Home / Financial Firm (Unknown - Insurer) / Determination 258547
Determination 258547
Denial of flood water inundation claim - flood exclusion and proximate cause
Summary
A body corporate's basement car park was inundated when power was cut, stopping its drainage pumps. The FSP denied the claim as flood damage. The Panel found the proximate cause was the pump failure from the power interruption, not flood, and held the FSP liable under the policy's accidental damage terms.
Proximate cause is the effective or dominant cause, and the pump failure caused by the precautionary power interruption, not flood, was the dominant cause, bringing the loss within accidental damage cover.
Issues
- Claim denial primary · upheld
“The Panel determines the FSP is liable to meet the Applicant's loss in accordance with the terms of the policy.”
- Delay secondary · unclear
“the agent took over three months to conduct the review and in notifying the Applicant of its review decision did not inform the Applicant of the Applicant's entitlement to proceed.”
Subjects and remedies
home or building damagenatural disasterpay claim
Text of the determination
Case No: 258547 Determination Page 1 of 6
Case number: 258547
General Insurance - Domestic Insurance - Residential Strata Title - FSP
Decision - Denial of claim-Exclusion/ condition
6 January 2012
Background
1. The Applicant (a Body Corporate for a block of strata unit apartments)
incepted a residential strata insurance policy through its brokers with the
Financial Services Provider (FSP).
2. Following the devastating weather events in Queensland in January 2011
the Applicant lodged a claim with the FSP through their insura nce brokers for
damage sustained to the property as a result of the inundation of the
property.
3. According to documentation exchanged the FSP declined the Applicant’s
claim on 2 June 2011 maintaining that the policy did not respond to the loss.
4. The Applicant requested a review of the decision on 10 June 2011 and
supplied a copy of engineering reports to confirm that the loss was not
caused by flood but by loss of electricity to the electrical pumps.
5. No response was received by the Applicant until September 2011. At that
time both the FSP and the FSP’s agents responded to the Applicant. The
FSP advised by letter dated 8 September 2011 that the claim was denied on
the basis of the available evidence that the damage caused to the property
was caused by flood and the policy was unable to respond. The FSP did not
address the Applicant’s claim that the loss was due to the pumps ceasing to
operate due to the lack of electrical supply. The FSP’s underwriting agency
also wrote to the Applicant by letter dated 13 Septe mber 2011. In that letter
the underwriting agency acknowledged that the basement car park of the
block of strata units suffered damage as a result of the ingress of flood water
through the buildings upon the failure of the electricity supply to the building
causing the electric submersible pumps to fail. They also noted that the
storm water drains were incapable of removing the water because power
was turned off to the apartment blocks which stopped the storm pumps from
operating which in turn allowed under-slab drainage to accumulate in the
garage. The underwriting agents have advised the Applicant that the claim is
denied and relied on the flood exclusion. They have not addressed the issue
of the failure of the electricity supply.
Determination
Case No: 258547 Determination Page 2 of 6
6. The Panel also notes that the agent took over three months to conduct the
review and in notifying the Applicant of its review decision did not inform the
Applicant of the Applicant’s entitlement to proceed with the dispute before
the Financial Ombudsman Service (FOS).
7. This dispute is one of two disputes lodged with FOS against the FSP arising
from the same incident. An earlier dispute 246106 relates to a home
contents policy and not the residential strata insurance policy. Nevertheless,
the issues in both matters are broadly the same, and for the sake of
expediency this dispute is being considered at the same time as the earlier
dispute.
Summary of Applicant’s position
8. The Applicant acknowledges receipt of the policy documentation but
maintains that the inundation of the underground common areas (basement
car park area) was storm water from the drains.
9. The Applicant maintains flood water from the river did not reach the common
areas. It is the Applicant’s argument that the inundation was due to the
failure of the mechanical pumps which are designed to work on a continuous
basis to keep water from inundating the low lying car park and other
common areas. Water was coming from the drain and damage would have
been prevented had there not been a mechanical breakdown of the pump.
10. The Applicant relied upon the report of an engineer J & A to argue that the
system was coping very well until there was a power failure. Once the
submersible pumps ceased to work, the basement car park area was
inundated through the drainage.
11. The Applicant calculated the total loss at $22,316.61.
12. When forwarding the dispute to FOS the Applicant has also advised of the
numerous attempts made to contact the FSP’s agent to obtain a review of
the decision on 10 June 2011. They noted that they received a final decision
from the FSP on 13 September 2011 dated 8 September 2011. After
receiving that decision they received further correspondence from the agent
dated 13 September 2011. They do not understand the purpose of that
correspondence.
13. The Applicant’ s solicitors maintain that due to the long period of time, a
failure to act, failure to make a decision and ultimate disorganisation of the
agency and/or the FSP, their client is being prejudiced by the delay and
hence the need for legal representation.
Case No: 258547 Determination Page 3 of 6
Su mmary of FSP’s position
14. The FSP has not provided a Notice of Response in this dispute but has
relied upon the submission referred to in dispute 246106. As the Applicant’s
solicitor is also involved in that dispute the approach is reasonable.
15. Essentially it is the FSP’s argument that the policy excludes flood cover and
the apartments were inundated by flood. The FSP argues that the policy
does not extend to cover flood.
16. The FSP maintains the Applicant did not elect to take out machinery
breakdown cover under section 1 of the policy although it accepts that the
policy does provide additional benefits for fusion of electrical motors.
17. In any event the FSP argues that there was no breakdown but failure of the
mains power in the area which prevented the operatio n of the pumps. The
FSP accepts the reports of J & A and maintains those reports support their
position. They argue there is a deficiency in the design of the pump system
and that allowed the entry of the flood waters.
18. Insofar as the proximate cause of the damage the FSP argues that whilst the
reasoning that but for the interruption of power, the pumps would have
operated and no damage would result, is a correct factual analysis, the
interruption of the power was not causative of the damage and in any event
interruption to power supply, being consequential damage, is not covered
under the relevant policies.
Issues
19. Whether the policy extends to cover the loss suffered by the Applicant.
Reasons for decision
20. Due to the nature of the dispute this matter has bee n referred to a Panel for
Determination in accordance with the Operational Guidelines to the Financial
Ombudsman Service’s Terms of Reference.
21. The decision has been made by a Panel consisting of an Ombudsman, a
representative with extensive experience in the insurance industry and a
representative with extensive experience in consumer claims.
22. There has been a full exchange of information between the parties and the
Panel is satisfied that each party has had the opportunity to address the
issues raised.
Case No: 258547 Determination Page 4 of 6
23. There is no dispute that the insurance policy documentation had been
received, nor any dispute that the policy documentation does not extend to
cover flood.
24. As indicated in Determination 246106 due to the issues involved in this
matter, a site inspection was conducted by the Panel Chair Ombudsman.
Present at the site inspection were the Applicant’s representative, the
property maintenance manager, the Body Corporate manager and two FSP
representatives.
25. During the course of the site visit it was confirmed by the property
maintenance manager that the submersible pumps in the basement/garage
were operating effectively on the day to prevent any inundation of the area. It
was only when the power supply was shut down by the relevant authorities
that the submersible pumps ceased operating and the waters inundated the
property.
26. The property maintenance manager maintained that no water entered
through the open garage doorways but the water came up through the drains
within the garage inundating the garage and basement area to a level of
approximately 1.5 metres.
27. Once emergency pumps were obtained they were able to pump out the area
and once power was restored the submersible pumps operated to disperse
the waters. The parties accept that this is an accurate description of the
events of the day.
28. Although there have been issues raised in this matter with respect to
mechanical breakdown, the Panel, consistent with Determination 246106 is
of the view that there was no mechanical breakdown or failure. The
submersible pumps had operated to disperse the water and were operating
effectively and efficiently until there was a failure in the power supply. That
failure occurred due to a decision of the relevant authorities to interrupt the
power supply. It is likely that this was a precautionary or pre-emptive
decision and at the relevant time, the power supply was not impacted by the
flood waters. The FSP has provided no evidence to dispute this view.
29. The central issue in the Panel’s view in this dispute is whether the power
failure leading to the failure of the pumps was the proximate cause of the
loss or whether the proximate cause of the loss was the inundation of the
area after the failure of the submersible pumps by flood waters from the
Brisbane River.
30. Whilst the FSP argued the proximate cause was the flood water that
triggered the chain of events leading to the loss/damage, there is no
evidence that the flood water had impacted on the power supply company.
The decision was it appears a precautionary one.
31. The FSP does not dispute that the pumps were operating effectively to keep
the area free of inundation. The FSP concedes the correct factual analysis is
Case No: 258547 Determination Page 5 of 6
that the interruption to the power supply led to the failure of the pumps that
then allowed the flood waters to inundate the basement car park area.
32. The Panel accepts that the flood waters from the rising Brisbane River back
flowed through the drainage system consistent with the opinion offered by
the Applicant’s engineer. The engineer noted that the draining system for the
basement area is designed to cater for water inundation during events like
flooding of the river, a burst water main and any leakage from tanked
retaining walls around the basement. The inundation that occurred rose to
approximately 1.5 metres above the floor level at the lowest point of the
northern end. Once the submersible pumps had ceased to work the
basement area was inundated through the drainage system.
33. The engineer made certain recommendations to avoid a similar occurrence
in the future. In the Panel’s view these recommendations are not relevant to
the determination of the proximate cause of the loss in this dispute.
34. In determining the proximate cause the Panel has considered the arguments
put by the FSP and the Applicant. As the FSP has correctly pointed out, a
determination of the proximate cause requires a determination as to what the
effective, efficient or dominant cause is.
35. The FSP argues that in this matter, it was the flood water that triggered a
chain of events resulting in the ultimate loss. The FSP argues in these
circumstances it was the flood that was causative of the loss.
36. The evidence which is undisputed is that prior to the interruption of the
power supply the submersible pumps operated effectively to prevent any
inundation of the basement car park area. It was only after the power supply
interruption or power supply failure that the submersible pumps ceased
operating and the inundation occurred. In other words, following the logic of
the FSP, the trigger to the chain of events was the interruption to the power
supply. Once the power supply was restored the pumps operated effectively
to disperse the water.
37. Determining the issue of proximate cause is always a judgement of fact in
each particular case and is often not straight forward in its interpretation.
Whilst the Panel accepts there is argument that the proximate cause could
be considered to be the inundation through the drainage, the Panel having
looked at the information provided as a whole and having regard to the
relevant legal principles, terms of the policy, good insurance practice and
relevant prior Determinations, determines that it is fair in the circumstances
that the proximate cause be determined to be failure of the water pumps due
to the interruption of the supply.
38. The policy is an accidental, physical loss or destruction contract of insurance
between the Applicant and the FSP. In the Panel’ s view as a result of the
decision to interrupt the power supply, this has caused the pumps to fail
which has led to the damage. In the Panel’s opinion this falls within the
accidental damage provisions of the policy.
Case No: 258547 Determination Page 6 of 6
Determination
39. Accordingly the Panel d etermines the FSP is liable to meet the Applicant’s
loss in accordance with the terms of the policy.