Home / Financial Firm (Unknown - Insurer) / Determination 286534
Determination 286534
Denial of claim (storm damage)
Summary
The applicant claimed $87,000 for storm damage to a garage, balcony and house after a February 2011 storm. AFCA found the FSP entitled to deny the balance of the claim after it had accepted repairs to a bedroom ceiling.
Expert evidence showed the damage resulted from long-term roof maintenance, deterioration and faulty workmanship rather than the storm, engaging the policy exclusions.
Issues
- Claim denial primary · not upheld“the Panel determines the FSP is entitled to deny the balance of the Applicant's claim.”
Subjects and remedies
home or building damagenatural disasterno remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Case No: 286534 Determination Page 1 of 8
Case number: 286534
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of claim
26 March 2013
Background
1. The Applicant held an insurance policy with the Financial Services Provider
(FSP) for an eighty year old residential property. The relevant period of
insurance operated for twelve months beginning from 11 March 2010. During
this period, the building was insured for a sum up to $1,800,000 and
contents for $400,000. The majority of claims were subject to a $500 excess.
2. The Applicant completed a claim form on 11 May 2011 for damage that
occurred on 4 February 2011 following a severe storm. The following
description was provided:
“Water damage & tree damage (tree fell onto garage) to garage structure and
minor damage to contents in garage.”
3. The Applicant included a quotation with the claim form in the sum of
$87,000. The scope of works included storm damage to the garage,
balcony/carport and main building.
4. Upon engaging an engineer (E) and a roof plumbing & tiling expert (RC) to
review the claim, the FSP decided to accept the cost of repairs to the internal
damage to the ceiling within bedroom 2 but deny the balance. The Applicant
has disputed this decision.
Summary of Applicant ’s position
5. The Applicant is represented by his broker. For the sake of convenience,
reference to the Applicant will include his broker.
6. Although there were some maintenance issues with the property, the storms
of February 2011 were of such severity that it was inevitable that his property
would sustain water damage. In this regard, he relies on the following:
The Bureau of Meteorology records which show approximately
112.6mm of rain fell within a 3 day period (4 to 7 February 2011).
A report from a structural and civil engineer (SE).
Determination
Case No: 286534 Determination Page 2 of 8
The fact the property had not sustained damage in the preceding two
years.
7. Given this, the Applicant submits the FSP should account for the damage
that would have inevitably been caused by the storm.
Summary of FSP’s position
8. The FSP relies on the expert evidence of E and RC as well as the following
policy provisions to maintain its position:
“ General Exclusions
These apply to the whole Policy
Unless otherwise stated in the Insurance Schedule, this Policy does not
cover:
1. loss of or damage to Your property which is caused by:
(a) wear, tear, rust, corrosion or gradual deterioration
(b) mechanical breakdown, electrical breakdown, faulty
workmanship, inherent defect, omission or design.”
Issue
9. Whether the FSP is able to rely on the relevant exclusion cla uses to deny
the balance of the Applicant’s claim.
Reasons for Decision
10. As advised by the parties, due to the amount in dispute, the matter has been
referred to the Panel for Determination in line with the Operational
Guidelines to the Service’s Terms of R eference. This dispute has not been
the subject of a FOS Recommendation and has proceeded directly to
Determination.
11. This decision has been made by a Panel consisting of an Ombudsman, a
representative with extensive experience in the insurance industry and a
representative with extensive experience in consumer claims.
12. The FSP is seeking to rely on an exclusion clause and therefore has the
burden of establishing on the balance of probabilities that it applies.
Expert Evidence
13. Both parties have relied upon expert evidence to substantiate their position.
The FSP has relied upon E and RC whereas the Applicant has provided a
report from SE.
Case No: 286534 Determination Page 3 of 8
14. E was engaged to inspect and report on the first floor balcony and rear
garage; it provided a report dated 11 June 2011 that contained photographs
in support and the following of relevance (headings have been placed for
convenience):
Balcony
The damaged balcony is the flat top of a carport that stands over the
side driveway. This area has been tiled with ceramic tiles set out in a
basket weave pattern with mortar jointing.
The balcony is a square area approximately 3m by 3m. The tiled area
is a flat plane that slopes gently to a drain in the rear. The tiles were of
a glazed ceramic type. The whole tiled area however had been covered
by a white plasticised material later found to be “Gripset” Liquid Rubber
Membrane.
The membrane extended up the walls surrounding the tiled area but
much of this had been peeled off. It is quite obvious this membrane had
been applied many years ago.
This membrane has been used on an area that is walked over despite
the manufacturers of “Gripset” warning parties against this. In addition,
it was not meant to be used over glass or a glazed surface.
The reason for the use of the membrane was due to the joints between
the tiles showing signs of distress, with efflorescence oozing from them.
This indicates the substrate under the tiles has broken down and the
waterproofing measures undertaken to the tiled area has been
compromised. This would not have occurred from a single storm,
particularly not a storm on 4 February 2011.
The ceiling under the balcony was both damp and stained, indicating
that a lot of water has flowed onto and through this ceiling for a long
period of time.
Garage
The garage is a massive brick structure with a pitched terracotta roof. A
corner of a parapet around the roof is leaning over and may fall. The
insured claimed this was impacted by a tree in the storm on 4 February
2011. If a branch had been large enough to cause this damage, then it
is reasonable to presume this would have damaged the adjacent fence.
However, this was not the case.
The ceiling has been damaged and is sagging as though it has been
affected by water over a period of time. The hole in the corner looks as
though it has been cut, presumably to let water out.
The roof drains into a box gutter behind the parapet. There is no doubt
that various storms would have overwhelmed the gutter, allowing water
to flow into the ceiling.
The garage appears to be suffering from neglect. Ivy is also growing
inside the garage.
Case No: 286534 Determination Page 4 of 8
The parapet has been damaged but it is unlikely this was caused by a
single event of storm. The brickwork below this corner appears to be
free of cracks but there is a lot of vegetation around there. It is possible
repeated impact from branches may have affected these bricks.
15. Following this, E concluded the following:
“Neither the damage to the tiled balcony nor the garage have been caused by
a single storm event – certainly not the storm on 4 February 2011. Both areas
of damage show long- term characteristics.”
16. RC provided a report dated 27 June 2011. The report was to address the
rainwater ingress into the house, in particular the front and second bedroom,
the carport and the garage. In furtherance of this, he conducted an
inspection of the roof.
17. The Panel does not propose to repeat all of RC’s findings in the body of the
Determination since this has been exchanged with the Applicant. It is
sufficient to reiterate his relevant conclusions regarding these issues:
“ Point 1
Rainwater leakage that has occurred into the front bedroom of the house is
the result of leaking from a chimney Lear Gutter.
The chimney Lear Gutter is in an advanced state of deterioration with
extensive rust hols evidence and as such, all leakage is due entirely to a
longstanding roof maintenance issue.
Point 2
Rainwater leakage is occurring into a second bedroom to the southern side of
the house again around the site of a chimney installation.
Rainwater is leaking from the second chimney due to faulty workmanship that
sees the replacement of the original Lear gutter with a new gutter.
The workmanship involved with the installation of the new gutter is obviously
NOT(original emphasis) the work of a qualified or experienced plumber and
presents as the work of a complete amateur unlicensed person and the
resultant water ingress, is entirely attributable to faulty non-compliant
workmanship issues.
Point 3
Rainwater leakage that is occurring from the ceramic tile balcony of the
carport is the result of a combination of badly rusted box gutters, box gutter
also has NO (original emphasis) effective overflow system and also,
significant deterioration to the waterproofing membrane installed atop the
ceramic tile balcony.
All rainwater ingress that is causing damage to the ceiling of the carport
presents as a obvious roof maintenance issues – NOT (original emphasis)
storm created.
Point 4
Rainwater leakage that is occurring into the garage is again the result of faulty
workmanship in regard to leakage from the box gutter and in the case of
damage to the metal hanging flashing this has been caused by the growth of
Case No: 286534 Determination Page 5 of 8
a tree within the brick parapet wall of the garage, which should not have been
allowed to have occurred.
Point 5
No storm damage or storm created openings to the roof
My inspection of the entire roof to this house, the garage and the ceramic tile
balcony to the carport found NO (original emphasis) evidence of any storm
damage of (sic) storm created openings of any kind.
To the contrary, this house lacks appropriate maintenance works to the roof
for a considerable period of time. It is this lack of proper maintenance and the
faulty w orks that have cause (sic) the leakage issues to this property.”
18. SE’s report of 28 September 2011 contained the following:
Two areas adjacent to the chimneys in the bedrooms exhibited water
damage through the plaster in the ceiling. This is obviously associated
with a leak in the roof cladding.
A similar problem with a leaking roof has occurred in the north-east
corner of the garage.
The balcony over the existing carport has exhibited damage to the
ceiling from excessive water leakage. A visual inspection revealed the
balcony inadequately graded and the applied waterproofing compound
having broken down. The application of this membrane occurred after
the storm according to the owner. Further, the owner stated the balcony
floor had been submerged in 75-100mm of water.
19. Based on the above, SE concluded that:
“Whilst it is probable that the damage has been an ongoing maintenance
problem with roof leakage, the storm in February 2011 has exacerbated the
problem. Roof guttering and downpipes would not be able to accommodate
for storms of significant magnitude and as a result flooding and/or excessive
water leakage has occurred. The amount of damage directly caused by the
storm damage is difficult to quantify at this point in time, but some extent of
damage, to the ce iling has been caused by the storm.”
20. The FSP provided SE ’s report to E who responded in an email dated 11
January 2012 with the following:
“... I see no broad area of disagreement between what I said in my Report and
what [E] has said.
I note that our original instructions ... did not include the main roof of the
house. As a consequence, I did not pay particular attention to the roof or the
interior of the house. ...
From what I can see, the gutters of the house appear to be at least a metre or
more from the external walls and the gutters and downpipes appeared to be in
reasonable order. Even if they overflowed I would not expect that water would
run onto the ceilings of the house. It is possible that a massive rain event like
that which occurred on 4 February 2011 may have overwhelmed flashings
and allowed water to flow inside. I do not think that this is likely mainly
because this house appears to have been very well built in an era and
location where things like the roof drainage were properly designed and built.
Case No: 286534 Determination Page 6 of 8
There have been plenty of heavy rain events since the 1930s and 40s so the
chances of the 4 February storm sending water to a ceiling are not very high.
On the other hand, a leak in the roof cladding (ie a cracked tile), could allow
water to flow in. As you know however, I was not required to access the roof
so I cannot comment on whether there are any cracked tiles. [SE] attributes
the damage he saw to ongoing maintenance, exacerbated by the storm. I do
not think it is at all possible to quantify damage by one cause or the other.
Therefore, for reasons given above, I would attribute all of it to ongoing
maintenance problems – subject to another inspection.”
Consideration of the evidence
21. The substantive argument presented by the Applicant is that regardless of
the condition of the property, the storm event of 4 February 2011 was
significant enough to have resulted in some damage. However, the expert
evidence does not appear to support this.
22. In particular, both reports to the FSP highlight numerous iss ues that appear
to explain the cause and source of the water ingress to various parts of the
property. The Panel will expand on this.
Bedroom 1
23. According to both RC and SE, the water ingress to the house was localised
to bedrooms 1 and 2. As the FSP has accepted the internal repair cost to
bedroom 2, the Panel will limit its review to bedroom 1.
24. In regard to the water ingress to bedroom 1, RC identified that this was due
to the Lear gutter being extensively rusted with rust holes evident. E, by its
own admission in its email dated 11 January 2012, did not pay particular
attention to the roof or interior of the house. This is not surprising given RC
would have been more appropriately placed to opine about this issue.
25. Accordingly, despite E indicating that it was possible for storms to have
resulted in water ingress (although he considered this unlikely), the Panel
prefers to rely upon RC’s opinion as it was based on a visual inspection and
investigation regarding the cause of this water ingress.
26. RC’s explanat ion of the cause of the ingress is supported by photographs
and is reasonable and plausible. In addition, SE’s report does not dispute
these findings. In particular, it is unclear if SE actually inspected the roof as
his report is silent on his observations in this regard. For instance, although
he comments on there being a leak in the roof, he does not expand on how
this leak occurred.
27. Given this, the Panel accepts RC’s evidence about the source of the water
ingress into bedroom 1. In particular, the Panel accepts that the proximate
cause of the leakage to this area would be wear, tear and rust as opposed to
the storm. This is based on the fact it is reasonable to accept that if the Lear
gutter was in good, serviceable condition, it is unlikely water would have
penetrated this part of the home.
Case No: 286534 Determination Page 7 of 8
28. Although SE has provided a broad conclusion stating that the magnitude of
rainfall would have exacerbated and caused resultant flooding, the Panel is
not persuaded by this given he has not considered whether a properly
installed Lear gutter would have avoided the water ingress. In the Panel’s
view, having considered the extensive deterioration and holes as evident in
the photographs, it is more probable than not that this was the cause of the
ingress, not the storm.
29. The FSP is therefore entitled to deny this aspect of the Applicant’s claim.
Carport Balcony
30. In regard to the carport balcony, the Panel is particularly persuaded by E’s
evidence in this regard. E has provided a plausible explanation as to how a
balcony appropriately waterproofed could have this ability compromised and
why this is unlikely to have occurred from the storm. In support of his
conclusion, he referred to the leakage in the ceiling as being evident that this
was occurring for a long period of time.
31. SE’s evidence has not refuted this analysis. Instead, it provides some
corroboration to E’s conclusion given he identified excessive leakage and
inadequate grading.
32. RC also provided further support to E’s position and expanded on this by
identifying that the box gutter has no overflow system, which is a vital
omission.
33. In the light of all of this, the Panel is persuaded that the damage to the
carport balcony was due to gradual deterioration and/or faulty workmanship.
Accordingly, the FSP is entitled to rely on the exclusion clauses associated
with those causes to deny this aspect of the Applicant’s claim.
Garage
34. The Panel is persuaded by RC’s evidence in this regard, particularly given
the following issues he identified:
The inappropriate tree growth causing the hanging flashing, which was
installed as the waterproofing agent to a box gutter, being
compromised.
The inappropriate use of a nail through the box gutter.
The box gutters being in an advanced state of deterioration and
containing no overflow system.
35. This was supported, to an extent, by E as he believed the issues identified in
the garage were long term rather than caused by one event. SE’s report also
appeared to provide some support to the fact that a leak in the roof cladding
occurred although he was not specific as to how the leak occurred.
36. Although SE, in his broad conclusion, stated that the roof guttering and
downpipes would not have been able to accommodate the storm, it is
Case No: 286534 Determination Page 8 of 8
unclear whether he arrived at this conclusion having taken into consideration
the above three issues identified by RC. In this regard, the Panel prefers
RC’s evidence given he has specifically identified the extent of the faulty
workmanship and deteriorated issues which, on the face of them, readily
lead to the conclusion that these factors were the cause of the loss, not the
storm.
37. Accordingly, the Panel accepts the FSP is entitled to deny liability for this
aspect of the Applicant’s loss.
Determination
38. On the basis of the available information the Panel determines the FSP is
entitled to deny the balance of the Applicant’s claim.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.