues with
the grout and lifting of tiles in areas of the kitchen and dining room floor
which would not have been affected by the burst pipe. These issues
are evident from the photographs taken by the various consultants;
the state of the grout and the attempted patch repairs (as shown in the
photographs) supports JH’s view that the grout has deteriorated over a
period of time, rather than over a shorter period following the burst
pipe, particularly as the Applicants have confirmed that the water was
mopped up within about twenty minutes. The fact that the relevant
building standards do not require the kitchen floor to be “waterproofed”
does not alter the fact that the proper installation of a tiled floor requires
adequate grouting which will remain in place for a reasonable period of
time (subject only to normal deterioration);
it may be that the cracks to the tiles have occurred first in areas which
are subject to the greatest pressure or movement – as noted by JH, the
susceptibility of tiles in particular areas may be affected not only by the
incidence of heavy traffic, but also by matters such as the presence of
structural beams. This may explain why no damage has been observed
to other areas of high traffic; and
while JH did not conduct intrusive investigations of the particleboard,
based on his report it is reasonable to assume that he observed the
“bowing” of the tiled surface. As noted above, JH’s investigations of the
particleboard were more thorough than those of the other consultants.
Case No: 305274 Determination Page 8 of 10
Application of policy
32. The Applicants’ policy provides cover for loss or damage “caused by” certain
defined events including “liquid escaping suddenly and unexpectedly from a
water main, drain [or] fixed pipe”.
33. The courts have determined that in order to identify whether particular
damage is caused by a specified event, it is necessary to establish the
proximate cause of the damage. This is generally done by determining the
dominant or effective cause of the damage.
34. For the reasons outlined above, I consider that JH’s report establishes that
the proximate cause of the damage to the kitchen tiles was poor installation,
which led to subsequent movement and cracking of the tiles. JH’s report
establishes that water inundation from the burst pipe was not the sole (or
even an additional) proximate cause of this damage.
35. Accordingly, the damage was not “caused by” the defined event of liquid
escaping from the pipe and therefore is not subject to cover under the policy.
36. Given this, the operation of the policy exclusions is not directly relevant to
the issue of damage to the kitchen floor. However, for completeness, I note
that I do not consider that the faulty installation of the tiles falls within any of
the general exclusions under the policy. The relevant policy exclusions apply
to loss or damage caused by, arising from or involving:
wear and tear, rust, deterioration or corrosion;
mechanical, structural, electrical, electronic or other failure or
breakdown; or
an unreasonable failure by the insured to properly maintain or repair
the insured property.
37. I consider that damage resulting from a failure by the tiler to install an
appropriate underlay is qualitatively different from damage caused by “wear
and tear” or “deterioration” which occurs in the ordinary course of events.
Further, I consider that the issues associated with the faulty installation of
the tiles do not fall within the ordinary meaning of “structural ... or other
failure or breakdown”. Finally, I do not consider that the Applicants should be
considered to have unreasonably failed to properly maintain or repair their
property, given that they did not own the house at the time the tiles were
installed, and the available evidence (including the pre-purchase inspection
report) indicates that the issues with the tiles had not previously come to
their attention.
Damage to granny flat
38. The parties do not dispute that the flooding water from the burst pipe entered
under the kitchen tiles, into the kitchen sub-floor and through the light fitting
in the granny flat below.
Case No: 305274 Determination Page 9 of 10
39. On the basis of the available evidence, I consider that the water from the
burst pipe was able to enter under the kitchen tiles because the grouting
between the tiles had deteriorated as a result of movement of the tiles
caused by inadequate installation.
40. Accordingly, the influx of water into the granny flat can be considered to
have two proximate causes (the faulty installation and the burst pipe) which
operated interdependently to allow the water to enter.
41. The inundation by water from a burst pipe falls within a defined event under
the policy. However, the faulty installation of the tiles does not fall within this
or any of the other defined events covered under the policy. Further, for the
reasons outlined in paragraph 37 above, I do not consider that the faulty
installation falls within any of the exclusions under the policy. Accordingly,
the policy is silent as to the effect of damage caused by faulty installation.
42. In circumstances where there are two proximate causes of damage, one of
which is within the scope of cover and the other of which is not expressly
excluded, the courts have determined that the insured is entitled to recover.
43. Accordingly, I consider that the Applicants are entitled to indemnity under the
policy for the damage to the granny flat.
44. I note that conflicting views have been expressed as to the extent of this
damage. JH’s report stated that the water which entered th e granny flat was
not sufficient to cause “any real damage” to the plasterboard ceiling lining of
the granny flat. JH also considered that the ceiling itself, along with the
cornice and the plaster setting, all remained in a reasonable and serviceable
condition.
45. However, the Applicants have provided photographs taken on the day the
pipe burst, which clearly show water markings on the ceiling of the granny
flat. The FSP’s assessor (SW) and builder (AJ) also accepted that there was
damage to the ceiling and t he light fitting, and AJ’s quote includes amounts
for a painter, plasterer and electrician which appear to relate to the repair of
damage to the granny flat.
46. Based on this, I accept that there was some cosmetic damage to the ceiling
of the granny flat and that the light fitting was also damaged. Given that AJ
observed and quoted on the damage, I consider that the FSP should either
arrange for the repair of the damage or cash settle the Applicants for $1,265,
being the amount allowed in AJ’s quote for the p ainting, plastering and
electrical works.
47. I consider that the cause of the damage remained unclear until the FSP
received the engineer’s report. Accordingly, I consider that the FSP should
be required to pay interest on any cash settlement amount from
7 September 2012 (being 7 days after the date the report was received) until
the date of payment.
Case No: 305274 Determination Page 10 of 10
Damage to sub-floor
48. In the same manner as for the granny flat, the water ingress to the timber
sub-floor occurred due to the deterioration of the grouting between the tiles
(as the result of poor installation) and the water flooding from the burst pipe.
Accordingly, for the reasons outlined above, any resulting damage should be
covered under the policy.
49. When the Applicants’ building consultant (TI) inspected the kitchen in June
2012, he observed that the particleboard flooring had swollen significantly
and suffered water damage. However, it is not clear whether TI observed the
particleboard directly.
50. When the FSP’s engineer (JH) attended the property in August 2 012, he
inspected certain areas of the particleboard flooring by removing the
downstairs light fittings, and observed no evidence of any water staining or
water marks to indicate that it had ever become wet. Accordingly, JH
concluded that the particleboard floor and the timber floor frame supporting
the upper level of the house had not sustained any water damage.
51. In light of the conflicting observations of TI and JH, I consider that the FSP
should re-assess the damage to the timber sub-floor and, if necessary,
arrange for the repair of the sub-floor or cash settle the Applicants for the
cost of the repairs.
Determination
52. On the basis of the available information I determine that:
the FSP is entitled to deny the Applicants’ claim for damage to the
kitchen floor;
the FSP should arrange for the repair of the damage to the ceiling,
cornices and light fitting of the granny flat or cash settle the Applicants
for the amount of $1,265 in respect of such damage. The FSP should
pay interest on any cash settlement amount calculated in accordance
with section 57 of the Insurance Contracts Act 1984 (Cth), from 7
September 2012 until the date of payment; and
within 21 days of each party accepting this Determination, the FSP
should re-assess the damage to the timber sub-floor and if necessary,
arrange for the repair of the sub-floor or cash settle the Applicants for
the cost of such repairs, within 14 days of receiving the assessment.