Home / Financial Firm (Unknown - Insurer) / Determination 240088
Determination 240088
Denial of storm damage claim for balcony repairs
Summary
Applicant's storm claim for balcony repairs was denied by the FSP as wear and tear, deterioration and gradual damage. AFCA found the FSP proved the exclusion, so no repair payment is ordered.
Once the insured interior loss was shown, the FSP had to prove an exclusion; it proved wear and tear and gradual damage but not the structural defect exclusion.
Issues
- Claim denial primary · not upheld“the FSP has established that, on the balance of probabilities, the damage to the flooring of the balcony has been the result of wear and tear, deterioration and/or gradual damage”
Subjects and remedies
natural disasterno remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Case No: 240088 Determination Page 1 of 6
Case Number: 240088
General Insurance – Home Building – Storm damage – Policy exclusions –
Wear and tear, deterioration, gradual loss or damage, structural defect and/or
faulty workmanship
Date: 25 November 2011
Background
1. The Applicant insured his two storey home building against loss or damage
caused by insured events for $315,619 with a $100 policy excess. The policy
commenced on 9 March 2006 and had been renewed annually to 9 March
2011.
2. On 15 January 2011, the Applicant reported that his first floor balcony, living
room, bedroom, piano and portable fridge had been damaged during a storm
which occurred on or about 14 January 2011.
3. The Financial Services Provider (FSP) accepted liability for the damage to the
living room, bedroom, piano and portable fridge, but denied indemnity for the
cost of repairs to the balcony on the ground that the balcony had not been
damaged by the storm.
4. The FSP contends that the storm water escaped into the house because the
balcony had not been built according to correct building codes and the
materials used were not suitable for that type of structure.
5. The FSP maintained that the damage to the balcony was the result of faulty
workmanship, wear and tear, deterioration or gradual damage which are
exclusions of the policy of insurance.
6. The Applicant contends that when he purchased the property four years ago it
was warranted that it met the building codes of the time it was built.
Summary of Applicant ’s Position
7. In early January 2011, his locality received approximately five inches of rain
over a prolonged period. He had never had rainwater enter his home through
the roof/ceiling of the ground floor.
8. The damage occurred with only a few points leaking and by the end of the
period of rain the majority of the north wall was leaking. On the 28 January
2011, there was another heavy rainfall with 27mls in nine minutes. The area
was flooded again.
Determination
Case No: 240088 Determination Page 2 of 6
9. A building consultant eventually arrived to inspect the damage and informed
him that the rainwater had water flooded the balcony causing the rainwater to
enter his home through areas where joins in the malthoid sheeting had broken
down. He also stated the rainwater had caused the hardboard masonite flooring
to swell.
10. The FSP’s loss assessor inspected the damage and confirmed what the
building consultant had told him. The assessor also informed him that the FSP
would repair the balcony.
11. The FSP informed him however that it would accept the claim for the internal
damage to his home but not pay for the repairs to the balcony.
12. When he purchased the property he had all of the necessary searches carried
out ensuring that the building had passed all building regulations and
standards.
13. He also received advice from the Building Commission of Victoria (BCV) who
advised that the building code of 1990 states that as the balcony is not a wet
area it only needs to be waterproof.
14. The BCV also informed him that the construction of the balcony would have
been accepted when the house was built as the building code was broader at
that time. The BCV was also of the opinion that the FSP’s building consultant
had relied upon the current building code which it should not have done.
15. The FSP should meet the terms and conditions of the policy of insurance and
repair the damage to the balcony.
Summary of FSP’s Position
16. It appointed a building consultant (consultant) to identify the source of water
into the Applicant ’s home. The consultant reported that the storm water entered
through the first floor balcony. He stated that the reason for the water entry was
due to the incorrect building method used in the structure of the balcony.
17. Damage as a result of a structural defect and/or faulty workmanship is
specifically excluded under the terms of the policy.
18. The consultant reported:[80]
“ ...The balcony to the first floor has been floored (sic) with timber decking which
has then been lined with hardwood masonite (not suitable for external
applications)and the lined with sheet malthoid (a bitumen type of sheeting that
is not generally used in domestic situations). The product is not the problem, it
is the manner in which it has been installed and finished off against the
building. To remain watertight it is relying on silicone sealant that has been
applied to the join of the malthoid sheeting and front wall and windows. Silicone
is not a long term solution and in this case has broken down in parts allowing
rainwater ingress below. The actual joins of the malthoid have also deteriorated
to the point they are allowing rainwater ingress as well.
Case No: 240088 Determination Page 3 of 6
...
The facts are the building and in particular the weather/water proofing of the
area between the ground floor structure and first floor structure is and has
always been inadequate and the incorrect product (masonite hardboard
substrate) has been used.
This component of the structure is non-compliant with current and past building
codes and regulations and needs to be completely stripped and rebuilt in the
correct manner and with the correct materials.”
19. The report confirms that the balcony has not been built to current or past
building codes. This is considered to be a structural defect and/or faulty
workmanship which are excluded under the terms of the policy.
20. Further, the silicone sealant that has been applied to the joins of the malthoid
sheeting and front wall and windows, has been breaking down over time
allowing rainwater to ingress below.
21. This is gradual damage and is not a result of a single insured event. The policy
excludes damage that is a result of gradual damage, due to wear and tear and
is not a result of a single event.
22. When it denied the claim, the Applicant was invited to obtain his own builder’s
report and submit it to the FSP for review of the claim. The Applicant declined
the offer as he refused to pay for the report despite its assurance it would pay
for the report if the claim was accepted.
23. It then offered to have a second building report prepared by another
independent builder at no cost to the Applicant. However, he again rejected the
offer believing it would not be an independent assessment.
24. The Applicant has not established that the damage that occurred to the balcony
is as a result of an insured event and denial of the claim is maintained.
25. It relies on the following policy/contract provisions:
‘Glossary of words with special meaning
storm
A violent wind (including cyclones), sometimes combined with thunder, heavy
falls of rain, hail or snow; or
Thunderstorms or hailstorms, sometimes accompanied by heavy falls of rain
or snow.
The policy doesn’t (sic) cover everything
General exclusions – apply to the overall policy
...
wear and tear and lack of maintenance, including rust, corrosion,
deterioration, except in the case of escape of liquid (refer elsewhere in the
document),
gradual loss or damage of any kind;
Case No: 240088 Determination Page 4 of 6
structural defects and faulty workmanship in the construction of the building or
lack of maintenance to the building and/or contents.
Events you are covered for
...
Insured events
We will cover you for loss or damage to your building and/or contents caused by the
events detailed in this section. The loss or damage must occur at the insured
address.
...
Storm
You are covered for loss or damage as a result of storm.
You are not covered for storm damage to:
...
the building or contents as a result of water, wind or hail entering the building
due to a defect, structural or design fault that you knew about or should have
reasonably known about.’
Issue
26. Whether the Applicant is entitled to be indemnified for the cost of repairing the
balcony of his home.
Reasons for Decision
The onus of proof is on the Applicant to establish, on the balance of probabilities,
that he has suffered a loss caused by a risk insured against. Once the
Applicant has established that the loss was prima facie caused by a risk
insured against, the onus shifts to the FSP to show, on the balance of
probabilities, that the loss falls within an exclusion in the contract of insurance.
There has been an exchange of material which the parties rely on. Each party has
had access to the material on which the other party bases its case. As a
consequence it is not necessary to go into all of this material in any great detail.
27. The interior of the Applicant ’s home was damaged by rainwater escaping
through damaged malthoid floor sheeting and, prima facie, the Applicant has a
claim that falls within the terms and conditions of the policy of insurance.
28. Therefore, the onus shifts to the FSP to establish that, on the balance of
probabilities, the damage was caused by an exclusion of the policy of
insurance.
Case No: 240088 Determination Page 5 of 6
29. The FSP has relied the following exclusions to deny indemnity:
Structural defects and/or faulty workmanship;
Wear and tear, deterioration, gradual loss or damage.
Structural Defects and/or faulty workmanship
30. The FSP’s building consultant reported that the balcony did not comply with the
building code or regulations. However, the house was built in about 1990 and
the Applicant has confirmed through the Building Commission of Victoria that
the balcony conformed with the building code at that time.[75/76]
31. The FSP has not submitted any evidence of the building code that applied to
balconies in about 1990.
32. Therefore, the FSP has not met the onus on it to establish that the balcony did
not meet the building code when it was constructed in 1990 and it cannot rely
upon that exclusion to deny indemnity.
Wear and tear, deterioration, gradual loss or damage.
33. The FSP’s building consultant has stated that the malthoid sheeting covering
the masonite hardwood is no longer watertight due to the silicone sealant on
joins and at the front wall and windows breaking down in parts and allowing
rainwater ingress below. The joins of the malthoid had also deteriorated to the
point they were allowing rainwater ingress.
34. The consultant also stated that the Applicant had suggested that the rainwater
from the storm had caused the hardboard substrate to swell thus breaking the
silicone seal and sheet joins. The consultant did not accept this premise.
35. The consultant reported that the timber decking underneath the hardboard
substrate has gaps between the boards so the hardboard substrate has, since
the day it was installed been exposed to moisture from below, so that the
hardboard has been exposed to moisture over a long period of time.
36. Although the materials used as flooring to the balcony were acceptable at the
time when it was constructed, rainwater over time and weather has caused a
breakdown in the silicone sealant to the malthoid sheeting joins and at the front
wall and windows.
37. The malthoid sheeting acts as a waterproof barrier but it is only effective if the
sealant used does not breakdown. There is no evidence that the rainwater that
fell on or about 14 January 2011 caused the malthoid sealant to breakdown.
38. The Applicant was invited to submit his own builder’s report on the cause of the
rainwater leaking into his home but he has not taken up the offer.
Case No: 240088 Determination Page 6 of 6
39. On the evidence submitted, the Panel finds that the FSP has established that,
on the balance of probabilities, the damage to the flooring of the balcony has
been the result of wear and tear, deterioration and/or gradual damage which is
excluded from the cover provided by the policy of insurance.
Determination
40. Accordingly, the Panel determines that the FSP is entitled to deny indemnity for
the cost of repairs to the balcony of the Applicant ’s home.