Text of the determination
Case No: 284846 Determination Page 1 of 10
Case number: 284846
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of Claim
8 August 2012
Background
1. The Applicant held a home building policy with the Financial Services
Provider (FSP) from 28 September 2008. The sum insured for buildings is
$168,000 and the policy has a $250 excess.
2. Prior to this the Applicant held other home building policies with the FSP,
covering the same property, since purchasing the property in May 2001.
However these were cancelled at various times for various reasons,
including non payment, errors made by the FSP and a change of Insured
Name when the Applicant’s partner no longer had a financial interest in the
property.
3. On 1 February 2012 the roof of the property collapsed and walls were
pushed out by the collapsing roof. The Applicant immediately contacted the
FSP to report the incident and arranged for the SES to attend to make the
property safe.
4. The FSP and Applicant arranged for building specialists to attend the
property to provide reports on the cause and extent of damage.
5. As a result of their investigations, the FSP denied the Applicant’s claim
saying there was no evidence of any cause of the roof collapse being
attributable to a defined event of the policy.
6. The Applicant disputes the denial of his claim and says further damage has
occurred at the property since the collapse of the roof due to the FSP’s
inaction.
Summary of Applicant’s position
7. The Applicant says storms passed through the area approximately 2 weeks
prior to the collapse of the roof and he is of the opinion the rain associated
with these storms, has caused the roof to collapse.
8. Reports from two building experts provided by the Applicant indicate the
cement roof tiles have been water logged from these storms and this has
Determination
Case No: 284846 Determination Page 2 of 10
caused the roof to collapse, which supports the Applicant’s view of how the
damage occurred.
9. The Applicant says the reports provided by the FSP from its three experts
are contradictory and inaccurate. He says the FSP has made every atte mpt
to find a reason to deny his claim.
10. The Applicant says he wants his house repaired and he believes the FSP
should honour his claim.
Summary of FSP’s position
11. The FSP says its experts have provided information to suggest there is no
damage to the roof of the Applicant’s property which would suggest any
insured event has caused the collapse.
12. The FSP says its experts have provided advice indicating the roof was in a
poor state of repair, had not been constructed properly and the insulation
installed in the roof may have become water logged over a period of time
which could have contributed to the roof collapsing.
13. The FSP says its experts have advised there is no evidence of any impact
damage, storm damage or termite damage to the roof.
14. As such, the FSP say s it is entitled to deny the Applicant’s claim.
15. Furthermore, it says it arranged for the Applicant’s property to be protected
from further loss as soon as it was able and as soon as it was practicable
after the report of the damage was made to them by the Applicant. It says its
efforts in this regard were hampered given the extent of the collapse which
made the site dangerous and difficult to access to effect protection being put
in place.
16. The FSP relies on the following policy provisions of its Product Disclosure
Statement (PDS):
“ What are you covered for?
This insurance is designed to cover you for loss or damage to your insured
building or contents caused by the listed insured events that occur during the
period of insurance ...”
(Page 2)
“ What you are not covered for
There are certain times when this insurance may not provide cover.
Some events we may not cover include:
Damaged caused by seas or river flood (see Section 1.12).
Damage caused by water seeping or entry of water to your building unless
through an opening caused by the storm or a direct result of it (see
Section 1.12).
Case No: 284846 Determination Page 3 of 10
Damage to your building and/or contents caused by water or another
liquid escaping as the result of a gradual process (see Section 1.7).
...
Wear and tear, depreciation, deterioration, atmospheric condition, mould,
mildew, insects, vermin, action of light, rot or inherent defect (see section
5.0).”
(Page 5)
“ Definitions (The Meaning Of Some Words)
...
“damage” or “damaged” means when an item insured by this policy is
physically harmed but does not include wear and tear .
...
“insured event” means one of the events listed on pages 23 to 31.
...
“properly maintained” means that your building is structurally sound,
secure and in a good state of repair and its roof guttering regularly cleaned.
...
“storm” means violent weather and high winds, sometimes accompanied by
rain, hail or snow including a cyclone, tornado or willy willy.
...
“wear and tear” means damage or a reduction in value through age, ordinary
use or lack of maintenance.”
(Pages 16 to 21)
“ 1.7 Water Or Other Liquid
You are insured for damage to your building and/or your contents caused
when water or another liquid suddenly escapes from:
...
We will not pay if the damage is the result of a gradual process.
For example, we will not pay for damage:
where moisture is seeping through faulty shower recess grouting; or
from condensation or rising damp,
where more damage has occurred over time because the fault was no
[sic] remedied immediately.
...
We will not pay:
to fix a defect in the design or construction of a system;
to repair or replace a defective part; or
if your building has not been properly maintained. ”
(Pages 26 to 28)
“ 1.12 Storm, Rain Or Flash Flood
Case No: 284846 Determination Page 4 of 10
You are insured for damage to your building and/or your contents caused
by storm, rain, or flash flood.
We will not pay for water damage to your building caused by storm or rain
seeping or otherwise entering your building unless the water entered
through an opening in the wall or roof that had been made directly by the
storm or rain or as a direct result of it.
We will not pay for damage to your building caused by water:
penetrating or entering your building because it has not been properly
maintained or as a result of a design fault, structural defect or because of
defective workmanship,
entering your building through an opening in the wall or roof made for
the purpose of alterations, additions, renovation or repair.”
(Page 29)
“ 3.10 Essential Temporary Repairs
If this policy insures your building, you are able to proceed with essential
temporary repairs to your building up to a maximum of $500 after your
building is damaged by an insured event .”
(Page 39)
Issues
17. What caused the roof to collapse.
18. Whether the FSP is entitled to deny the Applicant’s claim.
19. Whether the FSP has based its findings on any factual inaccuracies provided
to it by its experts.
Reasons for decision
20. This decision has been made by a Panel consisting of an Ombudsman, an
industry representative and a consumer representative.
21. The Panel is satisfied there has been a full exchange of material between
the parties and that each party has had the opportunity of clarifying the
issues that arise from the material.
22. As advised to the parties, FOS has considered it appropriate to expedite the
dispute in accordance with the Operational Guidelines to the FOS Terms of
Reference. This dispute has not been the subject of a FOS
Recommendation and has proceeded directly to Determina tion.
23. There is no dispute that the roof of the Applicant’s property has collapsed
and that this collapse occurred on the evening of 1 February 2012.
Case No: 284846 Determination Page 5 of 10
24. At the time of discovering the damage, the Applicant immediately contacted
the SES to attend to make the property safe. He also advised the FSP of the
incident. After not receiving a return call from the FSP, the Applicant again
contacted the FSP on the morning of 2 February 2012. Upon receipt of this
call, the FSP appointed a Loss Adjuster (C) to attend.
25. Based on advice received via a telephone call from C, the FSP agreed to
appoint building engineers to determine the cause of damage. Processes
were also put in place to make the building safe as C advised the FSP the
SES were not able to do so, due to the exte nt of damage and the site being
unsafe.
26. Enquiries made by C indicated a building engineer would need to attend the
site and the use of a cherry picker may be required to provide tarpaulin
covers to the property to protect it from rain, which was expected later that
day (2 February 2012). However, as the weather in the area generally was
considered to be severe around this time, facilitating this request and
obtaining already stretched resources to acquire the necessary tools and
personnel to perform this task, meant protection was not able to be put in
place until 7 February 2012.
27. The Applicant says that as a result of the delay in protecting the property, his
contents contained within the property suffered rain water damage over the
ensuing days. The Panel has considered this and is of the opinion the FSP
did not cause any unnecessary delays in effecting the protection. Likewise,
the Applicant was not able to do anything to protect the property as the site
was inaccessible due to safety reasons.
28. The Applican t’s property was purchased by him in 2001. At the time of
purchase, he was advised by the real estate agent that the property had
been restumped, rewired, had new ceilings, the tile roof had been restored
and the bathroom renovated, among other features. The Applicant provided
a copy of the original sale brochure produced by the real estate agent at the
time of sale which supports his comments.
29. This brochure from the real estate agent details the property as being
constructed around the 1920’s. Opinions pro vided by the FSP’s experts
indicate the building was probably built around the mid to late 1930’s.
Expert Evidence/Opinions
30. The FSP requested the Applicant to provide any expert reports on the cause
of damage if he wished to.
31. The Applicant provided reports from two builders (C and B). The opinions
expressed by both C and B were that the roof had collapsed due to rain
penetrating the cement tiles of the roof during heavy rains approximately two
weeks prior to the collapse, with these cement tiles effectively becoming too
heavy for the roof structure to support.
Case No: 284846 Determination Page 6 of 10
32. Both C and B indicated the roof and wall timbers were in good condition and
there was no indication of termite activity or dry rot present.
33. The FSP also requested that the Applicant supply documenta tion to show
what maintenance he had attended to at the property since purchase.
34. The Applicant provided these documents. They included a quotation for
restumping dated 20 April 2001 (noting repairs to the floor to improve as
practicable and that down pipes should be diverted into soak wells), a
termite inspection dated April 2001 (noting no termite activity), a quotation
for a replacement rear door and sub -frame dated 12 May 2001 (noting the
door was badly out of square necessitating the need to replace the sub-
frame), an invoice to clear a blocked pan line due to tree roots dated 28
February 2005, invoices for the installation of blow-in insulation dated
December 2001 and a quotation for floor sanding dated 29 July 2005. There
is no evidence to show the quotations provided were in fact acted on by the
Applicant.
35. The FSP appointed experts to assess the cause and extent of damage. The
FSP’s appointed technical consultant (M) advised the cause of the collapse
appeared to be due to a number of issues which were:
moisture build up in insulation,
fixings corroded,
ceiling joists end grain fixed to top plate,
ceiling joists not fixed to rafters,
creep of hanging beams disconnecting bracing beam and
angle of struts placing eccentric loading to hanging beams causing
rotation.
36. M added:
“There are many causes for collapses to roofs, in this case the only one that
we could determine was that the insulation is a blow in type and in many
circumstances this blow in insulation builds up a layer of moisture as it settles.
This moisture can increase the levels of bio-corrosion to the ceiling straps
causing a collapse for no apparent reason. We suspect that the build-up of
humidity or possibly a roof leak may have been the trigger for this collapse of
the roof frame.
The addition of insulation and moisture loading may then have changed the
static loading to roof frame. This additional loading then may have
destabilised the ceiling joists with the additional load transferred as a slight
upward pressure on fixings to end grain (pull-out force) as the ceiling joists
rotated on the inside edge of the top plate.
As the struts are not vertical, lateral loading of the top plate has occurred, and
once fixings of the joist finally disengaged the wall moved outward
disengaging the rafters from the hip causing the collapse of the rafters and
tiles to ceiling.”[sic]
Case No: 284846 Determination Page 7 of 10
37. The FSP’s second expert (BA), a consultant to owners and owner builders,
also attended the site. BA says there is usually more than one factor at play
in most catastrophic failures in buildings. In this instance, he identified three
relevant factors, namely:
the age of the building,
the relatively poor standard of construction of the roof framing and
disturbances associated with renovation work (principally the
restumping).
38. BA says:
“2.1.1 This concrete tiled, timber framed residence ... has suffered the
expected extent of deterioration over the many years that it has been
standing, including corrosion of the various fixings (almost exclusively
untreated mild steel nails) used in the construction of the floor, wall and roof
framing. The framing timbers are fully dried and have not been malleable for
many years.
2.1.2 A number of incorrect carpentry practices were noted in the various
portions of the roof and wall framing able to be seen. These include:
a. the discontinuous alignment of ceiling joists across the house
b. the lack of alignment of joists (on the outer wall plate) with the rafter
feet
c. deflection of rafters due to the excessive spans (between the ridge
and the underpurlins and between the underpurlins and the external wall
plates)
d. excessive deflection of underpurlins due to the lack of strutting and
most tellingly
e. the absence of collar ties
Had the framing to this roof lacked any one of the above then the event is
unlikely to have occurred and could probably have survived with minimal
displacement had all defects (a-d) been present but with collar ties in place.
2.1.3 Clearly there will be some disturbance to the wall framing (and to a
lesser extent the roof framing) associated with stripping out the older wall and
ceiling linings and the fixing of new ones but a quick view of the stumps to this
home makes it clear that the sub-floor framing has been lifted and new
stumps installed within recent years (ie as part of general decorative
renovation work). Installing new stumps inevitably strains the fixings to wall
framing and frequently requires the replacement of wall linings (due to failure
of old brittle fixings etc) because of the disturbances associate with this work.”
[sic]
39. BA has provided his opinion on the cause of the collapse as:
“3.1 It is my considered opinion that the spreading of the roof and the
displacement of the side wall supporting it results from:-
3.1.1 the carpenters engaged to frame this residence not following trade
practices generally used at the time home was built (and substantially refined
over the intervening period).
Case No: 284846 Determination Page 8 of 10
3.1.2 the relatively heavy roof load from the concrete tiles being in place over
many years
3.1.3 age related deterioration to the nail fixings and
3.1.4 relatively minor (had the roof etc been correctly framed) disturbances
associated with the renovation works undertaken
3.2 In my experience this failure represents latent building defects
exacerbated by recent renovations (done without a realization of the effect
they can have on older timber structures).” [sic]
40. The FSP then requested its final expert, a forensic and materials scientist (Z)
to attend the site. As part of its instructions, the FSP provided Z with copies
of all reports received at that time from its own experts and the Applicant’s
experts, plus all documents supplied by the Applicant with respect to work he
had carried out to the property since purchase.
41. The Panel takes issue with the way in which these i nstructions were
provided as it is the opinion of the Panel that this could be seen as
somewhat prejudicial to the opinion ultimately provided by Z.
42. Nonetheless, Z attended the site and it was his opinion that the roof timbers
were splitting and failing and had been for many years prior to the collapse.
He says the tile batons exhibit severe bowing and distortion with obvious
signs of imminent failure. It was his opinion the property required re-roofing
with replacement of roof timbers and additional support timbers needing to
be installed.
43. Z also commented on the blow-in insulation and says:
“There is evidence that “blow - in” insulation has recently been installed in the
ceiling space of the house. We understand that it has been suggested that the
roof insulation may have become wet and accordingly increased the weight
loading on the roof/ceiling structure. There was no material evidence that the
insulation material is, or has ever been, water-logged. Physical and chemical
changes occur if this happens and those indicators are not present.
Notwithstanding the lack of physical evidence, water logged insulation may be
expected to cause a collapse of ceilings but the physics of the loading does
not support an assertion that there would be sufficient loading on the roof
structure to cause a collapse.”
44. Z also provided his opinion on the cement roof tiles and says:
“We understand that it has also been suggested that the cement roof tiles had
absorbed water from recent rains and thereby increased in weight to the point
of causing the roof to collapse. Apart from the fact that the roof tiles had been
sealed with an acrylic membrane, the quantity of water absorbed and the
increase in weight loading would not be sufficient to collapse a timber framed
roof. There are many old weatherboard cottages that have old cement tile
roofs and those roofs do not collapse from rain- laden tiles.”
45. Z’s opinion on the cause of the collapse was:
“... the roof has collapsed because it is over 80 years old, was poorly
constructed in the first place with inadequate supports and fixings, there are
Case No: 284846 Determination Page 9 of 10
no collar ties and the nail fixings used have corroded to the point of failure
especially with re-stumping movement and the weight loading of a tiled roof. It
is the absence of any remedial work to the roof or wall timber structure and
fixings, over the life of the house, that has allowed the deterioration of the
fixings to continue unabated to the point of failure.”
The roof collapse failure is a process that was developing over many years
and it reached a point of catastrophic failure because of a number of
circumstances were in place that exceeded the low tolerance of a poorly
constructed roof.
46. Whilst the FSP’s experts comprehensively disagree with the Applicant’s
experts, there are also some inherent discrepancies between the opinions
provided by the FSP’s experts. However, one thing the FSP’s experts all
agree is that there is no evidence of any storm or impact damage to the
property to cause the roof to collapse. They also agree that there is a
com bination of factors which “could” have caused the collapse.
Consideration of Cause
47. The onus of proof rests on the Applicant to establish that, on the balance of
probabilities, he has suffered a loss caused by an insured risk. Once the
Applicant has established that the loss was caused by a risk insured under
his policy, the onus then shifts to the FSP to show that, on the balance of
probabilities, the loss falls within an exclusion clause in the policy.
48. The Applicant’s experts have considered the cause of damage to be rain-
laden cement tiles on the roof of the structure, due to heavy rain experienced
in the area approximately two weeks before the collapse. The FSP has
provided extensive details regarding rain and weather activity in the area for
the month prior and month after the collapse.
49. The Panel has reviewed the information related to weather events in the
area and is satisfied the area sustained heavy rainfalls approximately two
weeks prior to the collapse as indicated by the Applicant’s experts and
disputed by the FSP.
50. However, on considering this information, the Panel must also consider other
rain and weather events in the area over the preceding years. It is
acknowledged that the area has experienced heavier rainfall periods prior to
the two weeks before the roof collapse, over a number of years. The
question has to be asked then, if the roof tiles became rain-laden due to rain
two weeks prior, why, during heavier rain periods in the preceding years, did
the roof not collapse previously?
51. The Panel has carefully considered the opinion of Z with respect to the roof
tiles absorbing moisture due to their porousness. Z clearly says his
inspection of the roof tiles shows a protective membrane had been applied to
the tiles and as such, this would prevent the tiles absorbing water.
52. The Panel is of the opinion, on the balance of probabilities that the roof
collapse has therefore not been caused by rain soaking into the roof tiles. As
Case No: 284846 Determination Page 10 of 10
such, the Panel is satisfied the Applicant has not proven a claim under the
policy in this regard.
53. A further suggestion on the cause of the collapse was made by M which
detailed moisture building up in the insulation in the roof cavity, thus causing
a heavier than normal weight to be put onto the roofing timbers and
ultimately resulting in the roof collapsing. However, this theory has been
discounted by Z who inspected the insulation and found no evidence of it
being water logged or having ever been water logged.
54. Z also advised that had the insulation become water logged this would have
resulted in a ceiling collapse and not a catastrophic roof failure. The Panel is
of the opinion given there is no evidence of water having affected the
insulation, this cause can also be disregarded.
55. It should be noted that neither an accumulation of water/moisture build up in
insulation over a period of time, or rain water seeping into roof tiles, are
covered under the policy.
56. The Panel considers there is no definitive direct or one cause, such as might
have caused the roof to collapse. All suggestions put forward by the FSP’s
experts however, are relevant to the construction of the roof, the age of the
roof and the lack of maintenance over many years.
57. The policy clearly does not cover maintenance, wear and tear, gradual
deterioration or structural defects. The Panel is sa tisfied there is no cover
provided under the policy for any cause suggested by any of the experts for
the collapse of the roof.
Determination
58. On the basis of the available information the Panel determines, on the
balance of probabilities, that the cause of the roof collapse was a
combination of a number of factors relating to the age of the roof, its original
construction being sub-standard, gradual deterioration and normal wear and
tear, and a lack of preventative maintenance.
59. The Applicant has failed to demonstrate, on the balance of probabilities, that
the roof has collapsed due to an insured event and as such, the Panel
considers the FSP is entitled to deny the Applicant’s claim.