Roof leaks and internal damage attributed to FSP-arranged structural repairs; FSP refused to repair
Text of the determination
Case No: 268014 Determination Page 1 of 11
Case number: 268014
General Insurance - Domestic Insurance - Home Building - Service - Service
quality
26 July 2012
Background
1. The Applicant’s home was insured with the Financial Services Provider
(FSP) under home building policy.
2. The home sustained damage as a result of an event which the FSP
acknowledged was covered by the policy.
3. The FSP arranged for repairs to be carried out to the home.
4. The Applicant believes the repairs caused the home’s roof to leak, resulting
in water entering the home and causing further damage.
5. The FSP does not accept responsibility for the leaking roof and further
damage; contending that the leak was not caused by an insured event, but
was due to:
Wear, tear, rust, corrosion, deterioration, or corrosion.
Faulty design or workmanship.
The fact the home was not watertight, structurally sound, secure and
well maintained.
Summary of Applicant’s position
6. Although old, the roof had never leaked prior to the repairs.
7. Major restumping works as well as the removal of laths and plaster walls
shook the old slate tiles, causing them to slip and leak.
8. Major repairs also changed the direction of water flow on the tin made
section of the roof which the FSP had agreed to rectify.
9. The FSP has not demonstrated that the major repairs did not or could not
have damaged the roof. Its expert also does not explain how the roof could
suddenly leak if the leak was supposedly caused by wear and tear.
Determination
Case No: 268014 Determination Page 2 of 11
10. The FSP’s failure to address the leak h as resulted in further damage to the
plaster and paintwork in the relevant areas of his home. Although admitting
liability for such damage, it now refuses to repair the damage.
11. He is prepared to accept a proportionate settlement if the leaks in the old
roof cannot be repaired and the whole roof requires replacement.
Summary of FSP’s position
12. The leak in the roof and the internal damage arising from the leak were not
caused by an insured event.
13. Its expert evidence shows the roof leaks were caused by wear, tear,
deterioration, erosion, faulty design or workmanship, and the home not being
watertight, structurally sound, and well maintained; all of which were
excluded events.
14. The FSP relies on the following policy provisions:
“ Storm
If your home or
contents su ffer
loss or damage
caused by
a violent wind,
cyclone or
tornado
thunderstorm or
hail which may be
accompanied by
rain or snow, or
a sudden,
excessive run - off
of water as a
direct result of a
storm in your
local area
we will under
contents
replace or repair
your damaged
contents
we will under
buildings insurance
rebuild or repair
that part of your
home that was
damaged
rebuild or repair
that part of any
gate, fence or
free - standing wall
that was
damaged by
wind, unless
they were not
kept in good
order and
repair, that is,
they were not
structurally
sound or well
maintained
…
…
Water – leaking or escaping we will under however
Case No: 268014 Determination Page 3 of 11
If your home or
contents suffer loss
or damage caused
by water leaking or
escaping from
pipes
road gutters or
curbing
house gutters or
drainpipes
…
contents
replace or repair
your damaged
contents
we will under
buildings insurance
rebuild or repair
that part of your
home that was
damaged
we will NOT
cover loss or
damage caused
by water leaking
or escaping from
a
sho wer
recess or
shower base
stormwater
channel or
canal
stormwater
pipe off the
site
we will NOT
repair or replace
the item that the
water leaked or
escaped from
we will NOT pay
to locate the
cause of
damage unless
we have agreed
to the costs
beforehand.
…
Locating the cause of
damage
Demolishing and removing
debris
Fees arising from rebuilding
If as a result of an
incident described
on pages 6 to 17
you need to
locate the cause
of damage
demolish and
remove the debris
pay for fees
arising from
rebuilding
we will under
buildings insurance
pay the
reasonable costs
of
locating the
cause of any
damage if it is
not known
demolishing
and removing
debris from
your home
employing an
architect,
engineer or
surveyor in
connection
with
rebuilding or
however
we must have
agreed to pay
the costs
beforehand
the costs must
relate directly to
the part of your
home that
suffered loss or
damage
Case No: 268014 Determination Page 4 of 11
repairing your
home
meeting the
requirements
of a statutory
authority
…
Buildings – what we will
cover under b uildings
insurance
We cover domestic
residential
buildings for
replacement or
repairs up to the
buildings sum
insured
we will under
buildings insurance
rebuild or repair
that part of your
home that was
damaged as a
result of an
incident
described on
pages 6 to 17
…
What you are not covered for – general exclusions
we will NOT cover
loss, damage, injury or death that occurs as a result of
…
wear, tear, rust, corrosion, deterioration or erosion
…
faulty design or workmanship
…
Settling claims – under buildings
If we agree to cover the claim under buildings insurance
…
we will
repair or rebuild that part of your home which sustained loss or
damage, or
pay you the cost to repair or rebuild it, whichever is smaller
if we choose to pay you the cost to repair or rebuild your home,
we will pay the builder directly unless we tell you otherwise
…
Things that may put your claim or cover at risk
You may put your insurance claim or cover at risk if you do not meet
your obligations to us. We may refuse a claim, cancel your Policy, or
do both
Case No: 268014 Determination Page 5 of 11
…
if you
…
do not maintain your home in good repair and condition. This
means your home must be watertight, structurally sound, secure
and well maintained ”
Issues
15. Whether the leaks in the Applicant ’s roof (and damage arising from these
leaks) were caused by repairs carried out by the FSP.
Reasons for decision
16. As informed to the parties, due to the nature of the dispute, this matter has
been referred to an Ombudsman for Determination in line with the
Operational Guidelines to the Financial Ombudsman Service’s Terms of
Reference.
17. I am satisfied that the material has been exchanged and the parties have
had the opportunity to respond to the issues raised.
18. I understand that the Applicant has since repaired the roof (at a cost of
$2,530) so the question of whether the roof required complete replacement
no longer arises. I understand that the internal damage to home arising from
the roof leaks has not been repaired as yet.
Proximate cause of the roof leak and subsequent damage
19. It is not in dispute:
The Applicant’s home was initially damaged by water which had
escaped from a neighbouring property.
The FSP accepted liability for the damage and made arrangements to
repair the Applicant’s home.
The home required extensive repairs, which included removal of walls
and laths, and re-stumping and re-blocking of the building structure.
20. The Applicant’s case is that the roof began leaking after extensive structural
repairs were carried out by the FSP. It did not leak before such repairs so he
surmises that the repairs must have caused the home to move which, in
turn, displaced the roof and caused the leak.
21. Although I am mindful that the Applicant has not strictly substantiated his
assertion with expert evidence, I do not find his explanation implausible
given the nature of the structural repairs that had been carried out the home.
Case No: 268014 Determination Page 6 of 11
22. It does not appear unreasonable that extensive structural repairs (like re-
stumping or re-blocking works) can cause a building to move and in turn,
cause other damage to it; particularly when there is nothing in the material to
suggest that the Applicant’s home has had a demonstrated history of roof
leaks prior to the incident under consideration.
23. I have carefully considered the FSP’s submi ssions and evidence in
response, and do not find them persuasive.
24. The FSP ’s first suggestion is that the Applicant has not established that the
roof leak (and the subsequent damage arising) was caused by an insured
event, but this was not the Applicant ’s c ase to begin with. His case is that the
damage was caused by building movement occurring during the course of
the FSP’s repairs.
25. Turning to the exclusions and policy conditions relied on by the FSP, I note
that the FSP relies extensively on a report prepared by roofer “RC”.
26. I have carefully reviewed RC’s report and derive little assistance from it.
Although the report makes a number of strong comments as to the condition
of the roof, I found its conclusions generally unsubstantiated but largely
rhetorical and speculative.
27. The following are some of my concerns with the report:
After purporting to attribute the leak into the Applicant’s daughter’s
room to some “ damaged and defective slates concentrated to one
small area of the roof ”, the report readily concludes:
“ The damage and deterioration evident to the slates is entirely in
keeping with normal and natural wear and tear over more than 100
years or (sic) service life… ”
It does not explain how age and/or wear and tear caused these slates
to become damaged or defective, or for that matter, impacted their
waterproofing capabilities.
More importantly, the report does not explain (and I am unclear) why
the damaged and defective slates happened to be confined to “one
small area ” of the roof .
It is plain that the slates on other sections of the roof were of similar
age, and one would ordinarily expect the slates to age consistently.
Accordingly, if the age of the slates were indeed a contributing factor to
the leak (which is what RC ’s report purports to suggest), it would not be
unreasonable to expect leaks at other (if not all) areas of roof.
In other words, if age was a factor, I fail to understand why the leak
should only be confined to one particular location on the slate tiled roof.
The report provides a photograph of a broken slate accompanied by
the following narrative:
“ This slate has been broken for many years as evidenced by extensive
weathering to the breakline. ”
Case No: 268014 Determination Page 7 of 11
It is plain that this section of the report purports to imply that the leak
into the Applicant’s daughter’s bedroom has been occurring for a long
time.
I have reviewed the relevant photograph and note that the “ breakline ”
was actually clean and free of any stains or growth. This is in contrast
to the top side of the broken slate which was substantially covered by
stains and growth. It is not unreasonable to expect the “ breakline ” to be
covered with similar stains and growth if it had been exposed to
“ extensive weathering ” for a long time as the report claims.
Furthermore, if this area of the roof was indeed leaking for a long time
as alleged, it would not be unreasonable to expect evidence of water
stains and/or rot on the timber battens and framing within the roof
cavity and on the top side of the ceiling boards. No such evidence has
been provided in the material exchanged.
The report provided one photo showing a nail missing from one
particular slate and then proceeds to state:
“ Nails that are installed to hold lower slates into position have gradually
worked their way through the top slate. This is a typical normal wear
and tear issue and I cannot perceive of any circumstances where this
type of damage would be consistent with past works… ”
The report does not explain, and I am unclear:
- How the author knew that the missing nail in the photograph had
allegedly worked its way through the top slate as claimed.
- How this is considered a “ typical normal wear and tear issue ” . The
report does not explain how nails would work through the slates
over time.
How a missing nail on one particular slate enabled the author to
conclude that “nails ” had worked their way through a number of
slates (ie. purporting to imply that a number of slates were allegedly
affected by nails working through them).
After claiming that the corrugated iron section of the Applicant’s roof
was “ due overwhelmingly to original installation faults ”, the report
proceeds to conclude that that particular section of the roof was
“ obviously ” not the work of an appropriately qualified or licensed roof
plumber.
The report provides no evidence that the corrugated iron section of the
Applicant’s roof was in fact installed by a non-qualified or licensed roof
plumber, so it is unclear how the report could boldly conclude as such.
In my view, it is not an unreasonable proposition (and life experiences
have indeed shown) that an even appropriately qualified or licensed
tradespersons can carry out poor work.
Furthermore, whilst the report purports to suggest that this area of the
roof was defectively installed and made some references to Australian
Plumbing S tandards, the report’s conclusions on the matter appears to
Case No: 268014 Determination Page 8 of 11
be convoluted, if not inconsistent with the available evidence and
surrounding circumstances.
The report makes reference to a relevant standard that purports to
state that iron roofs can only “ be legally installed by a licensed
plumber ” , and then proceeds to conclude (without substantiation) that
an unlicensed roof plumber must have necessarily installed the metal
roof.
The report also purports to suggest a number of installation defects
without proving the relevant plumbing standards applicable, or where
one was applicable, demonstrate that such a standard was in place
when the roof was installed.
In particular, the report states:
The roof lacked a “ turn up process ”.
The report says “ any knowledgeable plumber” would have
installed one and that the lack of one was a contributing factor to
the leak into the Applicant’s dining room.
The report does not say if the Australian Plumbing Standards
mandates a “ turn up process ” if it was as essential as the report
makes it out to be, let alone demonstrate that such a standard
was in place when the roof was installed.
Further, the report does not explain how a lack of a “ turn up
process ” had caused or contributed to the leak to begin with.
In any case, the report is difficult to reconcile with the evidence.
There is no dispute that the metal roof had been in place for many
years and as such, ought to have been exposed to many
instances of rain events.
If the lack of a “ turn up process ” was a contributory cause , there
ought then to be evidence of prior water entry. As previously
indicated, I found no evidence of prior water entry in the material
exchanged.
It had “ totally inappropriate aluminium flashing ”.
Although t he report states that the flashing “ does NOT have
sufficient tensile strength ” , it does not demonstrate what its actual
tensile strength was and what would be an appropriate tensile
strength. Nor does it explain how the alleged lack of tensile
strength caused or contributed to the leak.
The report also does not say if there is an Australian Plumbing
Standard that regulates the matter of tensile strength, let alone
show that such a standard was in place when the roof was
installed.
Whilst the report did suggest that the flashing only provided 60mm
coverage (when the relevant Australian standard allegedly
specifies a minimum 150mm), it does not show that such a
standard was already in place when the roof was installed.
Case No: 268014 Determination Page 9 of 11
More importantly, it does not explain how the alleged inadequate
coverage would cause or contribute to water entry.
“ [Old] fashioned straight shank roof nails ” were used.
The report states that “ all ” plumbers would only utilise “ modern
screws ” to install roof cladding without explaining or
demonstrating that such “ modern screws ” were readily available
or already the standard at the time the old iron roof was installed.
The report does not substantiate the claim that straight shank
nai ls “ have lost their bonding to the timber battens ”.
No evidence of the condition of the roof cavity has been provided.
Such evidence ought to be easily obtainable and would arguably
be the best evidence to determine if the home has had any prior
issues with water entry.
“ The incorrect placement of the nails through the lower
corrugation is totally unacceptable non-compliant work practice
and is one of the other significant contributing factors to rainwater
ingress. ”
Whilst strongly worded, these comments have not been supported
by any evidence. There is no explanation as to what ought to have
been the correct placement of nails or “ compliant ” work , let alone
evidence showing that the work was “ totally unacceptable ” or
“ non-compliant work practice ”.
There is also no explanation how such alleged “ incorrect
placement ” or “ totally unacceptable ” or “ non-compliant work
practice ” had caused or contributed to the water entry.
No overflow system installed.
There is no explanation or evidence showing how the alleged lack
of an overflow system caused or contributed to the water entry.
Although acknowledging that he was only a “ tradesman ” and “ not a
structural engineer that would be able to provide in depth and informed
comments as to direct correlating effect between movement of the
building and damage to the slate roof ” , the report’s author was
nonetheless prepared to unequivocally claim:
“ It is my professional opinion that all rainwater ingress that is coming
into the roof has absolutely NO correlation or causal effect from
previous building works to the subfloor of this property. ” [the
emphasis was from RC himself]
He consistently attempts to justify his conclusions based on nothing
more than his years of experience in the roofing industry.
The Service has previously determined (see Determination 246385)
that whilst experience adds weight to an expert’s view, it should not be
the only reason for accepting the expert view. What ultimately
determines if an expert’s view should be accepted is whether it makes
sense in light of the surrounding circumstances.
Case No: 268014 Determination Page 10 of 11
For reasons previously outlined, it is difficult to make sense of RC’s
report when there is no evidence showing that the home has had
experiences with roof leaks previously.
In any event, the report does not consider the possibility of building
movement to cause damage to the roof. Nor does not it persuasively
dispel the possibility that building movement could cause such damage.
28. The report of the FSP’s building c onsultant also lacks persuasion because of
the absence of evidence of prior water leaks to begin with.
29. Whilst there is no doubt that the Applicant’s roof was old, this fact alone is
not sufficient to establish the operation of the exclusions and conditions
relied on by the FSP. The FSP has to persuasively establish with evidence
(not merely assume or make unsubstantiated assertions) that the leaks into
the home was due to the age, alleged faulty installation and/or alleged lack
of maintenance of the roof. Whilst the FSP’s reports makes some strongly
worded comments on the matter, they were largely unsubstantiated and
difficult to reconcile with the surrounding the circumstances.
30. The nub of the matter is that the FSP was required to show that the home
has had a history of roof leaks. This fact ought to have been simple to
establish. Photographs of the roof cavity as well as the top section of the
home’s ceiling boards were easily be available (and would arguably be the
best evidence) to establish such a claim. No such evidence was provided.
31. Apart from the fact that the Applicant’s roof was old (which the Applicant
acknowledges), I am not satisfied that the FSP has established that the roof
had leaked or has had a history of leaks prior to the repairs it undertook.
32. In the absence of evidence that the Applicant’s home has had prior
experiences with roof leaks, and as it is not an implausible proposition for
extensive structural repairs to cause further building damage, the evidence
satisfies me on the balance of probabilities that the repairs carried out by the
FSP was likely to have caused the roof to leak and consequently, the
internal damage that resulted from the leak.
Determination
33. For these reasons, I determine that:
a. The FSP is responsible for the Applicant’s roof leaks as well as for the
subsequent damage arising from the leaks.
b. The FSP is required to reimburse the Applicant for the cost he incurred
in repairing the roof leaks and it is to pay interest on such cost at the
statutory rate from the date the Applicant paid for such repairs until
such cost has been reimbursed.
Case No: 268014 Determination Page 11 of 11
c. The FSP is required to fulfil the terms of this Determination within one
(1) month of it being notified of the Applicant’s acceptance of the
Determination (should he accept it).