Home / Financial Firm (Unknown - Insurer) / Determination 237693

Determination 237693

Storm water damage to ceilings denied under storm created opening and faulty workmanship exclusions

FirmFinancial Firm (Unknown - Insurer)
Decided2011-11-10
ProductGeneral Insurance · Home building and contents
OutcomeFor the complainant
Amount awarded—
Non-financial loss—
Amount claimed—
SourceAFCA PDF

Summary

The applicants claimed for ceiling water damage after a severe March 2010 storm, and the FSP denied it on the storm created opening and faulty workmanship exclusions. AFCA found the FSP had not proved the faulty workmanship exclusion applied and directed it to indemnify the applicants under the policy.

The insurer bears the onus of proving an exclusion, and it had not shown that faulty design or workmanship was the direct predominant cause of the water ingress.

Issues

Subjects and remedies

home or building damagenatural disasterpay claim

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Case No: 237693 Determination Page 1 of 6 Case number: 237693 General Insurance - Domestic Insurance - Home Building - Storm - FSP Decision - Denial of claim 28 October 2011 Background 1. This is a review of a Recommendation by the Service dated 25 July 2011 which was found in favour of the Financial Services Provider (FSP). The Applicants have rejected the Recommendation and in accordance with the Terms of Reference, the matter has been referred to me for Determination. 2. The relevant background, summaries of the parties‟ pos ition and issues in dispute have been set out in the Recommendation and for the sake of clarity and completeness, I will repeat same. 3. The Applicants held a home building and contents policy with the FSP. 4. In March 2010, the Applicants‟ home was inundated w ith water following severe weather events in Victoria. The Applicants lodged claims for contents and damage to the ceilings in the insured property. 5. After the assessment of the claims, the FSP agreed to cover the contents item , but refused indemnity for the ceiling damage on the basis there was no storm created opening and the damage resulted from a construction defect with the installation of the down pipe spreader. 6. The Applicants disputed the decision and provided reports from the builder and plumber who installed the downpipe spreader. 7. The FSP reviewed the claim and maintained its denial of the claim for water damage to the ceilings. Summary of Applicant s’ Position 8. The roof and downpipe spreader could not cope with the severe rain at the time of the event. 9. The FSP‟s submission that the roof plumbing has not been installed in accordance with the regulations is wrong. They have provided reports from the building company and plumber who installed the downpipe spreader in support D e termination Case No: 237693 Determination Page 2 of 6 of their submission. The property passed inspections after the major extension was added, with no mention of issues with the roof. 10. There have not been any leaking issues with the roof in the five years before 2010. The severity of the storm was the cause. 11. When they purchased the policy from the FSP, they were under the impression that they would be covered for situations such as water inundation from a storm. They note the FSP agreed to insure them and it sounds like everyone needs to have a building inspection by the FSP‟s contra ctor before taking cover to ensure that the FSP will not deny their claim. It is also unfair of the FSP‟s expert to disregard the findings of the builder and plumber as biased as the same argument could be made about him and the FSP. 12. They seek in the very least, to have the FSP meet the majority of the claim. Summary of FSP’s Position 13. The expert evidence indicates the downpipe spreader has not been installed correctly and does not comply with the relevant building regulations and this was the cause of the loss. 14. It notes there is no evidence of a storm created opening and therefore, it is entitled to refuse the claim under the terms of the policy. 15. The Applicants‟ experts do not comment on the cause of the inundation. It notes the reports are self-serving because the Applicants‟ experts themselves would be liable for any construction issues given they built the home. 16. The FSP relies on the following policy provisions: “ Storm If your home or contents suffer loss or damage caused by  a violent wind, cyclone or tornado  thunderstorm or hail which may be accompanied by rain or snow, or  a sudden, excessive run-off of water as a direct result of a storm in your local area … however under buildings insurance ► we will NOT cover loss or damage caused by storm to retaining walls, or when water enters through an opening that was not created by the storm. … What you are not covered for - general exclusions we will NOT cover ► loss, damage, injury or death that occurs as a result of Case No: 237693 Determination Page 3 of 6 …  faulty design or workmanship ” Issue 17. Whether the FSP is entitled to refuse the claim under the terms and conditions of the policy. Reasons for Decision 18. The relevant i nformation has been exchanged between the parties and each has had the opportunity to address the issues that have been raised. I have read all of the material that has been exchanged and I have carefully considered the parties respective submissions including the further submission by the Applicants dated 8 August 2011. 19. I have also had the opportunity to view a video recording made by Applicants of the events immediately after the onset of the subject storm including the attempt by the Applicants or members of their family to mop up and/or expel the large amount of water that had entered the premises as a result of the storm. That video recording has been made available to the FSP. 20. The storm the subject of this dispute occurred on Saturday 6 March 2010 with extremely heavy rain and probably unprecedented hail across parts of metropolitan Melbourne. It was described at the time as a “one in a hundred year storm ”. As a direct result of the volume of rain and hail, a large amount of water entered the Applicants ‟ property. The Applicants state that water has never previously entered the property before this significant event. 21. As noted in the Recommendation, the FSP submitted that because there was no storm created opening, the water entered the property through the inadequate installation of a down pipe spreader above the affected area. As noted by the Case Manger, the policy also excludes loss resulting from faulty design or workmanship. 22. The question before me is whether the water entered the property as a result of the storm created opening and/or whether the damage resulted from faulty design or workmanship. 23. A number of expert reports have been provided by the parties. These have been set out in their relevant parts and in paragraphs 19, 20, 21 and 22 of the Recommendation and which I have set out below. 24. The parties have provided a number of expert reports . The report by „IL‟, dated 31 August 2010, concludes: “A property constructed and implemented roof maintenance program would alleviate pressure on tiled roofing system. Case No: 237693 Determination Page 4 of 6 Downpipe spreaders need special attention to detail in their construction and installation as they pay a major influence to efficient water distribution onto lower roof in all applications. Therefore we believe that the conditions of downpipe spreaders and lead soaker flashings as stated by Insured to be pre existing and have been for an extended period of time. Whilst some contribution can be directly attributed to recent storms, the spreader does not readily comply with National Plumbing Code AS 3500. No storm created openings were present during site inspection. ” (sic) 25. The IL contractor provided further information to the FSP in an email dated 19 October 2010, which states: “ Here is an extract I have found from a roof tiling company which I believe they have taken from the Roof Tiling code. Hope this helps. 5.12 Discharge of Water from Upper Roof The discharge of water from upper roofs, though downpipes directly onto tiled roofs, should be avoided. However, in cases where water is discharged onto a tiled roof, the following requirements are necessary. . A spreader must be used at the base of the downpipe. The spreader must be sealed at both ends to prevent water discharge into the side lap of the tile. . Under the spreader an outer flashing (usually lead) should be installed and dressed into the profile of the roof tile. . The roof area below the spreader should be sarked for a minimum width of 1800 mm either side from the point of discharge and extended down to the eaves gutter or valley .” (sic) 26. The Applicants have provided reports from the builder of the home and the plumber who installed the roof plumbing. The „BVH‟ report, dated 28 February 2011, states: “We have been handed a copy of your letter with report addressed to the owners of the abovementioned property. We as the builders of the dwelling we too have undertaken our own investigations and now refute your denial of responsibility. This property was built some 6 years ago in accordance with all the requirements and regulations of the relevant and authorised Authorities. When there has been rain at any time during these past 6 years, water has not entered inside the property, save when the storms did occur. The report from our Licensed Plumber who also, conducted his own investigation is attached for your attention. As such we support the claim that this damage to the property was caused by the torrential storm which occurred in March of last year. We will support the owners should they wish to pursue this matter further.” (sic) Case No: 237693 Determination Page 5 of 6 27. The plumber who installed the roof plumbing, „DJPS‟, provided a report which states: “I the plumber [name] have been and inspected the down pipe in question at number [address] in doing so I have seen there is nothing wrong or illegal about this Down pipe spreader I also called the plumbing commission to ask them about this and was told That the spreader end is to be capped off to at least half the size which was 50mm in total And at a minim should be capped off to 25mm which we even capped off more as we had only a 15mm opening at the end also the letter sent to the builder refers to the wrong plumbing code the letter talks about the AS3500 but this down pipe comes under the HB39 this down pipe also has not had any water leak into the house in over 4 years and the water damage is due to the extreme amount of water from the resent storms” (sic) 28. In this matter, the Case Manager accepted that there must be a storm created opening before the policy will cover loss from water entering the property. 29. This type of exclusion is very common in home building products and there are dozens, if not hundreds of Determinations by this Service relating to disputes where an insurer relied on that exclusion. 30. The vast majority of cases involving that exclusion fail because of the application of that exclusion, but, in my view, it is not an absolute application. 31. The video recording referred to above graphically shows the large amount of water that entered the property during and immediately following the subject storm. In my view, there can be no doubt that the sheer volume of water was such, that an opening or openings within the structure were caused by the volume of water that entered the property. For example, the volume of water breached gaps in doorways and flowed into the house. 32. In addition, the FSP relies upon its expert in respect to the design and construction of the downpipe spreader and flashing in its expert report. The Applicants expert does not agree and at best, the issue between the experts is somewhat vexed. 33. The FSP carries the burden of proving the application of the exclusion and the predominant cause of the water ingress was due to poor design and construction. I note that the prospective reports post date the incident by several months. 34. Having regard to the severity of the storm event, I am not satisfied that the FSP has carried the burden of proving that ingress of water was caused by a faulty design or construction. It may be that design or construction could have been improved, but in my view, in order for the FSP to avoid liability in this case , it needed to demonstrate that the water ingress arose directly as a result of the faulty design or workmanship. I am not satisfied it has carried that burden and in the special circumstances of this case, I find in favour of the Applicants. Case No: 237693 Determination Page 6 of 6 Determination 35. Accordingly I determine that the FSP is required to indemnify the Applicants in accordance with the terms of the policy.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.