Text of the determination
Case No: 231608 Determination Page 1 of 7
Case number: 231608
General Insurance - Domestic Insurance - Home Building - Service - Service
quality
28 September 2011
Background
1. This is a review of a Recommendation dated 20 June 2011 by the Service
wherein the Case Manager made a Recommendation that the Financial
Services Provider (FSP) was not entitled to decline the Applicants‟ claim for
repair or replacement of the air conditioning system. The Case Manager further
recommended that the FSP was not entitled to apply separate excesses to the
repair cost invoices because they flowed from the same event, and she further
recommended that the FSP was not entitled to decline the Applica nts‟ claim for
gas leak repair invoice as an excluded event.
2. The Applicants accepted the Recommendation. The FSP has rejected the
Recommendation and in accordance with the Terms of Reference, the matter
has been referred to me for Determination.
3. The Background, Summary of the Parties Positions and issues are set out in
the Recommendation and for the sake of expedition and efficiency, I will repeat
same.
4. The Applicants hold a Business Insurance Policy underwritten by the Financial
Services Provider (FSP). The policy provided cover for the insured‟s business
premises between 11 September 2007 and 30 September 2009. A further
Business Insurance policy underwritten by the FSP was taken out providing
similar cover for the Applicants‟ business.
5. On 5 September 2008 the insured premise was subject to a severe localised
storm which resulted in water and mud flowing through the premise. During the
event, the Applicants‟ air conditioning system was inundated with water and silt.
6. The FSP accepted the claim and elected to repair the air conditioning unit.
7. The Applicants have since suffered ongoing mechanical issues since the
repairs and the air conditioner is still not working at full capacity. The Applicants
have sought reimbursement of repair costs as part of the original claim and/or
repairs or replacement of the air conditioning system from the FSP.
8. The FSP has declined the Applicants‟ claim for repair costs and/or replacement
of the air conditioner arising from the storm incident. The FSP relies on its
expert ‟s r eport which opined that there was no relationship between the original
incident and the ongoing breakdowns.
Determination
Case No: 231608 Determination Page 2 of 7
Summary of Applicants ’ Position
9. The FSP chose to repair the comprehensively damaged air conditioning unit for
$20,482. The FSP only obtained one quotation and since the repairs were
completed the Applicants have experienced ongoing issues.
10. The Applicants submit the air conditioning unit worked to a reasonable level for
6 months prior to it being turned off for winter. However, when the unit was
restarted in October 2009 it was not working properly.
11. The Applicants paid for a number of repairs prior to lodging a claim because the
repairs were becoming more extensive.
12. The Applicants have received two opinions that the unit should have been
replaced rather than repaired. The Applicants note that a complete replacement
of the air conditioning system would have cost $25,000.
13. The Applicants have enclosed the following invoices from a different repairer
company “GA” :
Tax invoice dated 14 April 2010 for $148.50. The invoice notes the charge
was for a site attendance and discovery of the seizure of a fan motor.
Tax invoice dated 28 April 2010 for $1,058.28. The invoice notes the
charge was to replace the fan blade.
Tax invoice dated 18 May 29010 for $429. The invoice notes the
refrigerant was short and a compressor was leaking.
Tax invoice dated 15 June 2010 for $358.38. The invoice notes a faulty
discharge „temp sensor‟ was found.
Tax invoice dated 15 September 2010 for $154. The invoice notes the unit
was out of refrigerant and the compressor was required to be
disconnected at contactor.
Tax invoice dated 20 September 2010 for $511.50. The invoice notes
pressure testing was performed to detect leaks.
Tax invoice dated 4 November 2009 for $1,246.52. The invoice notes the
PC Board was burnt out and required replacement.
14. The Applicants contend that the works by “ GA ” cover works which were
supposed to be completed by CCA. “ GA ” informed the Applicants that the unit
should have been replaced initially and these problems all stem from the
original repairs. Further, had the air conditioner been replaced it would have
had a 5 year warranty.
Summary of FSP’s Position
15. The FSP relies on the following policy terms and conditions:
“Machinery cover section
Words with special meaning
Case No: 231608 Determination Page 3 of 7
...
Insured Damage: Sudden and unforeseen physical loss or destruction of or damage to
an insured item due to any cause not excluded under this cover section (and such
extensions to this cover section) which You have selected to be insured under this
cover section of Your Policy and which occurs at the Situation during the Period of
Cover and which requires immediate repair or replacement to allow continuation of
use.
...
What You are Covered for
If any Insured Item or any part of an Insured Item suffers Insured Damage We will
indemnify You in respect of such loss or damage as provided in the basis of settlement
clause. The insurance applies whilst the insured Item is within the Situation and
working or at rest or being dismantled, moved, reassembled or reinstalled for the
purpose of cleaning, adjustment, inspection, repair, overhaul or relocation but only
after completion of successful initial commissioning at the Situation.
...
What You are not covered for under this cover section and all extensions to this cover
section
...
We will not pay for:
1) The cost of:
a) Replacement of expendable items such as belts, filters, fuses, electric heating
elements, electrical contacts, thermostats, TX valves, cutting blades, crushing
surfaces, parts made of glass, porcelain or ceramics, chains, seals, links, dies
and moulds, conveyor belting, lubricants, fuel and nay transfer media.
b) Replacement of unserviceable component parts worn through normal machine
operation.
c) Adjustment, cleaning, purging or recharging of refrigeration or air conditioning
equipment....
...
2) The cost of:
a) Maintenance work including but not limited to the tightening of loose parts,
recalibration or adjustments
...
d) Replacement or repair caused by gradual deterioration (including rust,
corrosion, erosion, oxidation or scale formation)
...
g) repair of slowly developing deformation, distortion or fatigue of any part
...
i) Repairs to valves, fittings, glands, joints, gaskets, pipes, lines and connections
which are defective or leaking.”
16. The air conditioning system was restored to its normal operation and continued
to operate without incident until November 2009.
Case No: 231608 Determination Page 4 of 7
17. At the time of assessing the claim there was no evidence indicating that
replacement was a more appropriate option than repair.
18. The FSP notes that it received a claim form requesting reimbursement of repair
invoices. The FSP made the following claims decisions in relation to the
invoices:
The claim submitted for repair costs detailed in the invoices dated 14 April
2010, 28 April 2010, 18 May 2010 and 15 June 2010 are not linked to the
damage sustained on 5 September 2008 or the subsequent repairs.
The FSP did consider that the invoices dated 14 April 2010 and 28 April
2010 constituted one claim under Machinery Breakdown. The FSP has
reimbursed the Applicants $842 (net of the $250 policy excess).
The FSP accepted the invoice dated 15 June 2010 under Machinery
Breakdown and paid $75.80 (net of the $250 policy excess).
The FSP declined the invoice dated 18 May 2010 as it related to a gas
leak which is excluded under the policy.
19. The Applicants‟ broker sought consideration for all the invoices to be treated as
the one claim on the basis of all the ongoing failures related back to the original
repairs performed after 5 September 2008. The FSP considers that
reimbursement with respect of those invoices has been made in accordance
with policy cover. Any further claims by the Applicants will be considered in
accordance with policy terms and conditions.
20. The FSP has enclosed claim file records. I note the FSP spoke with “ GA ” on 21
October 2010 and was informed by “ GA ” that the “.unit should have been
replaced (more economic). “ GA ” noted the compressors and PC boards were
replaced and that the problem is now a defective rota-lock. GA further
considered that the unit needs to be replaced.
21. The FSP has enclosed its expert‟s report dated 4 December 2010 from which I
note the following:
The expert considers that the air conditioner has been operating since
September 2008 to November 2009 without incident.
The system is old and worn out and there is no connection between the
loss of September 2008 and the current failures.
The system is partially operating and repairs (by “UC”) for $3,750 would
resolve the issue. However these repairs would not be covered as they
are attributable to normal wear and tear. “ UC ” stated that there was a gas
leak and the refrigeration suction accumulator is faulty and the system
needs replacement.
22. The FSP has enclosed a report dated 14 October 2010 from “ GA ” who states
that:
“Due to the age of the system and the cost of repairs, we believe that the
system should have been replaced initially. The refrigerant leak on the
compressor is a defect of the rotor lock system adaption as a result of the
previous works.”
Case No: 231608 Determination Page 5 of 7
23. The FSP considers that the decision to repair the system in 2008 was correct
and that it has the option to pay the reasonable cost of repair or replacement to
return the insured item to the former state of operation.
24. The FSP has enclosed the repair invoice for the original repairer. The cost of
repairs was $20,482 and covered removal and replacement of compressors
and reversing valves. Further the condenser fan coil sensors were removed
and replaced. The quotation for repairs did include a notation of R22 gas which,
for unknown reasons, was not mentioned in the invoice.
Issues
25. Whether the FSP was entitled to decline the Applicant s‟ claim for repair or
replacement of the air conditioning system.
26. Whether the FSP was entitled to apply the two separate excesses to the repair
invoices provided.
27. Whether the FSP was entitled to deny the claim for the further repair costs
referred to in invoices 9308, 9387, 9846 and 9661.
Reasons for Decision
28. I have read the exchanged material and the parties submissions including the
Applicants‟ further submission dated 3 August 2011 and the FSP‟s further
submission dated 19 July 2011 and a further expert report accompanying that
submission from “JA” dated 11 July 2011.
29. The Case Manager, by reference to the material provided to her, accepted the
report from the air conditioning contractor “GA” and found that because it was
carrying on business in the air conditioning business that it could be considered
expert in the particular field. The report of “GA” was not a report in the usual
sense but rather a quotation for repairs that needed to be carried out to the air
conditioner. As such, in my view, it cannot have the character of “independent
expert report” in respect of the issues arising from the breakdown of the air
conditioner and the subsequent repairs. Further, the quotation did not purport to
be an expert report and it must be considered in the light of its purpose. In my
view it is to be contrasted with the report somewhat belatedly supplied by the
FSP from “JA” dated 11 July 2011 that sets ou t in detail the extensive
qualifications of the author and which I accept as being more typical of the
independent expert report to be relied on. The Case Manager did not have the
benefit of “JA‟s” report and had she received that report prior to making he r
Recommendation she may well have come to a different view.
30. In its quotation dated 14 October 2010, the contractor “G” expressed the
opinion that the air conditioning system should have been initially replaced.
With the benefit of hindsight, the FSP may have formed the same view but the
fact remains that it elected, as it was entitled to do under the policy, to repair
the air conditioning system. Apart from the mere expression of opinion, the
contractor “G” did not deal in detail with all of the usual cons iderations that one
Case No: 231608 Determination Page 6 of 7
would have expected to base the opinion that the system should have been
replaced.
31. As noted in the relevant parts of the policy (Machinery Cover) and the
schedule, the policy was issued on the basis of settlement by way of
“reinstatement or replacement”. This is contrasted from settlement on an
“indemnity basis” set out on page 16 of the policy. In accordance with the
provisions relating to reinstatement or replacement, the FSP undertakes to pay
the cost of rebuilding, replacing, or repairing any damaged machinery at its
election. The FSP‟s obligation is therefore to replace or repair the damaged
item to the condition that it was prior to the damage. Having so elected, it is
bound to stand by the quality of that repair work. There is no obligation under
the policy for the FSP to replace the whole of the unit, or indeed any part of the
unit if it is capable of repair. The mere fact that a contractor with the benefit of
hindsight gives an opinion that the whole of the unit should be replaced
imposes no obligation on the FSP to do so. In my opinion, the FSP has elected
to repair and/or replace parts of the air conditioner in accordance with its
obligation under the policy. In my opinion, it was not obliged to replace the air
conditioning system as recommended by the Case Manager. I acknowledge the
point made by the Applicants in respect of the expert report by “JA” that the
expert did not inspect the unit at any time and relied upon the literature
described in the report in documents 1 – 13 on page 4 thereof. Having regard
to the details in the report, I believe it was appropriate for the expert “JA” to
adopt that course.
32. I note the chronology and discussion referred to in “JA‟s” report. In respect of
what he describes as “initial event” of 5 September, he expresses the clear
view that emersion can affect electrical components only of the air conditioning
unit, and he further expresses the opinion that it was a reasonable decision for
the insurer to proceed with reinstatement as in accordance with the policy
provisions.
33. In respect of the second incident (4 November 2009) he accepts that the
problem with the control Printed Circuit Board (PCB) was related to the original
event and the FSP has acknowledged that it will reimburse the sum of
$1,246.52 in respect of the PCB failure. The Case Manager found that this item
was related to the original breakdown (see paragraph 37) but, again, the Case
Manager did not have the advantage as I do of the report provided by the
expert “JA”. In that report, the expert expresses the opinion that because the
condenser fan motors are located 200mm above the maximum water line, the
breakdown of this item is not related to the original event but is rather related to
deterioration (corrosion) of the motor bearings from normal environmental
exposure. In the circumstances I accept the opinion of the FSP‟s expert “JA” on
this issue.
34. In respect of the loss of refrigerant due to a leak on the rota-lock connection on
the compressor, the expert “JA” sets out i n some detail the reason for
refrigerant leaks to occur from a rota-lock connection namely normal vibration
and thermal expansion that causes the locking nut to work loose over a period
of time. The expert has assumed that the rota-lock was correctly tightened by
the installing contractor and, on that basis he expresses the opinion that the
breakdown was not related to the original works.
Case No: 231608 Determination Page 7 of 7
Having regard to the aetiology and the relatively brief time of operation of this
part of the machinery after the initial repairs, I accept that it is more probable
rather than improbable that the loosening of the rota-lock was related to the
original repairs and was not a normal operating maintenance event.
Accordingly, that item of damage should form part of the original claim and
should be paid for by the FSP in the sum of $390 (invoice 9486) and not be the
subject of any imposition of additional excess.
35. In respect of the fifth incident (replacement of a discharge sensor) and sixth
incident (investigation of a refrigerant leak), I accept the opinion set out in detail
of “JA‟s” report that neither of these incidents are related to the original event,
but are rather due to deterioration, corrosion, vibration and expansion that
would be consistent with equipment aged seven years or more.
Determination
36. The FSP is not required under the terms of the policy to replace the
refrigeration unit.
37. The FSP is required to reimburse the Applicants in the sum of $1,246.52 in
respect of the PCB failure.
38. The FSP is not required to indemnify the Applicants in respect of the condenser
fan motor (third incident).
39. The FSP is required to indemnify the Applicants for the gas leak in the sum of
$390 without reduction for any excess (fourth incident).
40. The FSP is not required to indemnify the Applicants in respect of the
replacement of the discharged sensor (fifth incident) nor the investigation of the
refrigerant leak and the costs related thereto (sixth incident).