Underground electrical cable damage claim refused as not a covered storm loss
Summary
The applicant claimed for a burnt-out underground mains cable after heavy rain and sought $4,883.98 for the repair. AFCA found he had not shown the loss was caused by a storm or other insured event, and accepted the FSP's expert evidence that the fault was pre-existing.
The insured bears the onus to prove an insured event, and the applicant provided no independent objective evidence that water caused the cable failure.
Subjects and remedies
home or building damageno remedy
Text of the determination
Case No: 227225 Determination Page 1 of 6
227225
General Insurance - Domestic Insurance - Home Building - FSP Decision -
Denial of claim
22 June 2011
Background
1. I have reviewed all the material submitted by the parties and save where I
make note specifically, I am satisfied the Background as set out in the
Recommendation is accurate and is as follows.
2. The Applicants are a married couple who held a home buildings insurance
policy issued by the Financial Services Provider (FSP). The policy provided
cover on a defined events basis.
3. On 20 August 2010 the male Applicant (the Applicant) lodged a claim on the
policy in respect to damage to an underground electrical cable, the repair
having been authorised by the Applicant several days earlier. The loss
description recorded by the FSP is as seen below:
“Torrential rain storm, caused the conduit cables in the ground to be damaged,
and power loss for some 8 hours to the home occurred. Insured had repairs to
the conduit done.”
4. The FSP refused the claim on the basis the loss was not due to any event listed
as covered under the policy.
5. The Applicant does not agree the FSP correctly identified the cause of the loss
and does not agree the FSP is entitled to refuse the claim. The Applicant
nominates the amount in dispute to be $4,883.98.
6. The A pplicant does not agree with the FSP’s decision, hence the dispute, which
was the subject of a Recommendation.
7. The Recommendation was in favour of the FSP and was not accepted by the
Applicant. The FSP accepted the Recommendation.
Summary of Applicant’s Po sition
8. I have reviewed all the material submitted by the parties and save where I
make note specifically, I am satisfied the Applicant’s position as set out in the
Recommendation is accurate and is as follows.
Determination
Case No: 227225 Determination Page 2 of 6
9. When the power supply failed an emergency electrician attended and stated
water had damaged the main cable under the driveway.
10. The FSP has alleged the problem was due to a kink in the cable that would
have occurred some 17 years earlier but does not appear to be certain as to
whether it was the conduit or the cable that was damaged at the location under
a concrete slab. The electrician that attended was able to make the necessary
repair without tearing up 20 metres of concrete driveway.
11. The FSP requires him to provide expert advice as to the cause of the problem.
The electrician is a tradesman with more than 30 years experience and he
spent nearly three days at the site. Given his experience, this electrician can
only be regarded as an expert witness.
12. The electrician advised that he did not identify any kink in the cable or conduit.
The conduit is still in place and it has the replacement cable running through it.
How the FSP’s assessor could conclude there was a kink in the underground
conduit that cannot be seen is unknown.
13. The FSP’s electrician w as at the site for no more than 10 minutes; he spoke to
the Applicant's son and looked around before taking a few images and then left.
14. The Applicant’s electrician commented that the FSP’s electrician’s report was
gross speculation as there was no way to tell if the alleged damage was
present under the slab. If the original installation workmanship was faulty, this
would have surely manifested many years earlier.
15. In the event there was a fault present before the storm, it was impossible to
know this. Section 46 of the Insurance Contracts Act 1984 would prevent the
FSP from refusing the claim on the basis the policy excluded loss due to a fault
or pre-existing defect.
16. The electrician did not agree that wear and tear to the cable of conduit would
be present in cables and conduit that was only 15 years old. It is more likely the
damage was due to water entering the cables due to the heavy rainstorms in
the area over the preceding two days.
17. Two events were connected with the entry of water to the cable:
1) The house is on a steep hillside and the neighbour on the high side
cleared his land allowing a much greater flow of rainwater into their
property below.
2) There was extremely heavy rain for two days before the power failure.
18. While he was told by the FSP that its assessor had spoken to the electrician
who repaired the cable, that electrician denied any such conversation had
taken place.
19. Water entry due to the storms was the cause of the loss, not an obscure and
unidentified kink in the conduit or cable, and he does not agree the FSP is
entitled to refuse the claim.
Case No: 227225 Determination Page 3 of 6
20. The Applicant rejected the Recommendation and indicated in emails dated 11
March and 26 March that he would talk to the electrician and get some
additional expert opinions as to the cause of the problem but no expert opinion
was submitted.
21. In an email dated 1 May, the Applicant indicated he had spoken to the
electrician and wrote:
“I have spoken again to the electrician who, at the time, not only fixed the
problem but confirmed to me, from his past experiences, that the job he was
doing would be covered by my insurance company. He now seems reticent to
put anything in writing because as he says he was not there at the exact time of
the storm or actually observed the fault occurring – he has gone from being very
supportive to being extremely unhelpful….
He did state, to me, that if the opening in the cable had occurred when the cable
and conduit were first laid, as assumed by the [FSP] electrician, then the
problem would have surfaced many years prior to when it did – the conduit would
not move under a cement slab unless an external event had caused some
damage.”
22. In a further email dated 6 May 2011, the Applicant wrote further:
“No one from [FSP] or my electrician were onsite when the storm happened or
for that matter when the electricity was first installed, so we are all guessing as to
what the cause was.”
Summary of FSP’s Position
23. I have reviewed all the material submitted by the parties and save where I
make note specifically, I am satisfied the FSP’s posit ion as set out in the
Recommendation is accurate and is as follows.
24. The policy provides cover against loss caused by any of the events listed as
covered under the contract. The invoice from the emergency electrician
included the notation “ Called Friday 3.00pm, mains cable to house burnt out
(under drive, water damage).
25. The assessor is a qualified electrician and his report provided included the
information quoted below:
“The house has a long drive and the mains go to the meter box outside and from
there go to into the distribution board in the house probably about 20m away. The
electrician ran temp power to the house so they had something over the weekend.
Came back Monday to cut up concrete near meter box to get to the bend of the
conduit – they were afraid they may have to rip the entire drive up but managed to
pull the cables out and pull new ones through. When old cables pulled out the 2
phases neutral and earth was burnt and moulded together. The electrician has
replaced the safety switch due to the number of times it tripped.
…from my experience…there was more than likely a kink or some damage to one of
these phases – probably from initial installation when the cable was pulled through
either rock in conduit or it has caught the edge of the conduit when getting pulled
Case No: 227225 Determination Page 4 of 6
through, then moisture has got into the conduit causing it to arc and go to earth
resulting in the circuits shorting out. There was some rain in the area around those
dates. However it has held up this long – house at least 15 – 20 years old. Water
didn’t cause the kink or damage to cable but once water got in there the short
occurred.
Conduits are never waterproof and the insulation of the cable is the waterproof
barrier for the copper, if the cable insulation was in good condition the short would
not have occurred .”
26. The Applicant lodged the claim on the basis the loss was caused by storm but
there is no evidence to establish the cables under the driveway were storm
damaged.
27. For water to have penetrated the cables, there must have been a fault in the
cables to allow the water penetration; it is not feasible that water alone would
be the cause of the cable insulation failing.
28. The assessor considers it probable the cause of the failure was damage that
occurred when the cable was originally installed. Regardless, if there was no
such damage to the cable insulation, then the failure can only have been due to
wear and tear, deterioration or faulty workmanship. Losses from all these
causes are excluded under the policy.
29. There is no evidence to establish the damage was due to storm or any other
event covered by the policy and the claim cannot be accepted.
30. The FSP relies on the following policy provisions:
“ Storm
If your home or contents suffer loss or damage caused by
a violent wind, cyclone or tornado
thunderstorm or hail which may be accompanied by rain or snow, or
a sudden excessive run-off of water as a direct result of a storm in your local area
…
We will under buildings insurance
- rebuild or repair that part of your home that was damaged
…
however under buildings insurance
we will NOT cover loss or damage caused by storm to retaining walls, or when
water enters through an opening that was not created by the storm.
…
Glossary
Storm
is a violent wind, cyclone, tornado, thunderstorm or hail which may be accompanied by
rain or snow, or a sudden excessive run-off of water as a direct result of a storm in
your local area. It does not include persistent rain by itself.”
Case No: 227225 Determination Page 5 of 6
31. The FSP accepted the Recommendation and did not provide any further
documentary information in support of its position save to rebut the Applicant’s
position in an email dated 12 May by saying; “As the Applicant has not
submitted any new expert evidence I have no further comment to make.”
Issue
32. Whether the policy covers the claimed loss.
Reasons for Decision
33. There has been an exchange of material between each party, and I am
satisfied each party has had an opportunity to reply to the issues raised.
34. Each FOS case is decided on its merits, taking into account the facts of the
case. I have reviewed all the material submitted by the parties both before and
after the Recommendation was issued, in order to reach my decision. I will only
refer to the relevant submissions and materials raised.
35. In a claim such as this, the Applicant has the onus to prove the loss was from
an insured event, in this case, a storm. The policy terms make it clear that the
FSP will not cover loss when water enters through an opening not created by
the storm.
36. The Applicant relied on his electrician to support his case. However, there is no
direct evidence from that electrician. The electrician did not provide a written
statement. There is an invoice dated 17 August 2010 from him, but the invoice
mainly details what work was done after the storm and the cost of the work.
The invoice states; “mains cable to house burnt out (under drive, water
damage)”, but that is the only commentary.
37. After the Recommendation, the Applicant indicated he would provide an expert
opinion but he did not. He said the electrician was no longer helpful. He also
said the electrician did say to him that if the opening in the cable and conduit
had occurred when it was first laid, then the problem would have happened
earlier.
38. The FSP relied on it assessor, a qualified electrician, who went to the site and
wrote a report dated 24 August. The relevant extracts from the report are set
out above. He says he spoke to the Applicant’s electrician, which the Applicant
refutes. In any event, he says that in his experience, for this event to have
occurred, that there was already damage to the cable, possibly at the time it
was installed. He says cables have waterproof barriers and so if the cable was
not already damaged, then the water could not have got in and caused the
short. He was of the opinion that water itself could not have created the
opening in the cable. He admits neither he nor the electrician who fixed it saw
the posited pre-existing damage, as the cables had shorted and were fused
together.
Case No: 227225 Determination Page 6 of 6
39. The A pplicant says that this is just “guessing” and if the cable/conduit were
damaged as suggested, then why did not this happen earlier? I cannot answer
this question but do not have to. I can only make a decision on the material
before me. The Applicant has provided no independent objective evidence to
support his case. The FSP has provided a report from an experienced
electrician. The expert has an explanation for how the loss occurred which I find
credible. On the material before me, I have trouble accepting that water by itself
could cause an opening in a cable or conduit.
40. Accordingly, I find the Applicant has not discharged he onus which rests with
him to establish a loss which is insured against.
41. In the circumstances, I do not need to deal with the other issues raised
regarding the wear and tear exclusion and section 46 of the Insurance
Contracts Act.
Determination
42. I determine that the FSP is entitled to refuse to accept the claim.