Determination 242247
Denial of wind storm damage claim: wear and tear and defective gable wall
Summary
Wind storm damage to a four-unit apartment building, where bricks fell through a ceiling, was declined by the FSP on wear and tear, deterioration and defect exclusions. AFCA found the wall's defective state was the dominant cause and that the applicant knew of the structural problem, so the decline was upheld.
The dominant cause of the loss was the dilapidated wall structure rather than the wind, and section 46 of the Insurance Contracts Act did not apply because the applicant was aware of the defect.
Issues
- Claim denial primary · not upheld
“I find on the balance of probabilities that the dominant cause of the dislodgment was the dilapidated state of the brick wall structure.”
- Product terms interpretation secondary · not upheld
“I do not accept that the Applicant can seek assistance from section 46 of the Act to have the defect to the wall covered”
Subjects and remedies
home or building damagenatural disasterno remedy
Text of the determination
Case No: 242247 Determination Page 1 of 7
Case number: 242247
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of claim-Exclusion/ condition
30 September 2011
Background
1. The Applicant holds a Home Insurance policy which is underwritten by the
Financial Services Provider (FSP). The policy covers a double story apartment
block comprising of four apartments.
2. On 4 January 2011, the Applicant lodged a claim with the FSP for damage
caused by high winds to the building on New Years Eve 2010. A section of the
internal roofing had collapsed in one of the units.
3. The FSP arranged for an assessor, builder and engineer to view the property.
The relevant experts noted previous repairs a nd large cracking to the building.
The engineer provided an opinion that the building was in disrepair and had
defects which caused an external wall to move in high winds causing the
resultant damage.
4. The FSP declined the claim on the basis that failure to maintain, wear and tear
and deterioration were excluded from cover under the policy.
5. The Applicant disputes the FSP declinature on the basis that but for the wind
storm the damage would not have occurred.
Summary of Applicant’s Position
6. The Applicant acknowledges there was no stud frame on the gable wall.
However, the building has lasted a century and she was not to know the stud
frame was missing until the ceiling collapsed.
7. The Applicant submits the ceiling would not have fallen if the wind storm had
not occurred. The Applicant notes that a tenant heard a “thud” from upstairs
after a couple of strong wind gusts.
8. The FSP’s expert reports make note of the trees on the property which the
Applicant has now arranged to remove as demonstrated by the quotations
provided.
Determination
Case No: 242247 Determination Page 2 of 7
9. A tradesperson that attended the site after the incident indicated that prior to
any exterior work being undertaken the sewer and storm water pipes need to
be checked.
10. The Applicant has obtained and enclosed a plumber’s report which states that
the sewer pipes are out of alignment and the storm drains are blocked. The
Applicant contends that underground issues could be affecting the building.
11. The Applicant has enclosed a quotation dated 14 January 2005 from a roofing
group to remove gable timbers and eaves and rebuild the gables.
12. The Applicant notes that some of the open tracks in the walls are due to re-
wiring. However, the cracking on the inside are a consequence of the building
structure.
Summary of FSP’s Position
13. The FSP relies on the following policy terms and conditions:
“The Insured Events You are Covered For:
You are covered for the following insured events causing loss, damage or destruction
to your home or home contents (Section 1 and 2), subject to the terms, conditions and
exclusion of this policy.
- Fire
...
- Lightening or thunderbolt
...
- Explosion
...
- Earthquake
...
- Impact
...
- Theft or attempted theft
...
- Riot or civil commotion
...
- Malicious damage
...
- Storm and/or rainwater
...
- Bursting, leaking, discharging or overflowing
...
Case No: 242247 Determination Page 3 of 7
- Accidental breakage
...
- Fusion or power surge in domestic appliances and equipment
...
General exclusion
These General exclusions apply to all sections of the policy
...
This policy does not cover:
...
Any loss, damage, or liability:
- That is not directly caused by an insured event
...
Loss, damage, destruction, consequential loss or liability directly or indirectly caused
by, contributed to by, resulting from, or arising out of or in connection with:
...
- Gradual deterioration, wear and tear, fading, marking, scratching, denting, chipping
or lack of upkeep or maintenance.
...
- Inherent defects, faulty workmanship, structural defects, or faulty design. ”
14. The FSP also considers section 46 of the Insurance Contracts Act (1984) (the
Act) relevant to this matter. Section 46 of the Act provides that if a claim is
made in respect of a loss that occurred in whole or in part as a result of a defect
or imperfection in a thing and the insured was not aware of the defect or a
reasonable person in the circumstances could not be expected to have been
aware of the defect or imperfection the insurer may not rely on an exclusion
clause that refers to the condition of the thing before the contract was entered
into.
15. The FSP has enclosed claim file records from which I note the following:
File note dated 8 March 2011, confirming receipt of a Bureau of
Meteorology report stating:
“Fresh gale 62 -74km/h 5.5-7.5m Moderately high waves with breaking crests
forming spindrift. Well-marked streaks of foam are blown along wind direction.
Considerable airborne spray. Some twigs broken from trees. Cars veer on road.
Progress on foot is seriously imp eded.”
File note dated 11 March 2011, of telephone conversation between the
FSP’s employee and engineering expert. The engineer belie ved from
conversations with the Applicant that she was aware of issues with the
external wall and other issues which she was not tending too.
File notes dated 11 and 22 March 2011, of telephone conversations
between Applicant’s representative and the FSP’s employee. The
representative advised she was aware of problems with the home, in
Case No: 242247 Determination Page 4 of 7
particular the cracks and lean of the wall which was referred to as “ the
leaning tower of Piza ” (sic). The Applicant had been saving money to
slowly fix up all the issues.
16. The FSP relies on assessor reports from which I note the following:
Apartment three is original throughout and in very poor condition. There is
serious cracking to all walls, ceilings and there is evidence of previous
patching repairs throughout.
One of the panels over the window has collapsed causing part of the wall
plaster to collapse and also minor damage to adjoining panels.
The ceiling in the second bedroom was seriously bowed and in poor
condition.
17. The FSP relies on a builder’s report from which I note the following:
There is a large bow on the outside of the brick wall on the second level
near where the bricks became dislodged.
There is a crack in the wall up high and there is a 10-20mm ledge along
the crack where the bricks have shifted.
Water ingress was not a factor in the collapse of the ceiling.
It is possible wind and atmospheric conditions contributed to the incident
although the builder was uncertain as to why the bricks dislodged and the
wall moved.
18. The FSP relies on an engineer’s report from w hich I note the following:
There is no timber frame on the gable wall and the brickwork is just a
facade. The single brickwork is non-load bearing and not structural.
The size of the cracking and lean to the brickwork require urgent repairs.
As strong winds hit the side of the property on the gable wall, the wall
sways because it is not reinforced by a frame. The mortar has become
disengaged in many areas from constant movement without restraint and
eventually some of the bricks gave way.
When the timber li ning boards to the eaves were replaced this pushed the
brickwork and caused it to dislodge and fall into the ceiling of the property.
There are trees planted close to the property which could be causing
damage to the footings and base brickwork.
It is only a matter of time before the gable wall fails again.
19. The FSP’s assessor and building experts noted a lack of maintenance and
cracking to a number of areas to the front fascia and rendered staircase, some
of which had been patched over previously.
20. The gable wall has deteriorated over time with the brickwork swaying in strong
wind due to the lack of frame. Further, the mortar becoming disengaged in
many areas due to the constant movement.
Case No: 242247 Determination Page 5 of 7
21. The previously patched cracks and the Applicant’s assertion that the ti mber
lining boards on the eaves have been cut to accommodate the bulge in the
wall, both point to prior knowledge of the significant problems which were not
investigated or addressed.
22. As the Applicant had prior knowledge of the building defect, section 46 of the
Act should not apply.
23. The FSP contends that the plumbers report does not alter its position because
erosion, subsidence, landslide, settling, shrinkage, expansion, undermining,
washing away or any other earth movement caused by an escape of liquid is
covered only if occurring within 72 hours after the event. Further, the significant
cracking, patching of cracks, alterations to eaves lining to accommodate a
bulging wall and the blocked storm water drains indicate the movement has
been occurring for some time and points to gradual deterioration, wear and tear
and a lack of maintenance.
24. The FSP notes that whilst the Applicant has claimed for damage resulting from
wind storm that the expert evidence indicates that the cause of the collapsed
brickwork was due to the deterioration and movement of the wall. The
movement of the wall caused bricks to fall through the ceiling. This damage is
excluded by its policy under wear and tear, deterioration and lack of
maintenance.
Issue
25. Whether the FSP is liable to make payment of the Applicant’s claim.
Reasons for Decision
26. There has been an exchange of material between each party, and I am
satisfied each party has had an opportunity to reply to the issues raised.
27. I have read each party’s submissions and materials and will only refer to the
relevant submissions and materials raised.
28. It is an accepted principle of insurance law that the onus rests with an insured
to prove, upon the balance of probabilities, that they have sustained a loss
caused by an event insured for under the policy in force at the date of loss
[ Regina Fur Co. Ltd v Bossom (1957) 2 Lloyd’s Rep 466]
29. Where the claimant satisfies the onus of proof as above, the burden then shifts
to the insurer to establish that the claim falls within an exclusion from cover
[ Bond air Services Ltd v Hill (1955) 2 Q.B 417; Legal and General Assurance
Society Ltd v The commonwealth of Australia & Precision Cranes and Hoists
Pty Ltd (1985) 3 ANZ Insurance cases 60-621]
Case No: 242247 Determination Page 6 of 7
30. The question before me is whether the damage claimed was caused by the
wind storm as an insured event or by wear and tear, deterioration and failure to
maintain as an excluded event.
31. The Applicant has provided quotations for plumbing works , however, these
quotations only list the works to be completed and do not link the issues with
the drains specifically to any foundation issues. Further, there is no information
regarding how the sewers became misaligned and drains blocked, whether this
caused leaking into the soil, and if so, whether this affected the foundations.
There is insufficient evidence for me to consider that the windstorm relates to
this issue or if another insured event has occurred with regards to the sewers
and drains. However, it would seem that unless the Applicant could
demonstrate that the foundations were damaged within 72 hours of escaped
water it would not be covered. There would also be the additional issue of
whether the blockage and misalignment fell under the failure to maintain
exclusion.
32. The Applicant has provided a quotation for removal of trees, however, this only
lists the work to be done and does not state whether the trees caused some of
the damage to the property. The engineer has indicated the trees may be
causing issues with the foundations but the statement is far from definitive.
Furthermore, the actions of trees does not constitute an insured event.
Accordingly, any works for the removal of trees would not be covered.
33. Similarly there would appear to be no evidence that the internal cracking is
caused by the wind storm but rather just general building movement.
34. I further note the evidence that the external wall damage was caused by the
defect in timber framing rather than the wind storm.
35. The evidence before me indicates that the Applicant was in fact aware of the
issues with the external wall of her property due to prior works to the gables
and previously repaired cracking. Whilst the Applicant may have been unaware
of the exact cause, being the lack of framing to the brick wall, she was
nonetheless aware of a structural issue with the wall. Given this, I do not accept
that the Applicant can seek assistance from section 46 of the Act to have the
defect to the wall covered by the FSP.
36. The Applicant has claimed that the wind storm caused the wall damage which
in turn caused the dislodgment of bricks which fell through the ceiling. In
contrast the engineer considers the wall would have failed regardless of the
wind and the wall had been moving in the wind due to its state.
37. The wind storm has been verified as having been up to 74km/hr on the date in
question. The claim file records indicate that this wind has some force to it.
38. It seems to me that the wind storm assisted these particular bricks to dislodge
and damage the ceiling. However, the dislodgement of bricks was due to the
state of the wall rather than the wind. In ordinary circumstances a wind storm
should not cause a wall to move or bricks to dislodge. Accordingly, I find on the
Case No: 242247 Determination Page 7 of 7
balance of probabilities that the dominant cause of the dislodgment was the
dilapidated state of the brick wall structure.
Determination
39. On the basis of the available information I determine that the FSP was entitled
to decline payment of the Applicant’s claim.