Home / Financial Firm (Unknown - Insurer) / Determination 281197
Determination 281197
Claim denied for structural cracking with multiple excluded causes
Summary
The Applicants claimed for severe cracking to their home and the FSP denied the claim after extensive investigation found several causes, each excluded. The Panel held the FSP was entitled to deny the claim and need not investigate further.
The Wayne Tank principle applies where one covered cause operates alongside excluded causes, so the excluded causes defeat the whole claim.
Issues
- Claim denial primary · not upheld“The FSP is entitled to deny the Applicants' claim in its entirety under the Wayne Tank principle, as several causes are excluded.”
- Inadequate claim investigation secondary · not upheld“The FSP has undertaken extensive investigations and is not required to undertake any further investigations.”
- Misleading conduct secondary · not upheld“No evidence the Applicants relied to their detriment on the FSP indications that the claim may be covered.”
Subjects and remedies
home or building damageno remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Case No: 281197 Determination Page 1 of 12
Case number: 281197
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of Claim
7 March 2013
Background
1. The Applicants hold a home building insurance policy with the Financial
Services Provider (FSP) which was current at the time of claim lodgement.
The policy provided a sum insured for buildings of $358,071 with an
applicable policy excess of $500.
2. On 12 November 2010 the Applicants’ daughter contacted the FSP to advise
that there was severe cracking to th e Applicants’ residence. She further
advised that the cracking had been present for several years and that there
had been some issues with a leaking toilet.
3. The FSP arranged extensive investigation of the Applicants’ premises in
order to determine the cause of damage. No singular cause was identified,
rather numerous causes excluded by the policy were found.
4. The FSP denied the Applicants ’ claim on the balance of probabilities that the
causes of the damage were excluded by the policy.
5. The Applicants dispute the FSP’s decision and have requested the FSP to
continue its investigation until the exact cause can be determined.
Summary of Applicants ’ position
6. The Applicants say that they contacted the FSP with regards to the large
cracks in their home to see if there was any cover under their building
insurance policy.
7. It was the FSP who voluntarily undertook investigations as to the cause of
the damage. As a result of those investigations, no definitive cause has been
identified.
8. The FSP should continue the investigation process until the exact cause is
located and if the cause is an insured event, rectify the damage to their
residence.
Determination
Case No: 281197 Determination Page 2 of 12
9. They have been led to believe repeatedly throughout the claims process that
their claim would be covered.
Summary of FSP’s position
10. The FSP says it has undertaken extensive investigation of the Applicants’
property over an 18 month period.
11. Whilst no definitive cause has been found, a number of possible or
contributing causes have been identified. These causes are all excluded
under the terms and conditions of the policy.
12. As the Applicants have failed to prove that they have sustained a loss
caused by an insured event, and that the investigation it has undertaken has
shown numerous uninsured causes, it is entitled to deny the App licants’
claim.
13. The FSP relies on the following policy provisions of its Product Disclosure
Statement (PDS):
“ Storm
If your home or contents suffer loss or damage caused by
a violent wind, cyclone or tornado
thunderstorm or hail which may be accompanied by rain or snow, or
a sudden, excessive run-off of water as a direct result of a storm in
your local area
...
we will under buildings insurance
rebuild or repair that part of your home that was damaged ...”
(Page 15)
“ Water – leaking or escaping
If your home or contents suffer loss or damage caused by water leaking
or escaping from
pipes
road gutters or curbing
house gutters or drainpipes
baths, sinks, toilets, basins or any other fixed plumbing apparatus
washing machines, dishwashers
refrigerators, heating or cooling systems with a water dispenser
waterbeds
an aquarium that holds 60 litres or more of water
...
Case No: 281197 Determination Page 3 of 12
we will under buildings insurance
rebuild or repair that part of your home that was damaged
however
...
we will NOT pay to locate the cause of damage unless we have agreed to
the costs beforehand.”
(Page 17)
“ Buildings – what we will cover under buildings insurance
We cover domestic residential buildings for replacement or repairs up to
the buildings sum insured
we will under buildings insurance
rebuild or repair that part of your home that was damaged as a result of an
incident described on pages 6 to 17. ”
(Page 23)
“ What you are not covered for – general exclusions
we will NOT cover
loss, damage, injury or death that occurs as a result of
...
wear, tear, rust, corrosion, deterioration or erosion
...
subsidence or landslide unless it happens immediately following an
earthquake or explosion
...
tree roots
...
faulty design or workmanship
...
mechanic al, structural or electrical failure of an item ...”
(Page 35)
Issues
14. Whether the FSP is required to conduct any further investigation into the
cause of the damage.
15. Whether the FSP is entitled to deny the Applicants’ claim.
Case No: 281197 Determination Page 4 of 12
Reasons for decision
16. As advised to the parties, FOS has considered it appropriate to expedite the
dispute in accordance with the Operational Guidelines to the FOS Terms of
Reference. This dispute has not been the subject of a FOS
Recommendation and has proceeded directly to Determination.
17. I am satisfied there has been a full exchange of material between the parties
and that each party has had the opportunity of clarifying the issues that arise
from the material.
18. The Applicants say that they originally contacted the FSP querying whether
large cracks observed at their property over the preceding six or seven years
were claimable under their insurance policy with the FSP. The FSP advised
they would arrange assessment and investigation to determine the cause of
the cracks.
19. The Applicants are of the opinion that no conclusive cause or causes have
been identified by the FSP’s investigations and in fact some of the reports
prepared by the FSP’s experts indicate further investigations are warranted.
As such, the Applicants expect that the FSP should complete those
investigations until the exact cause is determined.
20. The FSP says that it has conducted extensive investigations into the cause
of the damage to the Applicants’ home over an 18 month period. It says that
on the balance of probabilities based on those reports, the probable causes
are numerous.
21. The FSP relies on expert reports from I, an investigative and technical
building consultant, and C, a structural building engineer. During the course
of their original inspection of the property, a wate r leak detection test was
also carried out of all the main water supplies at the Applicants’ property.
22. I am satisfied that the damage to the Applicants’ home is the subject in
which expert evidence is admissible and the FSP was entitled to refer to the
evidence of I and C who both examined the property. I am also satisfied that
I and C were qualified to provide such expert evidence.
23. In I’s initial report of 21 December 2010, he summarises his findings and that
of C:
“ By way of summary , [C} and I have concluded the following:
2.1 That movement and crack damage to the dwelling is not as a result of
leakage from mains pressure water supply pipes or the dwelling’s
sewer system. There was no apparent leakage from the mains
pressure water supply pipes and the encountered leakage from the
sewer system was minor, too far removed and has caused no resultant
damage.
2.2 That there are no site indicators to suggest that a relationship exists
between movement and crack damage to the dwelling and the Board
Sewer located in the adjoining rear property. This Board Sewer is 2.7
Case No: 281197 Determination Page 5 of 12
metres deep and flows from west to east, parallel with the insured’s
rear boundary.
2.3 That on the basis of information provided by your insured, movement
and crack damage has been occurring for at least 6-7 years.
2.4 That it was not possible to establish with certainty the cause of
movement and crack damage to the dwelling because of acces
restrictions. Concrete pavement around the perimeter of the granny
flat prevented exploratory excavation along the base of the east and
south walls. Your insured should engage a structural engineer to
undertake invasive investigation (concrete pathways will need to be
removed to facilitate excavation for foundation soil and footing
assessment).
2.5 That in the course of the site inspection it was noted that the
principal dwelling’s roof frame was distressed (settling into the roof
void) [please refer to the photograph on page 5 of the [C] report]. The
insured was alerted to the problem.
2.6 That in the course of the site inspection it was noted that the in-ground
concrete swimming pool was fully drained (empty) but with insufficient
provision for hydrostatic relief. Your insured was alerted to the
possibility of uplift of the pool (pool popping out of the ground) in the
event of sustained rainfall and that a pool expert should be engaged to
provide additional hydrostatic relief alternatively, to re-fill the pool.
2.7 Cautionary alert – Your insured has been advised that both the
granny flat east side wall and the distressed roof frame to the
principal dwelling are likely to collapse in the event of further
settlement. Please inform your insured of the need to affect
appropriate stabilisation measures, immediately, to prevent
collapse and possible injury.
Item 3 – Determination
The cause of movement and crack damage to the dwelling could not be
definitely determined because of restricted access. That said, there is no
evidence of a relationship between observed damage and:
3.1 A storm event;
3.2 Leakage from mains pressure pipes or waste water drainage
pipes.
3.3 The Board Sewer.”
24. In C’s report dated 18 December 2010, he concludes:
“ 3.0 Conclusion
3.1 Our investigation into the cause of damage to the rear granny
flat portion of this dwelling has not produced a result other than
to state that observed displacement and fracture damage is
neither storm caused nor from leaking water supply pipes (none
encountered) nor from drainage services (only minor leakage
discovered from a sewer pipe section too far removed to be a
problem).
Case No: 281197 Determination Page 6 of 12
3.2 A further serious structural problem with the house roof framing
has been discovered. There is no supporting evidence to link this
with the damage to the granny flat.
3.3 We consider damage in both locations as dangerous
because we cannot yet establish what the cause is and,
therefore, the likihood is present of further rapid
deterioration in the stability of the supporting structures at
both granny flat and roof locations. While we know the granny
flat problem has been around for 6-7 years at least, the roof
collapse appears to be a complete surprise to the insured.
3.4 Your insured needs to engage a structural engineer as soon as
possible to investigate structural failures in the granny flat and
house roof frame. Access will need to be provided in both
locations, specifically removal of the external concrete path at
the base of the south and east walls of the granny flat as well as
removal of a ceiling section beneath the collapsing roof frame.
3.5 Although not part of our brief, we were surprise to find the large
swimming pool had been emptied by the insured at this time of
year. We are not aware of any connection to the two serious
structural issues but we will keep the action in mind. The insured
was made aware of the “float - up” danger of hi s action in
emptying the pool especially during wet weather. Tehre was
some staining at the deep end to indicate water entering through
the relief valve, or just rain water accumulation. An east-west
oriented rack was visible in the bottom of the pool.” (s ic)
25. I also note other relevant comments made by C in his report in relation to
possible causes of the cracking and the results of the leak detection
procedure. C reports:
NB: EWW refers to the east-west wing and NSW refers to the north-south
wing of the A pplicant’s residence.
“Inconsistent with the naturally occurring reactive foundations and resultant
low-level house damage in the area is the rear left-hand-side (L.H.S.) of the
building which supported the first floor granny flat. This part of the building
was subject to sever structural damage consistent with settlement and lateral
displacement to the east, at the back corner of the site.” (Page 4 of report)
“Preliminary assessments and considerations
Initial structural assessment of the overall building condition identified three
different, and possibly separate, areas of structural concern.
1. Low level internal and external building disturbance throughout,
consistent with houses constructed on reactive clay soil
foundations prior to the implementation of the Australian Standard
2870 – Residential slabs and footings.
2. Partial collapse of the roof framing at the junction of the EWW and
the NSW.
3. Substantial disturbance of the south-east corner of the composite
dwelling beyond normal expansion/contraction movements in the
foundation soils.” (Page 5 of report)
Case No: 281197 Determination Page 7 of 12
“1. As the structural concerns noted in items 2. and 3. present a significant
and overriding danger to the inhabitants of the property, we can omit
further reference to item 1 as a relatively harmless non-issue for the
moment.
...
2. While urgent consideration of item 2. is required, the ceiling hatch at the
south end of the NSW could not provide access to the sunken roof area.
As the existing roof is sarked another ceiling location, preferable closer
to the roof ridge intersection, has to be selected and opened so that the
roof framing can be examined and, if necessary, made safe from further
collapse.
We can only speculate that the roof collapse is attributable to an original
design or building defect, or possibly due to the progressive destruction
of critical support members by termite attack.
...
3. Our investigation of the disturbed south-east corner of the dwelling
involving the ground floor pool equipment room and the overhead
kitchen of the granny flat is also thwarted. The obstacle this time is our
inability to access the foundation and footings concealed under a
concrete path which seals the area between the boundary fence and the
building walls.” (Page 6 of report)
26. The Applicants say that these reports seem to suggest that they have
caused or contributed in some way to the cracking to their home, based on
the detailed advice regarding unrelated issues to the cracks that the experts
have observed . I am of the opinion the comments regarding the Applicants’
roof and pool were not intended to imply this, rather I and C, and the FSP,
have a responsibility to advise the Applicants of any additional issues which
may have been identified, as a way of risk managing the property. This also
provides the Applicants with an opportunity to rectify any other issues before
possible damage or loss occurs.
27. In addition, the Applicants have a responsibility to maintain their home and
the observations noted by I and C have been provided to assist the
Applicants in this regard. I am therefore satisfied that the FSP and its experts
have not intended these comments to be a suggestion that the Applicants’
actions or inactions have contributed to the cracking to their home.
28. A review of C’s report, revealed the following further and relevant
information:
Previous repairs undertaken by the Applicants to the area of concern
indicated an existing knowledge by the Applicants of the damage.
A single storey building in the south-west corner of the neighbouring
property to the east side was similarly damaged and a third property on
the south side of the boundary and to the east showed settlement
damage at a pool surround.
There are 7 conifer trees on the boundary fence approximately 2m from
the rear of the property.
Case No: 281197 Determination Page 8 of 12
The main sewer line, operated/controlled by SW (the Sewer Board),
appeared from plans to run directly underneath the co nifer trees,
approximately 2.7m underground.
There was no evidence on the ground to indicate that tree activity had
caused any sewer leaks and there was no indication on the ground to
indicate any sewer leaks at all.
Any investigation into the sewer would be difficult as it required some
convincing evidence of a leak to arrange SW to conduct investigations
and only SW was authorised to conduct such investigations.
The conifer tree at the extreme east of the boundary lines up exactly
with the gap between the east side of the granny flat building and the
west side of the adjacent damaged building in the property to the east.
This indicates that should tree root activity of this particular tree be
confined between the footings of the two buildings, then the moisture
extraction from the soil may be similarly concentrated leading to
excessive settlement of the ground between the buildings.
The leak detection test and CCTV test conducted by the appointed
plumber found no fracture or displacement of the line through the area
of interest. Some settlement of the pipe was detected and this would be
sufficient to retain water just prior to joining the line through the area of
interest, which may be indicative of excessive ground settlement which
would also affect the in-ground drain.
The plumber discovered a fault with the sewer line emanating from the
another location on the property. The pipe in this area was fractured,
offset and showed evidence of tree root invasion, however the waste
line concerned was too far remote and not significant enough to cause
the foundation problem causing the cracking.
No other water leaks at the property were located by the plumber.
The pool equipment room was something of an enigma with regard to
the rear wall panel which was a single ski n brick wall and which had
been added a considerable time prior to the reported damage. It was to
fill in an opening at this location however there is no explanation as to
why the opening existed in the first place.
It is C’s opinion that this room may als o be a separate addition and may
be supported on a footing system partially, or at the south side fully
independent of the house footing system. C opined that if this was the
case, the independence of the room footing would have contributed to
the lateral drift and downward rotation of the area concerned, which
had caused the cracking.
29. On receipt of these reports, the FSP denied the Applicants’ claim.
30. The Applicants contacted the FSP at the beginning of March 2011 to advise
that a neighbouring property had suffered a sewer leak/damage from the SW
sewer line. It was decided that further investigation should be undertaken,
especially in relation to the main sewer line, controlled by SW.
Case No: 281197 Determination Page 9 of 12
31. Unfortunately, these investigations were somewhat delayed through the
difficulties encountered by I in liaising with SW, and this hampered I’s
investigation.
32. In I’s report of 24 March 2011, upon completion of these investigations, he
reported the difficulties he encountered when attempting to co-ordinate site
inspections with SW and obtaining details from SW. The Applicants’
neighbour who had suffered the sewer leak in his backyard, had appointed a
plumber to attend to the leak. It was this plumber who first contacted SW.
33. During his discussions with the Applicants’ neighbour and the plumber, I
ascertained that the plumber, when investigating and attempting to
repair/clean up the sewer leak, noticed that a more prominent leak was
coming from the main sewer line belonging to SW. He contacted SW who
sent a representative to investigate the matter . In the plumber’s presence,
SW conducted a CCTV test of the SW pipe and found that it had suffered
tree root invasion.
34. The plumber further advised, and I later confirmed this with SW, that SW
attempted to remove the tree roots from the pipe a nd in the process, their
equipment became lodged within the line. It took some two to three weeks to
arrange for this equipment to be freed.
35. During the course of his enquiries with SW, I attempted to meet with SW
onsite, obtain details of their investigations including copies of any CCTV
footage and obtain information in relation to the likelihood of damage
occurring to the Applicants’ property. Unfortunately, SW was uncooperative
in this regard.
36. I am satisfied that I made every effort to investigate the involvement of SW
and the main sewer pipe in relation to the damage to the Applicants’
property.
37. Due to the lack of co-operation of SW, the FSP authorised I to arrange other
less invasive investigations to continue. This involved the sampling of soil at
the Applicants’ property to determine if any possible sewer leak from SW’s
main sewer line could have contributed to the damage at the Applicants’
property.
38. As a result, a geotechnical engineer, D, attended the property and took soil
samples from the area immediately adjacent to where the damage to the
property was evident (BH1), and a “control” sample (BH2) from the front of
the property, which is far enough removed from the main sewer line to allow
a control sample to be taken.
39. D found evidence within BH1 of traces of ammonia, which can indicate the
presence of sewerage; however, the results are inconclusive as the source
of the ammonia could not be determined.
40. D also provided his opinion based on his assessment of the soil, which he
summarised as:
Case No: 281197 Determination Page 10 of 12
“The site f actors and related information determined from the investigation,
relevant to the performance of the footings supporting the addition at the rear
SE corner of the dwelling at [Applicants’ address], are summarised as
follows:-
i. a high plasticity residual clay soil profile with a high potential for reactive
(shrink-swell) behaviour,
ii. evidence of footing movements (possibly from reactive soil behaviour)
elsewhere about the dwelling footprint,
iii. clay fill (with similar characteristics to the natural soil) of 1m depth at the
location of the wall movement,
iv. a possibility that the footings supporting the addition were not piered to
a depth below the fill and below influence from the adjacent sewer main
trench
v. disturbed ground nearby in the vicinity of the 3m deep sewer main
trench on the adjoining property,
vi. trees growing on the adjoining property in the immediate vicinity of the
cracked wall area, within close proximity (less than current tree height
and future mature height) and possible root intrusion within the footing
zone,
vii. an old break in the sewer main at this location, and its recent
investigation and repair by [SW],
viii. no evidence determined from CCTV examination of the sewer and
drainage line connections on [Applicants’ address] in the vicinity of the
rear SE corner that there are or were any breaks or leakages from those
services, and
ix. a period of 31 – 32 years from the time of construction of the addition
(about late 1972), to the reported first indication of current wall
movement problems, namely about late 2003/late 2004 (some 6 – 7
years prior to December 2010, as reported by the owner to [C]);
however, progressive movements are evident in the 30 year period prior
to 2003/2004 from the patching and repairs seen in this area of the
building.
There is no information from the details of original construction, either for
the swelling in its original form (construction prior to 1966), or for the two-
storey addition (possible late 1972), that confirms whether or not piers were
utilised for the footings, at either phase of development. The serious extent
of differential movement between the original construction and the two-
storey addition points to a difference in footings or the foundation soil
conditions. Again, it is noted that there is a substantial depth of (non-
engi neered) clay fill at the rear SE corner of the addition.”
41. D goes on to say that it is unusual that shallow footings on uncontrolled clay
fill of significant depth would perform adequately for 30 years or more and
then suddenly settle in a different manner. Some degree of settlement and
wall cracking/movement would occur, however it would be to a manageable
degree.
42. After reviewing the expert reports, I am of the opinion that a definitive cause
has not been confirmed. However, a number of possible causes have been
Case No: 281197 Determination Page 11 of 12
provided, one of which is the possible leakage of sewerage from the SW
mains pipe.
43. In the absence of any expert evidence from the Applicants to the contrary, I
am therefore satisfied, that whilst a singular cause cannot be established,
there are a number of causes which appear to have contributed to the
damage at the Applicants ’ property.
44. The onus of proof rests on the Applicants to establish that, on the balance of
probabilities, they have suffered a loss caused by an insured event. Once
the Applicants have established that the loss was caused by an event
insured under their policy, the onus then shifts to the FSP to show that, on
the balance of probabilities, the loss falls within an exclusion clause in the
policy. It is important that the Applicants understand they have the primary
onus of proving the loss and damage was caused by the insured event.
45. In this instance, the FSP has attempted to assist the Applicants, due to their
longstanding association with the FSP, by arranging investigations into the
cause of damage. I am of the opinion that the FSP was under no obligation
to arrange these investigations.
46. Unfortunately, the result of those investigations, whilst largely inconclusive,
did not assist the Applicants in proving their loss fell within an insured event
of the policy. However, the investigations did indicate that the various
contributing causes were in fact excluded under the policy.
47. The Applicants have also suggested that the FSP has indicated at various
times throughout the claim and inves tigation process, that their claim “may”
be covered, or that the cause “may” be a nearby leaking sewerage
main/pipe. Arguably, this brings into consideration the doctrine of estoppel.
48. In broad terms, the doctrine of estoppel seeks to ensure that a person who
leads another to act to his or her detriment, by relying on a statement made
by this person should be held responsible for those statement(s) insofar as
the representations made were relied upon. Statements or representations
may be in the form of an express promise or they may be inferred from the
conduct of a person. (See page 159 of Business Law of Australia [7 th
Edition]).
49. I have no doubt that the FSP has given indications to the Applicants
throughout the claims process that should it be determined that the cause is
a leaking sewerage main/pipe, then there may be some cover provided to
them under the policy. However, there is no evidence before me to suggest
that the Applicants have relied on this information to their detriment. That is,
there is nothing to indicate that the Applicants have taken any steps to repair
or rebuild their property at their own expense on the advice of the FSP.
50. The FSP refers to the Wayne Tank principle which provides that when there
is loss due to causes that operate simultaneously or congruently, one cause
being covered and any others being excluded under the policy, the exclusion
operates to the detriment of the total claim.
Case No: 281197 Determination Page 12 of 12
51. The investigations undertaken by the FSP have revealed that there are a
number of probable causes for the damage noticed at the Applicants’
premises. In this instance, none of those causes are insured events under
the cover provided by the FSP.
52. However, if I consider that a possible contributing cause of the damage is an
insured event, for example, a leaking sewerage line or pipe, it does not
distract from the fact that other causes have been identified. In accordance
with the Wayne Tank principle, these other identified causes are excluded
under the policy, and as such, this entitles the FSP to deny the Applicants’
claim in its entirety.
53. Whilst I sympathise with the Applicants ’ position and the extensive damage
to their home, they still have an onus to mitigate their loss and to prove that
their loss has been caused by an insured event. From the material before
me, I cannot see that the Applicants have made any attempt to arrange for
their own investigation of the cause of the damage and I suggest had they
done this, it may have been useful in helping them resolve the current issues
with their home.
Determination
54. On the basis of the available information I determine that the FSP has
undertaken extensive investigations in an effort to assist the Applicants and
are not required to undertake any further investigations.
55. I further determine that based on the evidence provided by the FSP as a
result of its investigations, it is entitled to deny the Applicants’ claim.