Home / Hollard / Determination 1005008
Determination 1005008
Claim for garage cracking said to be caused by earthquake declined on causation and exclusions for wear and tear, corrosion
Summary
The complainant claimed for garage cracking he attributed to a September 2021 earthquake. AFCA found the damage was caused by long-term lintel corrosion and construction issues, not the earthquake, and upheld the insurer's denial.
The complainant did not establish a claimable loss on expert evidence, and the wear and tear, rust and corrosion exclusion alternatively applied.
Issues
- Claim denial primary · not upheld“The insurer is entitled to deny the claim; complainant has not established a claimable loss and wear and tear/corrosion exclusion applies.”
Subjects and remedies
health or medicalhome or building damagenatural disasterno remedy
Related
Text of the determination
Determination
Case number 1005008
Financial firm Hollard Insurance Partners Limited
Determination | Case number: 1005008 Page 1 of 6
Case number: 1005008 26 April 2024
1 Determination overview
1.1 Complaint
The complainant holds a home insurance policy underwritten by the financial firm (insurer).
The complainant claims the property was damaged by an earthquake on 22 September 2021.
There is no dispute that an earthquake occurred, but the insurer says the damage was not
caused by the earthquake and is excluded from cover under the policy. The insurer also relies
on policy exclusions for defects, wear and tear, corrosion and maintenance issues.
The complainant disputes the insurer’s decision and wants the claim paid in full. He says the
damage was caused by the earthquake and subsequent tremors and the insurer is liable.
1.2 Issues and key findings
Has the complainant established a claimable loss?
No. The expert evidence establishes that the damage was not caused by the earthquake and
was caused by construction and maintenance issues, including corrosion of the lintel and
inadequate movement joints at the base.
Is the insurer entitled to rely on policy exclusions?
Yes. The damage to the property was caused by one or more excluded perils, including wear
and tear, corrosion and/or deterioration.
Why is the outcome fair?
The complainant has not established a claimable loss under the policy and the insurer has
shown that the damage is excluded from cover. It is fair for the insurer to rely on the terms
and conditions of the policy to deny liability for the claim.
1.3 Determination
This determination is in favour of the insurer.
The insurer is entitled to deny the claim and no further action is required.
Determination | Case number: 1005008 Page 2 of 6
2 Reasons for determination
2.1 Has the complainant established a claimable loss?
No. The expert evidence establishes that the damage was not caused by the earthquake and
was caused by construction and maintenance issues, including corrosion of the lintel and
inadequate movement joints at the base.
Complainant bears onus of establishing a claimable loss
It is accepted insurance law that an insured has the initial onus to show, on the balance of
probabilities (that it is more likely than not), that the loss or damage claimed falls within the
terms of the policy. Where this is established, the onus then shifts to the insurer to prove that
an exclusion applies if it seeks to deny or limit its liability for the loss.
There is no dispute that the insurer provided the complainant with the policy documents. The
policy covers several insured events including earthquake, unless a general exclusion applies
(see page 31).
There is no dispute that an earthquake occurred on 22 September 2021. However, the
complainant did not lodge the claim until April 2023. The complainant says he noticed
cracking to the garage and brick work has shifted when new garage roller doors were
installed in April 2023.
The complainant must establish that the damage claimed falls within the scope of the policy.
Expert evidence regarding the cause of damage
The insurer relies on reports from a builder (DW) and an engineer (SH). Both experts confirm
that there was an earthquake on 22 September 2021.
The DW report identifies structural cracking to the garage at the property but notes that it
does not appear recent. DW recommended an engineer report on causation.
The SH report includes seismological data and information obtained from Geoscience
Australia and states that the intensity of the earthquake was not sufficient to cause building
damage at the property. The engineer concluded that:
The cracking damage to the garage has not been caused by the claimed
earthquake event.
Instead, it is our opinion that the cracking damage to the garage brickwork has
been caused by construction issues including a lack of weatherproofing to the top
of the parapet, a lack of maintenance to the corroding lintel and inadequate
provisions for movement between the driveway and garage.
SH provided a supplementary report which includes photos captured on Google Maps from
March 2021, which show that the damage predated the earthquake event. SH reported that:
The extent and type of cracking is not consistent with the claimed earthquake
event, instead, is it consistent with long-term corrosion of the steel lintels which
has caused the steel to expand, resulting in cracking to the brickwork mortar.
Determination | Case number: 1005008 Page 3 of 6
The complainant has not provided any expert evidence regarding the cause of the damage.
Complainant has not established a claimable loss
Having considered all available evidence, I am not satisfied on the balance of probabilities
that the complainant has established a claimable loss under the policy.
The SH report is detailed, well-reasoned and supported by photographs. The SH report also
clearly explains the relevant seismic data and the likelihood of damage based on mapping
and zoning obtained from Geoscience Australia, together with contributing factors including
construction issues, soil reactivity and normal ground movement.
The complainant has not provided any expert evidence to refute these findings. He also has
not provided any proof that the damage was not present before the earthquake (such as
photographs or inspection reports). I acknowledge the complainant has health concerns and
says he cannot afford to obtain an expert report, but this does not negate the insurer’s expert
evidence.
In the circumstances, I accept the findings by SH that the proximate cause of damage to the
garage was not the earthquake, but long-term corrosion of the steel lintels which has caused
expansion and cracking of the brickwork. The proximate cause is not necessarily the first or
last or the sole cause of the loss. It is the effective, dominant or operative cause of the loss.
I also accept that the lack of isolation joints between the garage and the driveway contributed
to the damage.
The damage therefore happened over time and the complainant has not established that it
was caused by the earthquake event. It follows that the complainant has not established a
claimable loss under the policy and the insurer is entitled to deny the claim.
2.2 Is the insurer entitled to rely on policy exclusions?
Yes. The damage to the property was caused by one or more excluded perils, including wear
and tear, corrosion and/or deterioration.
Insurer has established that a policy exclusion applies
The insurer says the damage was not caused by an earthquake but by a combination of
excluded perils including defects, wear and tear/corrosion and lack of maintenance.
I have already found that the complainant has not established a claimable loss. The insurer is
therefore entitled to deny the claim and it is not necessary to consider whether any exclusions
apply. However, for the sake of completeness, I am also satisfied the claim is excluded.
Pages 54 of the policy sets out the relevant exclusions:
1. defects, structural or design faults, faulty workmanship or faulty design. We will
only apply this exclusion where you knew or should reasonably have known the
issue existed.
4. wear and tear, rust, corrosion and/or deterioration (except in some instances
relating to 'Sudden escape of liquid' and 'Legal liability' claims), but we will only
apply this exclusion if the loss or damage is directly caused by one or more of
these factors.
Determination | Case number: 1005008 Page 4 of 6
5. you not maintaining your buildings and/or contents in reasonably good repair
and condition;
Based on the findings in the SH report, I am not persuaded that exclusion 1 applies. There is
no evidence the complainant was aware of any construction issues with the garage, including
the lack of weatherproofing above the parapet and lack of isolation joints at the base.
However, I am satisfied on the balance of probabilities that the cracking to the property was
attributable to wear and tear and corrosion of the lintel, which has been occurring for some
time due to water penetration. I am therefore satisfied that the insurer has established that
exclusion 4 applies and the insurer can rely on this as an alternative basis to deny the claim.
2.3 Why is the outcome fair?
The complainant has not established a claimable loss under the policy and the insurer has
shown that the damage is excluded from cover. It is fair for the insurer to rely on the terms
and conditions of the policy to deny liability for the claim
Determination | Case number: 1005008 Page 5 of 6
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
Determination | Case number: 1005008 Page 6 of 6
3.2 Summary of expert evidence
Record Key points
Insurer’s builder ( DW )
Inspection Report
11 - 0 4 - 2023
The property was affected by a magnitude 5.9 eart hquake on 22
September 2021 at approx. 9.15am
T he re is cracking to the property , which does not appear recent
E ngineer to determine/confirm cause of damage
Insurer’s expert (SH)
Engineer’s Report
19 - 06 - 2023
On 22 September 2021 at approximately 9:15am, Geoscience
Australia rec orded a 5.9 (Mw) Magnitude earthquake in Victoria
P roperty is approxi mately 130km from the epicentre in a light zone
of intensity. Shaking would have been felt but not expected to
cause damage .
B ased on the Geological Survey Maps, local knowledge and
ex perience, the site is expected to have highly reactive soils.
Reactive soils will swell upon wetting and shrink upon drying.
D ifferential variations in the fo undation soil moisture content can
cause building movement damage.
The garage consists of masonry single skin with engaged piers.
Cracking is evident at the bottom of the southwest brick pier.
Damage to the property has not been caused nor contributed to
by the earthquake of 22 September 2021.
Historic i magery show s cracking was evident prior to the event
If the earthquake caused damage, would expect to see d amage to
the property’s more brittle mat erials such as the internal lining
Damage to the garage parapet caused by construction issues.
No mortar weat hering, damp - proof courses or flashing has bee n
installed on top of the parapet. A s a result the top of the lintel
below has corrode d and expanded causing movement/ cracking.
The concrete driveway abuts the brick pier, and no isolation joint
has been installed between them . This has hindered differential
movement which has cracked the brickwork and paving.
Insurer’s expert (SH)
Supplement ary Report
25 - 10 - 2023
P hotos captured on Google Maps from March 2021 show :
> the mortar cours e is wider at the corner openings where the
roller door lintels are supported on the brick walls
> the wider brick courses (caused by steel corrosion) were evident
prior to the earthquake event ( Sept ember 2021).
T he extent and type of cracking is not consistent with the claimed
earthquake event, instead, is it consistent with long - term corrosion
of the steel lintels which has caused the steel to expand, resulting
in cracking to the brickwork mortar.
The cracking adjacent to the garage openings has been caus ed
by construction issue s , such as inadeq uate weatherproofing
allowing corrosi on of the lintels.
L ong - term, normal and expected ground movement has
exacerbated the cracked paving at the junction bet ween the
concrete paving and brick garage which has n o isolation joint.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.